Sentry TSV User manual

Installation, Operation and
Maintenance Manual
TSV
Temperature Shut-off Valve
SPD 13.1.2 Rev. 6 10/07
SENTRY EQUIPMENT CORP
PO Box 127
Oconomowoc, WI 53066 USA
Phone: 262.567.7256
Fax: 262.567.4523
Email: [email protected]
www.sentry-equip.com

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com i
TABLE OF CONTENTS
SAFETY PRECAUTIONS............................................................................................... iii
1.0 General Description ..............................................................................................1
2.0 Installation.............................................................................................................2
3.0 Operation..............................................................................................................3
4.0 Maintenance..........................................................................................................3
5.0 Technical Data......................................................................................................4
6.0 Warranty Conditions & Limitations........................................................................5

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com ii
WARNING notices as used in this manual apply to hazards or unsafe practices, which could result in
personal injury or death.
CAUTION notices apply to hazards or unsafe practices which could result in minor personal injury or
property damage.
NOTES highlight procedures and contain information which assists the operator in understanding the
information contained in this manual.
WARNING
Do not install, maintain, or operate this equipment without reading, understanding and
following the proper Sentry Equipment Corp. instructions. Otherwise, injury or damage or
both may result.
NOTICE
The information contained in this document is subject to change without notice.
Sentry Equipment Corp, its employees, agents, and the authors of and contributors to this document
specifically disclaim all liabilities and warranties, express and implied (including warranties of
merchantability and fitness for a particular purpose), for the accuracy, currency, completeness, and/or
reliability of the information contained herein and/or for the fitness for any particular use and/or for the
performance of any material and/or equipment selected in whole or part with the user of/or in reliance
upon information contained herein. Selection of materials and/or equipment is at the sole risk of the user
of this publication.
This document contains proprietary information. No part of this document may be photocopied or
reproduced without the prior written consent of Sentry Equipment Corp.
Sentry Equipment Corp
966 Blue Ribbon Circle North
PO Box 127
Oconomowoc, WI 53066
Phone: 262.567.7256
Fax: 262.567.4523
Normal business hours: 7:00 a.m. to 4:30 p.m. CST (U.S. Central Time), Monday through Friday

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com iii
SAFETY PRECAUTIONS
Please read the entire manual before attempting to unpack, set up or operate this product. Pay careful
attention to all warnings, cautions and notes. Failure to do so could result in serious personal injury or
equipment damage.
Use of Hazard Information
If multiple hazards exist, the signal word corresponding to the greatest hazard shall be used.
Definitions
Indicates an imminently hazardous situation, which if not avoided, will result in death or serious injury.
Indicates a potentially hazardous situation, which if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation, which if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation, which if not
avoided, may result in property damage.
NOTE
Information that requires special emphasis
SHALL
This word understood to be mandatory
SHOULD
This word understood to be advisory

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com iv
It is solely the responsibility of the user, through its own analysis and testing, to select products
suitable for their specific application requirements, ensure they are properly installed, ensure that
they are safely applied, ensure they are properly maintained, and limit their use to their intended
purpose.
Improper selection, installation, or use can cause personal injury or property damage.
Sentry does not warrant against erosion and corrosion. Sentry makes no claims regarding
suitability for specific use, and provides no warrantee regarding material compatibility of
elastomers in specific services.
Hot Surfaces! This equipment may have very hot surfaces. If an operator contacts a hot surface,
injury may occur. Use protective clothing to prevent injury. If other equipment comes in contact
with a hot surface, damage to the equipment may occur. Ensure the area around this equipment
is kept clear to prevent damage from occurring.
High Pressures! This equipment may contain fluids at very high pressures. Prior to installing,
removing or maintaining this equipment, ensure that the equipment is isolated from all
connecting piping, the equipment is de-pressurized, the contents have been drained and the
equipment is cool.

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com 1
1.0 General Description
The Sentry TSV is a fully mechanical valve designed to protect instrumentation and
personnel from the damaging effects of excessive sample temperatures. These temperature
excursions could be the result of excessive sample flow rates, high cooling water
temperatures or momentary loss of cooling water. The TSV is a spring loaded, latching
design with all wetted metals of 316SS construction. An optional position indicating dry
contact (Sentry part # 4-05144A) is available to provide remote indication capabilities.

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com 2
2.0 Installation
Reference the diagram below, which best represents your application, for the proper location of
the TSV. It is imperative that the TSV be located downstream of the pressure reducing valve (i.e.
forepressure regulator, needle valve or VREL) and that no isolation valves be downstream of it.
Note that when the TSV closes all components upstream of the TSV will be subjected to full
system pressure.
It is recommended that the TSV be located such that the reset button is readily visible and
accessible. Approximately 40 lbs. of force may be required to reset the TSV. Consideration
should be given when locating the TSV so adequate force can be applied by operating personnel.
The mounting should be rigid enough such that the TSV will remain stationary while resetting.
If the TSV is to be mounted vertical, it is recommended that the orientation be with the reset
button up. If the TSV is to be mounted horizontal, it is recommended that it be positioned with the
inlet at the top.
A 1” dia. mounting hole is required in panels or brackets up to 5/32” thick. The ¼” dia. tube stubs
may be bent as required to facilitate plumbing of the valve.
Inlet Isolation Valve
Primary Cooler
Pressure Reducing Valve
Preferred TSV Location
Secondary Cooler
Optional TSV Location
(See Note 1 Page 3)
Temperature, Pressure &
Flow Indication
Optional TSV Location
(See Note 2, Page 3)
To
Analyzers
BPR/RV
Grab Sample
Sentry Design Systems
(See Note 3, Page 3)
Inlet Isolation Valve
Primary Cooler
Forepressure Regulator
Preferred TSV Location
Secondary Cooler
Optional TSV Location (See
Note 1 Page 3)
Relief Valve
Temperature, Pressure &
Flow Indication
Optional TSV Location
(See Note 2, Page 3)
To
A
nalyzersNeedle Valve
Grab Sample
Other Design Systems
(See Note 3, Page 3)

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com 3
Installation Notes
1. TSV’s mounted in this location will protect all analyzers, components downstream and
personnel but abnormally high sample temperature excursions may cause the secondary
cooling system (chiller) to become overloaded.
2. TSV’s mounted in this location will protect all analyzers, however pressure, temperature and
flow indicators as well as BPR/RV’s and personnel, could all be exposed to dangerous high
temperature sample.
3. Maximum downstream-regulated pressure should be limited to 250 psig.
3.0 Operation
The TSV is equipped with a indicating reset button. When the valve is in the tripped mode
(closed) the red indicating band on the reset button is visible. If the valve is received in the tripped
position it must be reset to allow sample flow.
This is accomplished by simply pushing in the reset button until it latches. In conditions where
ambient temperatures are above the valve trip point it will be necessary to hold the reset button in
until cooled sample allows the valve to latch.
If the TSV trips during sampling operations, isolate the analyzers on the line or lines affected.
Correct the problem causing the excessive sample temperature and reset the TSV. It may be
necessary to hold the reset button in momentarily until the TSV will reset. After the TSV is reset,
reinitialize sample flow to the analyzers.
4.0 Maintenance
Do not disassemble this valve! There are no customer serviceable components in this valve.
Occasional exercising of the valve may be performed by raising the sample temperature by either
increasing sample flow rate or decreasing cooling water flow rate. This may be necessary if
sample water is exceptionally dirty. Verify that all analyzers are isolated before performing this
operation. If a replacement valve is needed, contact Sentry Equipment Corp.

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com 4
5.0 Technical Data
• Inlet Pressure Rating………………….4400 psi (303 BAR)
• Outlet Pressure Rating ……………….250 psi (17 BAR)
• Trip Point (Standard)………………….120OF (49°C)
Optional Set Points 104°F (40°C) 153°F (67°C)
109°F (43°C) 194°F (90°C)
140°F (60 °C) 203°F (95°C)
160°F (71°C) 210°F (99°C)
• Max. Temperature Rating……………..250OF (121°C)
• CV……………………………………….. 0.21
• Wetted Materials ……………………… 316 Stainless Steel
Viton, Peek
• Optional Position Indicating Dry Contact…P/N 4-05144A
• Configuration ………………………SPDT (form C) (NOHC as used)
• Enclosure ………………………… NEMA 3, 4, 13 & IEC IP-67
• Terminations ……………………… Screw Type
• Estimated Life …………………… 500K operations
• Contact Rating …………………… 5A-125AC, 250VAC
5A-30VDC resistive
4A-30VDC inductive
0.5A-125VDC resistive
0.4A-125VDC inductive
Failure or improper selection or improper use of this product can cause property damage,
personal injury and death.
Due to the variety of operating conditions and applications for this product, the user, through it’s own
analysis and testing, is solely responsible for making the final selection and assuring that all
performance, safety and warning requirements of the application are met.
All Sentry TSV’s pass a rigid operational and leakage test before leaving the factory. This valve is
not user serviceable. If these instructions are not fully complied with, the product may fail and
cause damage to property or injury to persons. Sentry Equipment Corp cannot assume
responsibility for the performance of a customer serviced TSV.

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com 5
6.0 Warranty
Seller warrants products manufactured by it and supplied hereunder to be free from defects in
materials and workmanship for a period of twelve months from date of shipment. If within such
period any such products shall be proved to Seller’s satisfaction to be defective, such products
shall be repaired or replaced at Seller’s option. Seller’s obligation and Buyer’s exclusive remedy
hereunder shall be limited to such repair and replacement and shall be conditioned upon Seller’s
receiving written notice of any alleged defect within 10 days after its discovery and, at Seller’s
option, return of such product to Seller, ex-works Sentry’s factory.
The foregoing warranties are exclusive and in lieu of all other express and implied warranties
except in title, including but not limited to implied warranties of merchantability and fitness for
purpose. Seller shall not be subject to any other obligations or liabilities whatsoever with respect
to products manufactured or furnished by it, or any undertakings, acts or omissions relating
thereto.
Warranty Conditions & Limitations
This Warranty shall not apply to any Sentry product which, in the opinion of Sentry Equipment
Corp, has been (a) altered or repaired in a manner affecting the efficiency of performance of the
unit or (b) incorrectly installed or operated or (c) damaged in shipment or (d) damaged by flood or
fire or (e) if the serial number is missing, altered or defaced.
The owner shall be responsible for maintenance of his equipment. Wear or damage caused by
lack of normal maintenance or by misuse of the equipment shall not be considered as defective
workmanship and material.
Sentry reserves the right to make product design changes or improvements without notice and
without imposing any obligation upon itself to install these changes or improvements on its
products previously manufactured.
This warranty is for the sole benefit of the original purchaser and is not transferable unless agreed
to in writing by Sentry Equipment Corp.
Receiving Shipments (including loss or damage by transportation)
It is the customer’s responsibility to check for missing cartons and sign of damage to cartons. If
found, customer should note missing and/or damaged cartons on the delivery receipt and have
delivery receipt signed by the representative of the transportation company. If unpacking
discloses concealed damage from rough handling, the customer should request a concealed
damage inspection from the transportation company.
The Sentry Customer Service Department will aid your organization in any claim proceeding for
shortages or damages in shipment, but it is the receiver’s responsibility to file claim with the
carrier for damage or loss.

Temperature Shut-off Valve SPD 13.1.2 Rev. 7
SENTRY EQUIPMENT CORP
• 262.567.7256 • Fax: 262.567.4523 • sales@sentry-equip.com • www.sentry-equip. com 6
Customer Actions For Claims on Products During the Warranty Period
1. Contact the Customer Service Department at Sentry Equipment Corp, Oconomowoc, WI,
Telephone: 262-567-7256, to obtain a Return Material Authorization (RMA) number.
2. You will be sent an “RMA” and a “Decontamination Statement” that is required to be filled out
and returned with the equipment.
3. The following information must appear on the outside of the package:
a. RMA number marked on outside of box.
b. Decontamination Statement filled out and attached to outside of box.
4. Return defective equipment FREIGHT PREPAID. Collect shipments will be refused.
5. The factory will not process warranty claims until the customer has properly accomplished the
above items.
6. The Sentry factory may accept the entire claim, a part of the claim, or none of the claim if our
inspection of returned parts proves the failure was for reasons other than defective material or
factory workmanship.
Important Notes:
1. Sentry will not be responsible for damage incurred during the return shipment.
2. All returns subject to inspection and a $50.00 evaluation fee.
3. This RMA is not authorization for credit. Credits and/or replacements will be issued upon
evaluation of returned goods.
4. RMA is valid for thirty (30) days from issue date.
Table of contents
Other Sentry Control Unit manuals
Popular Control Unit manuals by other brands

infra world
infra world B6749 Instructions for assembly and use

IBC control
IBC control Variotron VVX MiniMax V manual

WindowMaster
WindowMaster CompactSmoke WSC 104 Installation instruction

Mark
Mark GTC E user manual

Tripp Lite
Tripp Lite SmartOnline SU5000RT4UTFTAA owner's manual

Black Box
Black Box LRA1204C manual