
12 September 2009
Absolute Pressure and Temperature
The equation above shows that the volume of gas is determined by pressure and temperature. In this equation,
the pressure, P, is absolute pressure (the owing or observed gauge pressure plus the atmospheric pressure).
The commonly used unit of measure for absolute pressure is pounds per square inch absolute (psia). For this
purpose, atmospheric pressure is considered to be 14.73 psi. Therefore,
Absolute pressure (psia) = Observed gauge pressure (psig) + 14.73 psi
The absolute temperature in the equation above is expressed in degrees Rankine, which is calculated as fol-
lows:
Degrees Rankine = Flowing gas temperature (°F) + 459.67
Calculating Gas Volume in Actual Cubic Feet
As a point of reference for discussing volumetric units of gas, one cubic foot (1ft3) of gas at a pressure of 1
atmosphere (assume 14.73 psia) at a temperature of 60°F (519.69°R) is considered one standard cubic foot
(scf). A cubic foot of gas at any other pressure and temperature is referred to as an actual cubic foot (acf) and
has no signicance unless the conditions of pressure and temperature are known. For example, given 1 acf
of gas at 200 psig at 100°F, the volume of gas at standard conditions may be calculated with the following
formula:
( )
( )
3
3
3
standard pressure volume observed pressure 1 ft
standard temperature observed temperature
200 14.73 1 ft
14.73 volume
519.67 100 459.67
214.73 519.67
Volume 559.67 14.73
× ×
=
+ ×
×=+
×
=×
=
Therefore, 1 ft3 of gas at 200 psi and 100°F would occupy a volume of 13.536 ft3 if the pressure and tem-
perature were reduced to standard conditions of 0 psi (14.73 psia) and 60°F. Numerous laboratory tests
have shown that the NuFlo Gas Flowmeter produces the same number of pulses per actual cubic foot of gas
regardless of the pressure and temperature of the gas when operated within its rated range. As a result, the
calibration factor can be specied in pulses per actual cubic foot. If the readout equipment for a gas meter
and the totalizer register in actual cubic feet, the ow totalizer divisor is set to the nearest whole number to
the calibration factor. The counter will then register actual cubic feet, regardless of the owing pressure and
temperature.
Example: Assume a 2-in. gas owmeter with a calibration factor of 124.96 pulses per actual
cubic foot, a owline pressure of 70 psig, and a temperature of 80°F.
If the readout equipment divisor is set for 125, totalizer measurements will be in actual
cubic feet; if the readout equipment divisor is set for 1,250, totalizer measurements
will be in tens of actual cubic feet.