oDefault Settings
The EM-PULSE installs with minimal user intervention.
If LEDs are green and you are happy with default factory settings
below, your installation is complete!
Each meter has default factory settings in ve Function Groups.
Review the default settings and their denitions below.
Function Group 1. Pulse Scale
Quickset pulse scale selection is the default factory setting.
With Quickset, pulse scale is automatically set based on the
largest installed CVT amperage rating as follows:
CVT Rated Amps Default Pulse Scale
5-50A 1 Wh/pulse
51-500A 10 Wh/pulse
501-5000A 100 Wh/pulse
5000+A 1 kWh/pulse
Check your CVT amperage rating to determine the pulse scale
for your input. For alternative pulse scale settings, see Section
7 - Function Groups.
Function Group 2. Pulse/Alarm Options
Fast Pulses (30ms), KY Mode is the default factory setting. Fast
pulses corresponds to a pulse width of 30 milliseconds. In
KY Mode pulses are the representative units and each pulse
output is independent. For alternative pulse widths, KYZ Mode,
or Alarm options see Section 7 - Function Groups.
Function Group 3. Energy Output Type
Real ‘True‘ Power (P) is the default factory setting. This is the
metric that utility companies typically use for billing.
For alternative Energy Output Types, see Section 7 - Function
Groups.
Function Group 4. Balanced Load Multiplier
The Balanced Load Multiplier is disabled in the default factory
settings. For options on balanced load multipliers see Section
7 - Function Groups.
Function Group 5. PowerPrint
PowerPrint is disabled in the default factory settings. For details
on how to utilize PowerPrint see Section 7 - Function Groups.
To Restore Factory Default Settings
Caution: Restoring factory default settings will revert device to
settings listed above. Any manual congurations previously set in
any of the Function Groups will be reset.
1. Hold setup button down until all LEDs blink red
(approximately 30 seconds) and release.
2. Momentarily press the setup button again within 5
seconds of the rst release.
3. Meter is now reset to factory default settings.
pFunction Groups
The EM-PULSE meter has ve Function Groups:
1. Pulse Scale
2. Pulse/Alarm Options
3. Energy Output Type
4. Balanced Load Multiplier
5. Powerprint Options
Each Function Group has factory default settings which can be
found in Section 6 - Default Settings.
This section will further dene each Function Group and detail
alternative settings that can be user selected in Section 8 - View
and Edit Settings.
Function Group 1. Pulse Scale
There are 8 Pulse Scale options on the EM-PULSE meter:
Quickset operation based on CVT rated amperage, user
selectable pulse scales, or Automeasure based on current
energy.
Pulse Scale Function
Quickset
1
- Default Pulse scale set based on CVT amperage rating
0.01 Wh/pulse
User Selectable pulse scales
0.1 Wh/pulse
1 Wh/pulse
10 Wh/pulse
100 Wh/pulse
1000 Wh/pulse
Automeasure
2
Set based on current energy being monitored
1Quickset pulse scale is selected based on the largest CVT size
installed. This is the factory default setting for the meter. See
Section 6 - Default Settings for usage of Quickset pulse scaling.
2Automeasure takes a sample of energy currently being
monitored and calculates the most appropriate pulse scale
after 10 seconds of sampling. Automeasure should be
initiated on when panel is fully loaded. This ensures that the
automatically chosen pulse scale will avoid pulse overload
warning condition during Normal Operation.
Function Group 2. Pulse/Alarm Options
Pulse/Alarm Options allow for setting dierent pulse types (KY
vs KYZ) and alarm outputs for alerts of phase loss or changes
from a saved PowerPrint (Function Group 5. PowerPrint). There
are 6 Pulse/Alarm Options on the EM-PULSE meter:
Pulse/Alarm Options Function
Fast pulses, KY mode - Default 30ms pulse width, KY mode
Slow pulses, KY Mode 1s pulse width, KY mode
Fast pulses, Alarm mode 30ms pulse width, alarm output enabled,
KY mode
Slow pulses, Alarm mode 1s pulse width, alarm output enabled, KY
mode
Fast pulses, KYZ mode 30ms pulse width, KYZ mode
Slow pulses, KYZ mode 1s pulse width, KYZ mode
Fast Pulses: pulse width of 30 milliseconds
Slow Pulses: pulse width of 1 second
KY Mode: Pulses are the representative units. Each pulse output
is independent.
Function Group Factory Default Setting
1. Pulse Scale Quickset Pulse Scale Enabled
2. Pulse/Alarm Options Fast Pulses (30ms), KY Mode
3. Energy Output Type Real ‘True’ Power (P)
4. Balanced Load Multiplier O/Disabled
5. Powerprint Options O/Disabled