Shield Shiel A-XT User manual

Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00 Issue Date: 5/2/2012
Shiel A-XT®Releasing Fire Control Panel
Installation and Operation Manual

Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
Underwriters Laboratories (UL)
File number (S 8485)
Fire Alarm Equipment
Shield Fire, Safety and Security Ltd.
The model series of the Shield A-XT Releasing Fire Control Panel is suitable as follows:
• Local Signaling Unit, Cross Zone and Releasing
• Commercial protected-premises control unit
• Types of signaling services are SLC Class B, Style 4, NFPA 72 conventional IDC Class B and
Style C or Class B, Style B, automatic fire alarm, manual fire alarm
• Non-coded Signaling
• Compatibility IDAXT0110
Install detectors with spacing as specified in section 90.19 of UL 864, 9th edition where units employing the multiple detector operation shall include
guidelines for installing of a minimum of two detectors in each protected space and to reduce the detector installation spacing to 0.7 times the linear
spacing in accordance with National Fire Alarm Code, NFPA 72. Also reference 55.3.1 and 55.3.2 of UL 864, 9th edition for these detector spacing
requirements.
NFPA
Shield Fire, Safety and Security Ltd.
This product satisfies releasing operation under:
• Carbon dioxide extinguishing systems, NFPA 12
• Halon 1301 fire extinguishing systems, NFPA 12A
• Sprinkler systems, NFPA 13
• Water spray fixed systems for fire protection, NFPA 15
• Foam-water sprinkler and foam-water spray systems, NFPA 16
• Dry chemical extinguishing systems, NFPA 17
• Wet chemical extinguishing systems, NFPA 17A
• Water mist, NFPA 750
• Clean agent fire extinguishing systems, NFPA 2001

Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
This page intentionally left blank.

Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
is a registered trademark of Shield Fire, Safety and Security Ltd.
All other product names are the property of their respective owners.
Copyright © 2012 by Shield Fire, Safety and Security Ltd.
All rights reserved.

Contents
i
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
Section 1
Introduction
Using This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Document Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Writing styles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
If You Need Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Limited Returns and Repairs Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
In-Warranty Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Damaged Goods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Component Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Service Replacement Items. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Out Of Warranty Items. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Customer Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Repair Warranties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Items Returned For Credit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section 2
Overview
Hardware Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Internal Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Power Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Releasing Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
NAC Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Panel Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Field Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Contents
ii
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
Section 3
Installation
General Installation Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Determining System Current Draw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Standby-Battery Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Operating Constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Mounting the Fire Control Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Preparing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Removing the Fascia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Separation of Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
AC Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Standby-Battery Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Field Cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Detection Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Remote Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Notification Appliance Circuit (NAC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Releasing Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Aux 24V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Testing the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Section 4
Programming and Operating
Programming the Fire Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Access Level 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Configuration Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Operating the Fire Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Access Level 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Control Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Single Zone Fire Condition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Double Zone Fire Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Abort Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Silence/Sound Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Contents
iii
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
Zone Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
NAC Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Power Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
System Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
General Trouble. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Lamp Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Released Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Low Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Change mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Extract fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Disablements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Relay Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Calibrating the Releasing Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Section 5
Maintenance and Repair
Cleaning the External Cabinet and Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Testing the Releasing System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Inspecting Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Replacing Standby-Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Removing the Standby-Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Installing the Standby-Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Replacing Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Battery Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
AC Input Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Replacing Cabinet Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Section 6
Supplementary Devices
Status Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
The J2 Jumper Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Abort Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Mode Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Hold Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Mode Select Key Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Contents
iv
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
Ancillary Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
The J2 Jumper Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Relay Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Connecting Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
24 VDC Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Connecting Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Power Fault (PF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Configuring Status Units and Ancillary Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Adding Status Units and Ancillary Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Removing Status Units and Ancillary Boards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Appendix A
Specifications
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
AC Line Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
System Power-Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Rechargeable Battery Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Ground Trouble Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Initiating Device Circuit (IDC) Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Notification Appliance Circuit (NAC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Releasing Device Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
AUX 24V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Power Output Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Remote Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Status Unit Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Supplementary Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Status Unit - Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Ancillary Board - Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

Contents
v
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
Appendix B
Calculations
Determining the Amp-Hour Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Current-Loading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
NAC Wiring Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Releasing-Circuit Wiring Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Appendix C
Wiring Diagram
Appendix D
Operating Instructions
Inspecting Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Replacing Standby-Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Emergency Contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Appendix E
UL Compliance Label
Appendix F
UL 864 Permitted Configurations

Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
2 of 127
Introduction 1
Using This Manual
The following sections provide instructions for installing, testing and troubleshooting the Shield A-XT Releasing
Fire Control Panel:
Section 1 Introduction provides document conventions, the technical help-line, repair and return
information.
Section 2 Overview provides a summary features of the Shield A-XT Releasing Fire Control Panel.
Section 3 Installation describes how to setup, install, test and troubleshoot the A-XT Releasing Fire
Control Panel.
Section 4 Operation describes how to initiate Access Level 2 or Access Level 3, identify Alarm
Conditions, Controls and Indicators, understand Relay Contacts and how to Configure Ancillary Cir-
cuit Boards.
Section 5 Maintenance and Repair describes how to maintain and repair the A-XT Releasing
Fire Control Panel.
Appendix A Specifications provides characteristics of the Shield A-XT Releasing Fire Control Panel.
Appendix B Equipment List provides model numbers for Shield A-XT Releasing Fire Control Panels, loop
devices, accessories, replacement parts and compatible Notification Appliances.
Appendix C Calculations provides calculations for determining load capacity, battery rating, and wiring length
of the Shield A-XT Releasing Fire Control Panel.
Appendix D Wiring Diagram is a copy of the wiring diagram used for shipping with A-XT Releasing
Fire Control Panel.
Appendix E Operating Instructions provides an overview of Shield A-XT Releasing Fire Control Panel
status and control instructions.
Appendix F UL Compliance Label is a copy of the compliance label applied to the cabinet door of the
Shield A-XT Releasing Fire Control Panel
Appendix G UL Permitted Configurations provides UL authorized codes for programming the Shield A-
XT Releasing Fire Control Panel.

Introduction 1
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
3 of 127
Document Conventions
This document contains conventions for part numbers and writing style.
Part Numbers
Part numbers are provided in Section 1, Appendix B and Appendix D of this manual. Refer to Appendix D,
Door Label for a diagram summary of this manual. Refer to Appendix B, Equipment List for a complete list of part
numbers required for completing this installation.
Writing styles
Before you begin using the Shield A-XT Releasing Fire Control Panel, familiarize yourself with the stylistic
conventions used in this manual:
If You Need Help
If you need technical support contact Shield at +971 48812070 or e-mail elv@shieldglobal.com. Shield technical
support is available Sunday through Thursday, 8:00 AM to 5:00 PM
Limited Returns and Repairs Policy
In-Warranty Items
All equipment supplied by Shield is provided with a warranty, these warranties are between Shield (the Seller) and the
company that placed the order upon the seller (the Buyer). The warranty Period is valid for 36 months from the
delivery date and is non-transferable.
Damaged Goods
In the event of damage to equipment during transit or any defect in the quality of goods, the Buyer shall Notify Shield
within seven days of delivery.The goods may then be returned to the Customer Service Department of Shield for
repair, or replacement parts may be supplied (by arrangement).
Component Failure
In the event of a defect of the supplied equipment during the warranty period, due to defective materials or
workmanship, then replacement parts shall be supplied to the Buyer using the Service Replacement Item (SRI)
scheme.
Service Replacement Items
The Buyer shall request the replacement part(s) required from the Customer Service Department. This Request shall
be made by fax to +971 48812198 or e-mail to elv@shieldglobal.com and shall include the Parts required the panel
Works Order (W/O) Number and the required delivery address.
Italic type Denotes a displayed variable, a variable that you must type, or is used for emphasis.
Courier font Indicates text displayed on a computer screen.

Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
4 of 127
Introduction 1
If the Buyer is not aware of the required replacement part(s), additional advice may be obtained from the Technical
Support Department. Once the SRI has been approved, items are normally dispatched for next day delivery subject to
stock availability.
SRI parts are supplied on the following terms and conditions:
• SRI parts are loan items and are not available for resale.
• All SRI parts must be returned to the Customer Service department of Shield within 14 days of delivery.
• Any SRI parts that have not been returned within 28 days of delivery will be invoiced at the price given in the
Shield Price List, less discount.
• Any returned items that are found to have failed due to fair wear and tear, willful damage, negligence, abnormal
working conditions, misuse or alteration or repair without the Suppliers approval or failure to follow the sellers
instructions will be subjected to a repair fee of up to the price given in the Shield Price List, less discount.
• Any returned items that are not part of the original equipment or are not in warranty will be invoiced at the price
given in the Shield Price List, less discount where applicable.
• All SRI parts shall be returned in the same packaging as the replacement parts were supplied in. Failure to ensure
that adequate anti-static precautions are taken during the replacement of parts, or in the return of SRI parts may
result in an invoice of up to the price given in the Shield Price List, less discount.
• Any SRI parts returned without the completed SRI delivery report or any SRI reference documentation will be
invoiced at the price given in the Shield Price List, less discount. The right to receive Service Replacement Items
is regularly reviewed and may be withdrawn from persistent abusers of this facility. Shield reserve the right not to
supply SRI items without prior notice.
Out Of Warranty Items
Shield provides a test and repair facility for most standard and special build products. This facility can also recondition
control panels, subject to availability of components.
Customer Repairs
Items for repair shall be returned to the Customer Service Department of Shield. Any items returned for repair must be
accompanied with the following:
• A request for repair work to be undertaken.
• A customer contact name.
• Details of the company requesting the repair.
Failure to supply the required information will result in the returned items being quarantined for a period not
exceeding 60 days. If the items are not identified within 60 days of receipt, then Shield reserves the right to
dispose of these items or return them.
A written quotation will be provided for all items to be repaired that are not included in the repair prices section of the
Shield Price list. No repairs or refurbishment will be undertaken without prior authorisation from the customer and a
written order for the repair work. Returned equipment will be held awaiting authorisation for a period not exceeding
60 days from the date of quotation. After this period, Shield reserves the right to dispose of these items or return them.

Introduction 1
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
5 of 127
Repair Warranties
Repaired items are not covered by the normal Warranties and Liability conditions. Subsequent failures of repaired
items will only be covered if the failure is due to a material or workmanship defect directly associated with the repair
and for a period not exceeding three months from the date of the repair. Shield are under no liability if the repaired or
replaced components are found to have failed due to fair wear and tear, willful damage, negligence, abnormal working
conditions, misuse or alteration or repair without approval or failure to follow the sellers instructions.
Items Returned For Credit
Items shall only be accepted for credit by written approval with the Operation Manager of Shield. Items will only be
eligible for credit in the first 3 months from the supply date.
Before any items are returned for credit, an RMA reference number must be obtained from the Sales / Operations
Department. This number must be used for any correspondence relating to the goods. All goods Returned for credit
must be approved before receipt.Written approval will then be issued using a Goods Return Application Form. A copy
of this form must be supplied with the returned goods. The RMA reference number must be clearly marked on the outer
packaging when returning goods to the company. Goods must be returned to Shield within 30 days of the issue of the
Goods Return Application Form. Only items listed on this from must be returned under the RMA reference. Items
returned without prior request for an RMA reference may be returned to the customer.
Failure to supply the required information will result in the returned items being quarantined for a period not
exceeding 60 days. If the items are not identified within 60 days of receipt, then Shield reserves the right to dispose of
these items.
Any items returned for credit will be tested and returned to a production release condition. Any material and labour
costs associated with this process shall be deducted from the credit amount in accordance with the Returned Goods
Policy in the Shield price list and at the discretion of the Managing Director.
Shield Fire, Safety and Security Ltd.
29th Floor, Reg us Suite, One Canada Square
Canary Wharf, London, E14 5DY, UK
Tel:+44 0 2077121610
Fax:+44 0 2077121578
E-mail: Shielduk@shieldglobal.com
Shield Middle East Operation
Jebel Ali, Dubai
U.A.E
Tel: +971 48812070
Fax: +971 48812198
E-mail: elv@shieldglobal.com

Overview 2
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
6 of 127
The Shield A-XT Releasing Fire Control Panel is a co nventional re control panel and releasing system. The re
control panel provides connections for Detection Zones, Notication Appliance Circuits (NACs), Releasing Circuits,
Relay Outputs, Status Units and AUX 24 V power.
Models of the Shield A-XT Releasing Fire Control Panel provide 115 VAC or 230 VAC operation in modes for
regulated and special application environments.
The gure below illustrates Class B, Style C eld wiring terminations of the Shield A-XT Releasing
Fire Control Panel:
Figure 2-1
Field Wiring Terminations
EXTRACT
SWITCH
REL PRES.
SWITCH
LOW P.EXTING.ABORT
RELEASE
MA N.
SELECT
MODE2ND STAGE1ST STAGENAC3POWERDATA
STATUS UNITS
REMOTE
CONTROL
AUX
24V
CNONOCNCNOCNC
ZONE 3ZONE 1 ZONE 2NAC2NAC1
RSTR0V SIL AL FLT NOCON CNCON CNCNC
FIRE RELAYLOCAL FIRETROUBLE RELAY
No Connection
(NC)
ZONE 2 IDC
EOL resistor
ZONE 1 IDC
EOL resistor
ZONE 3 IDC
EOL resistor
10K 10K
To Status Units
10K 10K
NAC 1
EOL resistor
NAC 2
EOL resistor
10K
NAC 3
EOL resistor
10K10K
10K
6.8K 6.8K
6.8K
6.8K
6.8K
EOL resistor
6.8K
6.8K
EOL diode
Authorized
Releasing
Solenoid
6.8K
EOL resistor
Relay
Relay
Relay Relay Relay Relay
AUX 24 VDC
( + ) ( - )
Section 2
Overview

Overview 2
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
7 of 127
The Shield A-XT Releasing Fire Control Panel provides functions for:
Zone Testing The zone testing function provides an automatic reset of zones in alarm.
NAC Delay The NAC delay function suspends the NAC output and permits alarms to be
verified before premises are evacuated.
NAC Reactivation The NAC reactivation function provides an alarm resound.
Voltage Free Relay Contacts Voltage free relay contacts are provided for local control and signalling.
Releasing Delay The releasing delay function suspends the releasing signal for up to 60 seconds.
Releasing Signal The releasing signal provides identification of the pending extinguishant release
and the flow of extinguishant during the releasing process.
Low Pressure The low pressure function provides releasing agent monitoring using a pressure
switch to measure low pressure conditions.
Abort The abort function provides suspension of the releasing count-down when
contacts on an external-momentary-switch are closed.
Deactivation Time The deactivation time function provides a delay setting to control the output
quantity of the releasing agent.
Manual Only Mode The manual only mode disables the releasing operation using automatic
detection devices.
First and Second Stage
Relays
First and second stage relay contacts are provided to trigger equipment outside
the system.
Pre-discharge and Release
Warnings
Pre-discharge and release warnings are provided with separate audible tones
and frequencies. These operating characteristics allow the two warnings to be
differentiated on the fire control panel.
Supervisory Signal Function The supervisory signal function provides audible and visual indications on the fire
control panel and on external status units. This mode also operates the output of
the TROUBLE RELAY. All supervisory conditions are non-latching.
Power Source Failure
Function
The power source failure function provides immediate audible and visual
indications at the fire control panel. The audible and visual indications are also
provided on external status units. Status Units can operate the output of the
TROUBLE RELAY.
Interconnected status units Interconnected status units are provided with a limited set of indicators and
functions compared with those provided on the Shield A-XT Releasing Fire
Control Panel. Status unit functions are non-configurable on the fire control
panel.

Overview 2
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
8 of 127
Hardware Features
The figure below illustrates hardware features of the Shield A-XT Releasing Fire Control Panel:
Figure 2-2
Hardware Features
Key Item Description
1Mains Terminal Block The Mains Terminal Block contains a 1.6 Amp fuse and accepts connections
from the transformer primary and input power connections. Connections from
the primary of the transformer to the Mains Terminal Block are pre-wired at the
Shield factory. Terminals of the Main Terminal Block are designated Line,
Neutral and Ground.
2Field Terminals Field terminals provide connections for Zones, NACs, Releasing Devices,
Relay Outputs, Status Units and AUX 24V.
3Fascia The front fascia of the Shield A-XT Releasing Fire Control Panel is
populated with controls and indicators for programming and operating the fire
control panel.
4Standby-Batteries The Shield A-XT Releasing Fire Control Panel contains two 12 VDC, 7 AH
batteries for operating the fire control panel during primary AC power failure.
7 A/H BATTERY 7 A/H BATTERY
7 A/H BATTERY7 AH Battery 7 AH Battery
L
Low
Pres. Tale
Tell Terminate
Releas e
W/Dog
Reset
Processor
Reset
Exting.
Mon.
Write
Enable
Exting. ReleaseMode
Man.Rel.Abort
Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.
NAC3NAC1 NAC2Sys.FuseEarth
Trbl.Trbl.Trbl.Trbl.Trbl.
Comms
Low
Batt.
Trbl.
Aux.24V
Trbl.
CPU
Mains
Fail
(+1)(+10)
Enter System ModeSelectModeReset Lamp Test
(+100)
Silence/Sound
Alarm
On Test/Disabled
Test Mode On
General
Disablement
System Trouble
Buzzer Silenced
2nd Stage Output
Extract F an On
Abort Activated
Releasing Trouble
Silence
Buzzer
Enable Access
EXTRACT
SWITCH
REL PRES. SWITCH
LOW P.EXTING.ABORT
RELEASE
MAN.
SELECT
MODE2ND STAGE1ST STAGENAC3POWERDATA
STATUS UNITS
REMOTE
CONTROL
AUX
24V
CNONOCNCNOCNC
ZONE 3
EZONE 1 ZONE 2NAC2NAC1
RSTR0V SIL AL FLT NOCNCNOCNCNOCNC FIRE RELAYLOCALF IRETROUBLE RELAY
24V DC
Power On
General System Status Fire In Zone
123
Zone Trouble/
Disablements/
Supervisory Releasing Status
Fire
Delay On
NAC Trouble/
Disabled
Power Trouble
General Trouble
Manual Release
Extinguishant
1st Stage Output
Release
Imminent Auto &
Manual
Manual
Only
Extinguishant
Released
Low
Pressue
1st Stage
Activated
Pull Down - Push Button
Manual
Extinguishant Release
FUSE
N
1
2
3
4

Overview 2
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
9 of 127
Internal Power Supply
The internal power supply of the Shield A-XT Releasing Fire Control Panel meets UL 864, 9th edition and
provides a 2 Amp, linear power-source for operating FACP functions as well as charging the standby batteries.
The 2 Amp power supply operates 115 VAC and 230 VAC models of the Shield A-XT Releasing
Fire Control Panel.
Reference Appendix C, Calculations to determine load current limitations of the 2 Amp power supply
Features of the internal power supply include:
Power Outputs
The Shield A-XT Releasing Fire Control Panel provides power outputs the terminals of NAC 1, NAC 2, and
NAC 3, AUX 24V, STATUS UNITS and EXTING. terminals.
Reference Section 3, Installation and Appendix A, Specifications for further information concerning NAC, Releasing,
Status Unit and AUX 24V outputs of the Shield A-XT Releasing Fire Control Panel.
Releasing Circuit
The Shield A-XT Releasing Fire Control Panel provides features for operating releasing signal delay, device
supervision, releasing emergency abort, flood control and manual release.The Shield A-XT Releasing Fire
Control Panel operates releasing devices in compliance with Fire Protection Service Valves under UL 260, UL 429 and
UL 429A.
NAC Outputs
NAC outputs of the Shield A-XT Releasing Fire Control Panel are programmable and can be operated in
regulated or special application mode.
Reference Appendix A, Specifications for constraints and operating levels of these NAC output modes.
Battery-backup Provides battery power to the load when the AC input of the power supply falls
below the rated level. The voltage at the load remains within the specified range
during these switching-transitions.
Battery-boost Boosts voltage when the battery voltage drops due to a low-battery condition.
Short-circuit protection Provides a shut down on the load side of the power supply when the load-current
exceeds the maximum level.
Automatic-retry Restores output to the load when operating conditions return to nominal levels.
This feature restores voltage levels at the load following conditions such as
over-current and battery depletion.
Status The AC input to the power supply is supervised by the A-XT Releasing Fire
Control Panel with Releasing. The control panel provides an LED status display
for normal and trouble conditions. Normal conditions occur when the power
supply is operating in an acceptable range. Trouble conditions occur when the
power supply is not operating in an acceptable range.

Overview 2
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
10 of 127
Panel Controls and Indicators
The fascia of the Shield A-XT Releasing Fire Control Panel is divided into sections for controls and indicators.
The figure below illustrates controls and indicators of the Shield A-XT Releasing Fire Control Panel:
Figure 2-3
Controls and Indicators
Controls
The fascia of the Shield A-XT Releasing Fire Control Panel provides upper, central and lower controls.
Upper Controls
The figure below illustrates upper controls of the Shield A-XT Releasing Fire Control Panel:
Figure 2-4
Upper Controls
Key Description Key Description
AUpper Indicators DUpper Controls
BCentral Controls ECentral Indicator
CLower Indicators FLower Controls
Low
Pres. Tale
Tell Terminate
Release
W/Dog
Reset
Processor
Reset
Exting.
Mon.
Write
Enable
Exting. ReleaseModeMan.Rel.Abort
Trbl.Trbl.Trbl.
Trbl.
Trbl.Trbl.
NAC3NAC1 NAC2Sys.FuseEarth
Trbl.Trbl.Trbl.Trbl.
Trbl.
Comms
Low
Batt.
Trbl.
Aux.24V
Trbl.
CPU
Mains
Fail
(+1)(+10)
Enter System ModeSelectModeReset Lamp Test
(+100)
Silence/Sound
Alarm
On Test/Disabled
Test Mode On
General
Disablement
System Trouble
Buzzer Silenced
2nd Stage Output
Extract Fan On
Abort Activated
Releasing Trouble
Silence
Buzzer
Enable Access
Power On
General System Status Fire In Zone
123
Zone Trouble/
Disablements/
Supervisory Releasing Status
Fire
Delay On
NAC Trouble/
Disabled
Power Trouble
General Trouble
Manual Release
Extinguishant
1st Stage Output
Release
Imminent Auto &
Manual
Manual
Only
Extinguishant
Released
Low
Pressue
1st Stage
Activated
Pull Down - Push Button
Manual
Extinguishant Release
C
B
A
F
E
D
Auto &
Manual
Manual
Only
Low
Pressue
Pull Down - Push Button
Manual
Extinguishant Release
atus

Overview 2
Shield Fire, Safety and Security Ltd.
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM
Revision E01.00
11 of 127
The table below describes upper controls of the Shield A-XT Releasing Fire Control Panel:
Central Controls
The figure below illustrates central controls of the Shield A-XT Releasing Fire Control Panel:
Figure 2-5
Central Controls
The table below describes central controls of the Shield A-XT Releasing Fire Control Panel:
Controls Modes
Releasing Key-Switch Provides key-switch modes for automatic & manual or manual-only release
Manual Extinguishant
Release
Provides manual release as a push button
Controls Modes
Silence/Sound Alarm Re-sounds the alarm when NACs are silenced using the Silence Buzzer
button.
Silence Buzzer Silences NACs connected to the Shield A-XT Releasing Fire Control Panel
after receiving authorization through Access Level 2.
Reset Resets latching inputs such as fire and pre-alarm events after receiving
authorization through Access Level 2. Trouble events are non-latching inputs and
cannot be cleared by the Reset button. Non-latching inputs are cleared when
faults are cleared.
Lamp Test Tests front-panel indicators and the internal buzzer by illuminating all LEDs while
darkening the front-panel display and sounding the buzzer.
Mode Places the menu in a mode for operating or programming the Shield A-XT
Releasing Fire Control Panel.
Select Selects the menu option displayed on the System Mode LED of the front-panel.
Enter Enables the menu selection to function on the Shield A-XT Releasing Fire
Control Panel.
Enable Access Places the menu of the Shield A-XT Releasing Fire Control Panel in
ACCESS LEVEL 2. Insert the key in the Enable Access lock and turn the key to
the right to open ACCESS LEVEL 2.
(+1)(+10)
Enter System ModeSelectModeReset Lamp Test
(+100)
Silence/Sound
Alarm Silence
Buzzer
Enable Access
Table of contents
Popular Control Panel manuals by other brands

Integrated Technical Vision
Integrated Technical Vision DLK640Plus Dlk640plus

Extron electronics
Extron electronics RCP 2000 user manual

Eaton
Eaton XV-112 operating instructions

Hamworthy
Hamworthy MARSHALL HE Installation, commisioning and maintenance instructions

B&R
B&R Mobile Panel 40 user manual

DSC
DSC PowerSeries Neo user manual