SENTRONIC M-SYSTEM DANAGE User manual

MODEL: MRP6
Final Control Elements
MINI-TOP ELECTRONIC ACTUATOR
(rotary type)
Functions & Features
• Small-size control valve actuator
• Electrical positioner incorporated
• 1/1000 high resolution
• Easy adjustment: electronic limiter at the valve open &
closed positions
• Overload protection
• Various power inputs
• CE marking available for 24 V DC power
Typical Applications
• Actuator for automatic control valve in pilotplants
• Air-conditioning in buildings or plants
• Micro-flow control for pharmaceutical injection
• For small-size control valves
MODEL: MRP6–[1][2][3][4]–[5][6][7]
ORDERING INFORMATION
• Code number: MRP6-[1][2][3][4]-[5][6][7]
Specify a code from below for each [1] through [7].
(e.g. MRP6-16LT-A0R)
• Special input range (for codes Z and 0)
[1] SPAN
1: 45 to 90 degrees
2: 90 to 180 degrees
[2] OPERATION TIME, TORQUE
3: 4 seconds / 90°, 10 N·m
4: 7 seconds / 90°, 16 N·m
6: 13 seconds / 90°, 33 N·m
[3] SEQUENTIAL CONTROL SIGNALS
L: Full-open/-closed signal
F: Forced open/close signal
B: Full-open/-closed and forced open/close signals
(Select 'With Terminal Box.')
0: Without
[4] TERMINAL BOX
T: With
0: Without
[5] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)
Voltage
6: 1 – 5 V DC (Input resistance approx. 1 MΩ)
0: Specify voltage (See INPUT SPECIFICATIONS)
[6] CE MARKING
C: With
0: Without
[7] POWER INPUT
AC Power
K3: 100 – 120 V AC
(Operational voltage range 90 – 132 V, 47 – 66 Hz)
(Not selectable for CE)
L3: 200 – 240 V AC
(Operational voltage range 180 – 264 V, 47 – 66 Hz)
(Not selectable for CE)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
GENERAL SPECIFICATIONS
Degree of protection: IP55
Action: Direct or reverse; field selectable with DIP switches
(factory set to “reverse”)
(In “reverse” action, the output stem seen from the cover
turns counterclockwise with an input signal increase.)
Operation at abnormally low input: Counterclockwise turn,
clockwise turn or stop; field selectable with DIP switches
(factory set to“clockwise”)
Note: Counterclockwise or clockwise if seen from the cover.
Detectable input drop level: -16 ±2.5 %
Electrical connection
•No terminal box
Wiring conduit: G 1/2 female; cable connector with 1 meter
wire (0.5 mm2) provided
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: MRP6
•Terminal box
Wiring conduit: G 1/2 female (two)
Terminal screws: M3 pillar terminal
(Sequential control signal suffix code B)
M3 chromated steel
(other terminal box types)
(torque 0.5 N·m)
Housing material: Diecast aluminium
Drive: Stepping motor
Position detection: Potentiometer
Deadband: 0.1 – 4.5 % adjustable (factory set to 1.5 %)
Restarting timer: 0 – 10 sec. adjustable
(factory set to 1.5 sec.)
Isolation: AC power to signal
Zero adjustment: 0 – 25 %
Span adjustment: 50 - 100 %
Protective functions: Overload protection
Power indicator: Green LED turns on with power supplied.
Input indicator: Green LED turns on with normal input
Status indicator LED: Red light blinks in 2 sec. intervals in
normal operations; blinks in 0.5 sec. intervals when a
foreign object is detected mechanically caught inside.
Manual operation: Available
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated (250 Ω)
■ DC Voltage: 1 – 5 V DC or specific range within 0 – 5 V
DC, minimum span 1 V
(For a current input, convert the current to a voltage with
250 Ω)
Input resistance: Approx. 1 MΩ
■ Forced open/close signal:
Dry contact inputs to command clockwise and
counterclockwise turns
Rating: 5 V DC @ 2.5 mA
OUTPUT SPECIFICATIONS
■ Operation Time & Torque (at rated power voltage)
MRP6-x3: 4 seconds / 90° 10 N·m (7.38 ft·lbs)
MRP6-x4: 7 seconds / 90° 16 N·m (11.8 ft·lbs)
MRP6-x6: 13 seconds / 90° 33 N·m (24.3 ft·lbs)
■ DC Voltage: 1 – 5 V DC (not isolated)
With “direct” action, 5 – 1 V DC position output is provided
proportionally to 4 – 20 mA DC (1 – 5 V DC) input.
Load resistance: ≥ 5 kΩ
■ Full-open / -closed signals: Limit switch contact
Rating: 125 V AC @ 0.75 A (cos ø = 1)
30 V DC @ 0.6 A (resistive load)
Mechanical life: 3 × 107 cycles
Maximum operation frequency: 60 cycles/min.
INSTALLATION
Power consumption
•AC: Approx. 25 VA
•DC: Approx. 0.6 A
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: 0.5 G max.
Mounting position: All directions
Do not mount the actuator with its output stem or cable
connector on the upside if the actuator is to be exposed to
dripping water.
Weight
DC powered: 2.7 kg (5.96 lbs)
AC powered: 2.8 kg (6.17 lbs)
Add 0.7 kg (1.54 lbs) for the terminal box.
PERFORMANCE
Resolution: 1/1000 or 0.09°, whichever is greater, with 0.1
% deadband setting
Insulation resistance
•AC powered: ≥ 100 MΩ with 500 V DC
(signal or metallic housing to power)
≥ 100 MΩ with 100 V DC
(signal to metallic housing)
•DC powered: ≥ 100 MΩ with 100 V DC
(signal or power to metallic housing)
Dielectric strength
•AC powered: 1500 V AC @ 1 minute
(signal or metallic housing to power)
100 V AC @ 1 minute
(signal to metallic housing)
•DC powered: 100 V AC @ 1 minute
(signal or power to metallic housing)
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007
EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
EN 61010-1: 2001
Measurement Category II
Pollution Degree 2
Full-open/-closed signal to other, power or metallic
housing: Reinforced insulation (125 V)
TERMINOLOGY
• Overload (Lock) Protection
The Mini-Top Series is equipped with a protection circuit
against overload caused by for example the valve catching
an alien substance.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: MRP6
When an overload is detected, the Mini-Top stops supplying
power to the motor and the status LED blinks in 0.5 sec.
intervals.
The protection is reset automatically with applying opposite-
direction input signal or turning the power off and
restarting.
• Restarting Timer
The Mini-Top Series is equipped with a timer circuit which
gives an interval period (0 – 10 seconds) between stop-
restart actions to prevent the motor and other internal
components from overheating.
It is recommended to set a long restarting time when the
ambient temperature and/or the temperature of flow
material is high.
• Electronic Limiter
This model is equipped with electronic limiters in order to
prevent mechanical locks when the input goes below 0 % or
above 100 %.
Limiters are set at approx. -0.5 % for the full-closed side,
approx. 100.5 % for the full-open side.
TERMINAL CONNECTIONS
black (1) +(U)
–(V)
+
COM1
+
COM2
white (2)
red (3)
green (4)
yellow (5)
blue (6)
gray (7)
brown (8)
(1) to (8): Terminal No. of terminal box.
Full-open/-closed signals and forced open/close signals are optional.
POWER
INPUT
POSITION OUTPUT (1 – 5V DC)
FULL-OPEN or
FULL-CLOSED
SIGNAL
(
output stem
)
turned CCW
(
output stem
)
turned CW
+(U)
–(V)
+
COM1
+
COM2COM1
POWER
INPUT
POSITION OUTPUT (1 – 5V DC)
FULL-OPEN or
FULL-CLOSED
SIGNAL
(
output stem
)
turned CCW
(
output stem
)
turned CW
COM1
FORCED
OPEN/CLOSE
SIGNAL
FORCED
OPEN/
CLOSE
SIGNAL
(
output stem
)
turn CCW
(
output stem
)
turn CW
(
output stem
)
turn CCW
(
output stem
)
turn CW
1
3
2
4
6
5
7
8
11
9
10
• With Both Full-open/closed Signal
and Forced Open/Close Signal
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: MRP6
DIMENSIONS unit: mm (inch)
146 (5.75)
15 (.59) dia.
22 (.87)
23 (.87)
CABLE CONNECTOR
w/1 meter (3.28 ft) LEADWIRE
12 –0.043 sq.
70 (2.76) dia.
0
MANUAL HANDLE STEM
6 (.24) sq.
4–M6 12 (.47) deep
90 deg. pitch
YOKE CONNECTION
20
(.79)
110 (4.33)136 (5.35)
199 (7.83)
16 (.63)
YOKE SURFACE
146 (5.75)
15 (.59) dia.
22 (.87)
67 (2.64)
12 –0.043 sq.
70 (2.76) dia.
0
MANUAL HANDLE STEM
6 (.24) sq.
2–G 1/2 CONDUIT
4–M6 12 (.47) deep
90 deg. pitch
YOKE CONNECTION
110 (4.33)136 (5.35)
199 (7.83)
16 (.63)
YOKE SURFACE
35 (1.38) 60 (2.36)
7.5 (.30)23 (.91) 34 (.134)
20
(.79)
32.5 (1.28)
Cable connector or leadwires not provided with terminal box.
■TERMINAL BOX TYPE
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: MRP6
SCHEMATIC CIRCUITRY
Hi / Lo
Limiter
Motor Control
Logic
Motor
Driver
Position
Detector
RESTART
TIMER
DEADBAND
ADJ.
Switching
Regulator
+
COM1
+ (U)
– (V)
Power
Circuit
SZ
Position
Output
+
Input
Circuit
INPUT
4 – 20mA DC
(1 – 5V DC)
COM1
CCW
CW
FORCED
OPEN/
CLOSE
SIGNAL
COM2
CCW
CW
FULL-OPEN
or
FULL-CLOSED
SIGNAL
POSITION
OUTPUT
1 – 5V DC
POWER
MODE
SELECTOR
POWER
INPUT STATUS
POT
MOTOR
LIMIT
SW
Full-open/-closed signals and forced open/close signals are optional.
Disregard the switching regulator circuit for DC power input.
Specifications are subject to change without notice.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MRP4 / MRP5 / MRP6
P. 1 / 8EM-4824 Rev.7
MINI-TOP ELECTRONIC ACTUATOR
(rotary type) MODEL
MRP4/MRP5
/MRP6
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Mini-Top........................................................................ (1)
The Mini-Top is not provided with a yoke or other compo-
nents required for mounting it to a valve. They are to be
provided by the user.
■MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
POINTS OF CAUTION
■CONFORMITY WITH EC DIRECTIVES
•ThisequipmentissuitableforuseinaPollutionDegree
2 environment and in Measurement Category II, with the
maximum switching voltage of 125V. (Applicable to the
full-open/-closed signal only)
Priortoinstallation,checkthattheinsulationclassofthis
unit satisfies the system requirements.
•Altitudeupto2000meters
•The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
•Install lightning surge protectors for those wires con-
nected to remote location. Refer to “LIGHTNING SURGE
PROTECTION”sectionbelow.
■POWER INPUT RATING & OPERATIONAL RANGE
•Locatethepowerinputratingmarkedontheproductand
confirm its operational range as indicated below:
Rating100–120VAC:90–132V,47–66Hz,approx.25VA
Rating200–240VAC:180–264V,47–66Hz,approx.25VA
Rating24VDC:24V±10%,approx.0.6A
•A fuse of the following rating is incorporated: 250V/1A
time delay.
•Arushcurrent1.5timesashighastheaboveratingscan
flow at the startup.
■GENERAL PRECAUTIONS
•Removethepowersupplytotheactuatorbeforewiringtoit.
■INSTALLATION
•Indoor,oroutdoorwheretheMRPisNOTexposedtodi-
rect sunlight.
•Ambienttemperature:-5to+55°C(23to131°F)
•Vibration:0.5Gmax.
•Install the MRP where you can reach for maintenance.
Observe at the minimum of 15 centimeters (6 inches)
above the cover.
■OUTDOOR USE
•WheninstallingtheMRPoutdoororwhereitisexposedto
rain or water drops, be sure to fasten the cable connector
tightly and leave a slack of the cable.
•DonotmounttheMRPinsuchdirectionthattheoutput
stemorcableconnectorisatthetopoftheMRPunit.
■ELECTRICAL CONNECTION
•WithDCpowertypeunit,powersupplyandsignallines
are not isolated. Use an isolator if needed.
•When you use a cable other than the standard 1-meter
cable equipped with non-terminal box type unit and its
extension distance is longer than that, use shielded cables
for signal line, or install signal cables in a separate piping
from power supply cables.
■LIGHTNING SURGE PROTECTION
•Inordertoprotecttheunitfromlightningsurgesentering
through cables, use of appropriate lightning surge protec-
tors are recommended. For 24V DC power supply line,
choose a surge protector with its maximum surge voltage
40Vorlessbetweenlines.RecommendedM-Systemmod-
el:MDP-D24.
■PID CONTROLLER
•ChoosePIDparameterscarefullysothattheMVremains
as stable as possible. Unstable operations shorten the life
of actuator and valve.
■O-RING, GASKET
•When replacing the actuator cover after adjustments,
check that the O-ring is securely placed in the groove.
•When replacing the terminal box cover, check that the
gasket is in place.
■YOKE DESIGN
•Whena foreignobjectis caughtin thevalve, atorque2
times greater than the maximum rating could be gener-
ated. Leave enough strength for mechanical components
such like the yoke and stem.
•Ifthe MRPis usedona steamline intemperature con-
trol,itispossiblethattheMRP’stemperatureriseshigher
than the ambient temperature due to transmission or ra-
diation via the steam piping, even when the ambient tem-
perature is within allowable range.
Use a longer yoke to increase heat dissipation and apply
insulating material.
■AND ....
•DONOTloosenthescrewxingthepotentiometerstem.
Loosening it could cause a malfunction.
•DO NOT steponto the actuator.DO NOT rest a heavy
objectonoragainstit.
Cable Connector
DO NOT Pull Tightly
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MRP4 / MRP5 / MRP6
P. 2 / 8EM-4824 Rev.7
PROTECTIVE FUNCTIONS
■OVERLOAD (LOCK) PROTECTION
The MRP is equipped with a protection circuit against
overload cause by for example valve catching an alien sub-
stance.
When an overload is detected, the MRP stops supplying
powertothemotorandthestatusLEDashesin0.5sec.
intervals.
The protection is reset automatically with applying oppo-
site-direction input signal or turning power off and restart-
ing.
Aforeignobjectcaughtinthevalve,inappropriateadjust-
ments, ground screw of the valve tightened too much, etc.
are some of the causes of overload. Check these parts and
remove the cause of trouble for ensuring proper life of the
actuator.
■FUSE
A fuse is equipped for protection against overload current.
Whenyouturnthepowersupplyon,checkthatthepower
LEDison.Ifitisoff,checkthatthefuseismelted.Replace
it with a new one.
If the new fuse is melted again soon after it has been re-
placed,theremaybeproblemswiththecontrolPCBorthe
motor. Contact M-System or sales representative.
■RE-STARTING TIMER
TheMRP isequipped withatimer circuitwhich givesan
interval period (0 – 10 sec.) between stop-restart actions
to prevent the motor and other internal components from
overheating.
It is recommended to set a long restarting time when the
ambient temperature and/or the temperature of flow mate-
rial is high.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MRP4 / MRP5 / MRP6
P. 3 / 8EM-4824 Rev.7
COMPONENT IDENTIFICATION
Power Input PCB
(for AC power)
Insulation Barrier
Control PCB
Motor
Potentiometer
Connector
O-Ring
Cable
Cable Connector
Output Stem
0
25
Power Input PCB (for AC power)
Insulation Barrier
Control PCB
Motor
Potentiometer
Manual Operation Stem
Gasket
Cable
Cable Connector
Output Stem
Position Indicator
Figure 1. MRP4 & MRP5 Component Identication Figure 2. MRP6 Component Identication
Remark:ConstructionoftheMRP5ispartlydifferentfrom
the above figure.
OFF
1
2
3
4
ON
PWR INP ALM
DLY
ZERO SPAN DZ
Insulation Barrier
Fuse
Connector
SW1
ZERO
SPAN
DZ
DLY
SW1
PWR
INP
ALM
: Zero Adjustment
: Span Adjustment
: Deadband Adjustment
: Restarting Timer
: Direct/Reverse Actions,
Operation at Abnormally Low Input
: Power Indicator (green with power supplied)
: Input Indicator (green with input applied)
: Status Indicator (red blinks in 2 sec. intervals,
blinks in 0.5 sec. intervals with mechanical lock detected)
Remark:Turningadjustmentpotentiom-
eters and switches with a torque exceed-
ing their tolerance may destroy their stop-
pers.
Turn them carefully and stop where they
hit the stoppers. Be careful especially
withRe-startingtimeradjustment.
Figure 3. MRP Control PCB Identication
Remark: MRP6 is equipped with manual operation stem
and position indicator. Turn the stem in counterclockwise
as viewed from the top of the actuator to close the valve
(reverseaction).Turnitslowlywitha6mm-widthwrench
(Operationtorque≤9N·m).
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MRP4 / MRP5 / MRP6
P. 4 / 8EM-4824 Rev.7
OUTPUT SPAN ADJUSTABILITY
The servo-control circuit compares and amplifies input sig-
nal (setpoint) and feedback signal from a potentiometer, and
drivesthemotortosuchdirectiontominimizedifferenceof
the two signals.
Thegeneraloperationalrangeis0–90deg.or0–180deg.
with a 5-deg. margin at both limits. See Figure 5.
INSTALLATION
ThefollowingisageneralprocedureformountingtheMRP
to a valve with a yoke and coupling.
BesureNOTTOCHANGEfactoryadjustedsettingofthe
MRP.
Remove power supply during the procedure unless other-
wise specified.
0
25 50 75 100
25
50
75
100
0
INPUT SIGNAL (%)
STEM POSITION (%)
Span Counterclockwise
Zero Clockwise
Zero Counterclockwise
Span Clockwise
Adjustable Zero Range
Adjustable Span Range
Figure 4. I/O Characteristics (Adjustable Range)
Table 1. Available Span Range for Each Model
MODEL MIN. SPAN MAX. SPAN
MRP4-1
MRP5-1 45° 90°
MRP6-1
MRP4-2 90° 180°
MRP6-2
Standard Zero Position
M
i
n
i
m
u
m
s
p
a
n
M
a
x
i
m
u
m
s
p
a
n
M
a
x
i
m
u
m
O
p
e
r
a
t
i
o
n
R
a
n
g
e
5 deg.
5 deg.
Adjustable Zero Range
Adjustable Span Range
Figure 5. Minimum & Maximum Span
MRPx
Bolts (M5)
Output Stem
Coupling
Yoke
Valve Bonnet
Figure 6. Example of the MRP Mounted to a Valve
1) SupplypowertotheMRPandapply0%input(100%for
direct action). Turn the output stem fully clockwise (seen
from the cover).
2) Turn the valve stem to fully closed position (fully clock-
wise).
3) SettheyoketotheMRP.
4) SetthecouplingtothevalvestemandttheMRPout-
put stem into the coupling. Then fix the yoke and valve
temporarily.
5) Fix the coupling so that there is no eccentricity between
both stems.
6) Fixtheyokeandvalvermlyaftercheckingtheeccen-
tricity of both stems again.
7) Attachthepositionindicatorifrequired.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MRP4 / MRP5 / MRP6
P. 5 / 8EM-4824 Rev.7
WIRING CONNECTION
Refer to the following diagram when wiring. If an optional terminal box is provided, remove its cover and connect lead-
wires.
Figure 7. Wiring Diagram
(1) to (8): Terminal No. of terminal box.
Full-open/-closed signals and forced open/close signals are optional.
Full-closed/overload signals are optional only for model: MRP4.
+
(U)
–
(V)
+
COM1
+
COM2
POWER
INPUT
POSITION OUTPUT (1 – 5V DC)
FULL-OPEN or
FULL-CLOSED
SIGNAL
(
output stem
)
turned CCW
(
output stem
)
turned CW
COM1
FORCED
OPEN/
CLOSE
SIGNAL
(
output stem
)
turn CCW
(
output stem
)
turn CW
1
3
2
4
6
5
7
8
11
9
10
• With Both Full-open/closed Signal
and Forced Open/Close Signal
COM2COM1 COM2
POWER
black (1)
+
(U)
–
(V)white (2)
red (3)
+
INPUT
COM1
green (4)
POSITION OUTPUT (1 – 5V DC)
+
yellow (5)
blue (6)
gray (7)
brown (8)
FULL-OPEN or
FULL-CLOSED
SIGNAL
(
output stem
)
turned CCW
(
output stem
)
turned CW
FORCED
OPEN/CLOSE
SIGNAL
(
output stem
)
turned CCW
(
output stem
)
turned CW
OVERLOAD
FULL-CLOSED
FULL-CLOSED or
OVERLOAD SIGNAL
Remark: The yellow wire must be left unconnected if the position output signal is not required. Cut the exposed section of
copper wire and insulate the tip of the wire.
3.2 min. 4.5 max.
3.2 min.
5.9 max.
10
■
WIRING INSTRUCTIONS FOR TERMINAL BOX OPTION
• Other Terminal Box Type• Sequential Control Signal Suffix Code B
Applicable wire size 1.25 mm2
Remove insulation by 10 mm.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MRP4 / MRP5 / MRP6
P. 6 / 8EM-4824 Rev.7
ADJUSTMENT PROCEDURE
Open the cover and adjust ZERO, SPAN, DZ (deadband),
DLY (re-starting timer) potentiometers and the direct/re-
verseSWonthecontrolPCBasshowninFigure3.
Other adjustments which are paint locked are for factory
use only and should be changed only by qualified M-System
personnel. M-System is not liable for any malfunction or
inconvenience caused by unauthorized change of them by
the user.
■DIRECT/REVERSE ACTION
Theactuatoractionisfactorysetto“Reverse”(the output
stem, seen from the cover, turns counterclockwise, with an
input signal increase). For changing the setting, use the
DIPSWonthecontrolPCB.RefertoTables2and3.
Remark1:SW1-4isnotused.
Remark 2: With the direct action, the position output is
5–1VDCproportionaltotheinput0–100%.
Table 2. Switching Actions
ACTION SW1-3 EXPLANATIONS*1
Direct ON OutputstemturnsCWwithan
input increase.
Reverse OFF OutputstemturnsCCWwithan
input increase.
Table 3. Operations at Abnormally Low Input
OPERATION*1SW1-1 SW1-2
Stop *2ON
Clockwise OFF OFF
Counterclockwise ON OFF
*1. Seen from the cover.
*2.
WhateversettingforSW1-1isdisregardedforStopmode.
■GENERAL
Afterinstallingthevalveandactuator,gotoadjustmentsin
orderofzero,span,andsensitivity(deadband).Ifoptional
limitswitchesareprovided,adjustthematthelast.
The following explanation applies to reverse action For di-
rect action, read the value in the brackets [ ].
Remark:Applyinganover-torquetotheadjustmentsmay
destroy stoppers or other sections of them. Use a small-
sized screwdriver and be sure to stop turning as soon as
they hit the stoppers.
■ADJUSTMENT PROCEDURE
A) Zero and Span
•Applypowersupplyvoltageand0%[100%]input.Turn
ZERO adjustment until the output stem reaches an ap-
propriate fully-clockwise position.
•Apply100%[0%]input.TurnSPANadjustmentuntilthe
output stem reaches an appropriate fully-counterclock-
wise position.
•With0%[100%]inputagain,checkthattheoutputstem
is at the appropriate angle. If the position is shifted, go
through the above procedure again.
Remark1:Thereisonlyminimaleffectofspanadjustment
tozeropoint,thusthestempositionshiftsverylittleatthe
extended side when the span potentiometer is turned.
B) Sensitivity (Deadband)
Whenthemotorrepeatssmallinvertingmovementswith-
out stopping still for small input changes, widen the dead-
bandbyturningtheDZadjustmentclockwise.
C) Limit Switches (optional)
Loosenthescrewsandadjustpositionsofthedogs.SeeFig-
ure8.
Thisadjustmentcannotbedoneinanintermediateposition
of the valve. Set it at the fully open or closed position.
Potentiometer
Limit Switches
Dog (full-opened position)
Screws
Dog (full-closed position)
Figure 8. Limit Switches
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MRP4 / MRP5 / MRP6
P. 7 / 8EM-4824 Rev.7
MAINTENANCE
ForeffectiveuseandlongerlifeoftheMRP,regularcheckingappropriateforitsoperatingconditionsarerecommended.Refer
to the following table.
ITEM CHECKING POINT HOW TO PROCEED
Functioning Applyinput0%,50%,100%,thenbackto50%,0%.
Check the actuator operations and positions at
each input value.
Repair or calibration
Abnormal sound No abnormal sound is heard during operation. Repair or calibration
Connector
Leadwire
The connector is firmly connected.
No breakdown of leadwires.
The insulation covers are not torn, not bruised.
Repair or calibration
Inside humidity, rust No condensation. No rust.
If there is water inside, check the packing.
Remove water, dry the case and inside parts.
Replace rusted parts. Calibration.
If the packing is damaged, replace it.
Screws Check that screws and bolts are securely fastened. Re-tighten them.
For repair or parts replacement, contact M-System or representatives.
■LUBRICATION
ThereisnoneedofoilingtheMRPinnormaloperatingconditions.
■REGULAR TEST RUNNING
If the valve is not frequently operated, run a test operation regularly (once a week, for example) to check proper functions.
TROUBLESHOOTING
TROUBLE
POWER
LED
INPUT
LED
S TAT U S
LED POSSIBLE CAUSE HOW TO PROCEED
No
function
ON ON Flash
2 sec
Abnormal input signal.
(No change over deadband)
Check input signal.
Narrow the deadband.
ON ---- Flash
0.5sec
Actuator mechanism is damaged. Repair
Overloadcausebyaforeignobjectcaught
in the valve.
Check the valve.
ControlPCBdamaged. Repair or replace.
Wiringerroratthemotororpositionsensor.
Check the connector.
Low power voltage or insufficient capacity. Check the power supply.
ON OFF Flash
2 sec
Abnormal input signal. Check the input signal.
Wiringerrorattheinputsignal.
Check the connector and connecting section.
OFF ---- ---- Wiringerroratthepowersupply.
Check the connector and connecting section.
Abnormal power supply voltage. Check the power supply.
Fuse melted. Replace the fuse.
ON ---- ON Malfunction by noise. Turn off the power supply and restart.
Low power voltage or insufficient capacity. Check the power supply.
ON ---- OFF Malfunction by noise. Turn off the power supply and restart.
Low power voltage or insufficient capacity. Check the power supply.
Unstable functioning Powervoltageislowoructuating. Check the power supply.
Unstable input signal. Check the controller, cables. Eliminate
noise.
Positionsensordamaged. Replace the position sensor.
Stops in the middle of span
Slows down in the middle of span
Actuator mechanism is damaged. Repair
Overloadcausebyaforeignobjectcaught
in the valve.
Check the valve.
----RegardlessofLEDstate.
For repair or parts replacement, contact M-System or representatives.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG
Table of contents
Popular Controllers manuals by other brands

Lynxspring
Lynxspring JENEsys Edge 534 installation guide

HobbyStar
HobbyStar 80A product manual

Romotop
Romotop DIRECT General Installation and Operation Instructions

Vacon
Vacon 100 INDUSTRIAL installation manual

Belimo
Belimo PKR Series QUICK MOUNT VISUAL INSTRUCTION MANUAL

Danfoss
Danfoss FH-TC installation guide