SICLI COP3000 User manual

Contents
Contents Page
1.0 Installation 3
Compatible Equipment 4
Detectors 4
Call Points 5
Beacons & Sounders 5
3 Channel I/O 7
1 Channel I/O 7
Zone Monitor Unit 8
4 Way Sounder Circuit Controller 9
Equipment Compatiblity 10
System Overview 12
Technical Specification 15
Optional Functions as per EN54 part 2 & 4 17
Cable and Wiring 21
Installation 22
Fixing details 23
External Connections 24
Networking 25
Inputs/Outputs 27
2.0 Panel Assembly Information 28
Attaching Panel Door 29
Installing Screen Door 30
Replacing Printer Paper Roll 31
Panel Fault finding 32
3.0 Appendix 33
4 Way Sounder Circuit COP4SIR 34
Zone Unit Monitor COPZMU-IS 35
1 Way I/O Unit COPMIO 36
Base CABB300 37
System Wiring 38
Loopsplitter 39
Internal Wall Sounder COPSYMPHONI 40
Base Sounder COPBS 41
3 Way I/O COPIO 42
Call Point COPBG-S, COPBG-SY, COPBG-WP 43
Serial Number Label Positioning 44
Battery Disposal 45
CE marking 46
www.acornfiresecurity.com
www.acornfiresecurity.com

COPP420 Analogue photoelectric sensor, this is the
most commonly used Sensor and is most suitable for
detecting slow burning fires.
The status LED can be programmed to either be
permanently off under normal conditions or to pulse in
order to confirm that it is in communication with the
COP3000 control panel.
COPOH450 Analogue photo/thermal sensor, this is a
new addition to the Cooper Fire Systems range of sensors.
It is the ideal Sensorfor a multi-use environment as it has
an excellent response to smouldering and fast burning
fires. photo/thermal sensors can be programmed for
thermal only operation at certain times of day
The status LED can be programmed to either be
permanently off under normal conditions or to pulse in
order to confirm that it is in communication with the
COP3000 control panel.
The range of compatible sensors for the COP3000 system consists of the following:
COPH430 Analogue heat sensor,
Heat sensors are suitable for dusty environments or
environments where smoke is likely to be present under
normal operating conditions. The CAH330 can be
programmed to operate in A1R, BS or CS mode of
operation depending on the required application and
sensitivity requirements.
The status LED can be programmed to either be
permanently off under normal conditions or to pulse in
order to confirm that it is in communication with the
COP3000 control panel.
Compatible Equipment
4
www.acornfiresecurity.com
www.acornfiresecurity.com

Compatible Equipment
Compatible callpoints
The range of purpose designed callpoints for COP3000 consists of a surface callpoint, a
flush callpoint and a surface weatherproof callpoint.
A range of accessories is available including a hinged protective cover, resettable
element kit and a flush bezel.
The status LED can be programmed to either be permanently off under normal
conditions or to pulse in order to confirm that it is in communication with the COP3000
control panel.
Compatible Sounders and Beacons
A wide range of loop powered sounders and beacons are available to operate with the
COP3000, consisting of a combined sounder base with a maximum output of 95 dB(A),
a standalone sounder with a maximum output of 100 dB(A) that is available in standard
or weatherproof versions and a stand alone loop powered beacon.
For applications where a discreet dedicated sounder is required, a cover plate is
available for the white base mounted sounder enabling it to be used as a stand alone
wall or ceiling mounted sounder.
All of these devices are fully programmable via the sophisticated COP3000 multi stage
cause and effect programming facilities.
All sounders have multiple selectable volume settings, the volume setting is controlled
by the COP3000 panel and so can be altered without needing to access the sounder.
COPBG-S
COPBG-SY COPBG-S
COPBG-SY
COPBG-WP
5
www.acornfiresecurity.com
www.acornfiresecurity.com

Base sounder
The CAS380 has been designed specifically to complement the latest generation of
Cooper Fire Systems soft addressed sensors.
it consists of a first fix bracket, and a main body which clips onto the bracket
incorporating the sounder and a Sensormounting base in a single composite assembly.
After the body has been clicked into place and connected, a Sensor or front cover is
then added to complete a very simple, quick and neat installation.
The cover enables the CAS380 to be used as a discreet stand alone wall or ceiling
mounted device.
The sounder base design incorporates a mechanism that can be activated if required to
lock either the Sensor or the cover into place to prevent unauthorised removal.
Dedicated Stand alone sounders
Stand alone sounders are ideal for applications where greater sound outputs are
required than can be achieved with a base sounder or for applications requiring a higher
level of resilience or ingress protection.
Two different versions are available standard version and an IP66 rated version.
COPBS
COPSYMPHONI
COPBS with Sensor fitted COPBS with CASC fitted
Compatible Equipment
6
www.acornfiresecurity.com
www.acornfiresecurity.com

Interfaces
COP3000 has been designed to be suitable for a wide range of applications, various
interfaces have been developed to enable the simple integration of other fire systems or
building control and safety systems. The following devices are available:
3 Channel I/O device. (COPIO)
COPIO has 3 input channels and 3 output channels, it is used to monitor up to three
separate inputs from equipment such as sprinkler flow switches and also to provide 3
separately controlled volt free output contacts which are intended to be used to control
external equipment such as air handling plant or access control systems.
All inputs and outputs operate completely independently of each other and can be
programmed using the sophisticated cause and effect capabilities of COP3000 to
operate either globally or in response to activation of specific devices or specific inputs.
Inputs are monitored for open and short circuits, a specific resistance is required to
activate an alarm condition, fully open or short circuit conditions are monitored and
generate a system fault signal.
Inputs are suitable for use as fire signal inputs such as from a sprinkler flow switch ,
however they can also be used to monitor non fire inputs such as external keyswitches.
Outputs are rated to switch a maximum of 1A resistive at 30V DC.
The COPIO is supplied in a surface mounting IP65 box.
1 Channel I/O device with mains rated switching capability
(COPMIO)
COPMIO is a single channel input / output unit, the output is capable of switching up to
1A at 230V AC.
Commonly used for applications such as door release controls and plant shut down
signalling
The input is monitored for open and short circuits, a specific resistance is required to
activate an alarm condition, fully open or short circuit conditions are monitored and
generate a system fault signal.
The input is suitable for use as a fire signal input such as from a sprinkler flow switch,
however it can also be used to monitor non fire inputs such as an external keyswitch to
activate day night mode or other panel functions
The COPMIO is supplied in a surface mounting IP65 box.
COPIO COPMIO
7
www.acornfiresecurity.com
www.acornfiresecurity.com

Zone monitor unit
COPZMU-IS is designed to enable a zone of compatible conventional sensors and
callpoints to be connected into the COP3000 loop,
For the compatibility refer to Sicli.
Please refer to local standards for details of the maximum allowable area to be covered
by a single zone. COPZMU-IS fixes to a standard, deep, double gang back box and can
be either surface or semi recess mounted. When semi recessed only the front section
protrudes giving a maximum 29mm depth.
Interfaces
COPZMU-IS
8
www.acornfiresecurity.com
www.acornfiresecurity.com

4 Way sounder circuit controller
COP4SIR provides power for 4 separately controllable conventional sounder circuits,
each circuit can be separately programmed.
COP4SIR is designed to greatly simplify installation in applications where specialist
sounders or beacons are required since it powers the sounders and allows full control of
the sounder operation without having to wire the sounder back to the COP3000 control
panel.
A 4 way unit takes up a single address but each circuit can be independently controlled.
A COP4SIR unit requires a local un-switched 230V supply and incorporates a back up
battery to 24 hours of standby operation followed by a minimum of 30 minutes of full
alarm ringing.
A standby of 72 hours can be achieved at the expense of reduced load capability.
Interfaces
COP4SIR
9
www.acornfiresecurity.com
www.acornfiresecurity.com

Equipment Compatibility
Relays / Auto-dialers and auxiliary equipment
A wide variety of relays and other equipment can be connected to the COP3000
system, but you should note the following constraints:
1) COP3000 provides monitored outputs to drive fire and fault relays mounted in
external equipment. External relays should be suppressed. If a non-suppressed
relay is used then a diode can be connected as shown in the wiring diagram in the
appendix, to suppress any reverse EMF on the release of the relay which might
cause the panel to malfunction.
2) A 24V DC output is provided at the panel to make it easy to connect ancillary
equipment. The panel can supply a continuous quiescent load of up to 100mA.
10
www.acornfiresecurity.com
www.acornfiresecurity.com

Equipment Compatibility
Additional instructions for electromagnetic compatibility
When used as intended this product complies with EMC Directive (89/336/EEC) and the
UK EMC regulations 1992 (SI 2372/1992) by meeting the limits set by the standards BS
5406 (Pts 2&3) 1988, EN50130-4 immunity and EN 61000-6-3 emission requirements.
The following installation guidelines must be followed.
1. External cables must be connected using the cable entries or knockouts provided.
2. When routing external cables inside the product they must be
a) Kept as short as possible
b) Routed close to the housing
c) Kept as far as possible from the electronics
Any modifications other than those stated in this manual, or any other use of this
product may cause interference and it is the responsibility of the user to comply with the
EMC and Low Voltage Directives.
11
www.acornfiresecurity.com
www.acornfiresecurity.com

System Overview
Simple user interface
The main element of the COP3000 user interface is a large (120mm x 90mm visible
area) touch screen display, which provides comprehensive user information and also
acts as a multifunctional keypad.
Comprehensive context sensitive help information is provided throughout the menus to
assist unfamiliar users with system operation.
The COP3000 touch screen display automatically reconfigures to suit the selected
function, for example, if the change device text menu option is selected, the touch
screen is automatically formatted as a full QWERTY keyboard to enable fast and simple
text entry.
The use of the touch screen display enables a wide range of user and engineering
facilities to be incorporated into the panel whilst still offering simple operation.
As well as a large format LCD display providing full system status information, the panel
incorporates 96 traditional zone indication LED's to provide clear information about the
status and spread of a fire even to a user who is completely unfamiliar with the
operation of the system.
In addition there are a number of system status LED's designed to give clear status
information to non technical users
User configuration and maintenance facilities
COP3000 has comprehensive facilities for on site system configuration, whereby the
user can add or remove simple devices or change device text directly via the panel,
without the need for a service engineer to visit site. For initial configuration or major
system changes special PC configuration software is available enabling Cooper Service
personnel to do this more efficiently than can be achieved using the system screen.
Exiting configurations can be uploaded to the PC so that changes can be made to the
existing system rather than having to revert to initial files.
Sophisticated sounder control facilities
COP3000 has the ability to support highly complex ringing pattern requirements.
Multistage cause and effect programming is possible whereby each addressable
sounder or output interface can be programmed independently if required and can be
set to respond to specific addresses, specific detection zones, specific panels on a
networked system or standard global ringing.
The panel supports three separate sets of programming per sounder and each stage
can be triggered differently For example, if a single sensor is triggered the panel can
12
www.acornfiresecurity.com
www.acornfiresecurity.com

System Overview
be programmed such that the sounder nearest to the sensor operates immediately and
continuously, the remaining sounders in the affected zone operate in pulsed mode and
the other sounders delay for a selectable period to allow the cause of the alarm to be
investigated before global ringing commences.
Soft addressing
COP3000 utilises intelligent soft addressing technology to greatly simplify the
installation and commissioning processes.
Once the system has been installed and the autolearn menu selected, the COP3000
control panel will automatically scan the detection loops and allocate each device with
an address number corresponding with its position on the loop, this avoids the
traditional need for manual addressing of the system devices which is time consuming
and provides a potential for error.
Every COP3000 analogue device incorporates an integral short circuit isolator ensuring
maximum system integrity. A single short circuit will not disable any loop-mounted
devices, the isolators in the devices each side of the short circuit will operate and the
COP3000 control panel will drive communication from both ends of the loop.
Simple future expansion
COP3000 is designed to ensure simplicity of future expansion.
If an additional device is added after the system has been programmed, the COP3000
will allocate the next available address, it will not alter any of the existing address
numbers allocation thus enabling simple updating of as fitted drawings etc.
Similarly if a device is removed, the relevant address is saved as a spare address for
future use, the addresses of the remaining devices are not altered.
Integral Power Supply and Battery
The COP3000 panel is designed for ease of installation, the power supply and battery
are integral to the main control panel so only a single panel is required even on large 4
loop systems.
Systems are available with either standard or extended capacity battery configurations.
Where system loading and standby period requirements necessitate an extended
capacity battery, a deeper backbox is utilised thus avoiding the need for a separate
battery enclosure.
The COP3000 charger is suitable for both standard and extended capacity batteries.
13
www.acornfiresecurity.com
www.acornfiresecurity.com

Optional printer
COP3000 panels are available with optional built in printers.
Where a printer is fitted, it is housed behind a printer cover door, which can be opened
by means of a special tool (Supplied) to provide simple and safe access to the printer
paper roll without exposure to any live equipment.
Paper replacement is extremely simple due to the drop in loading method and auto feed
printer design, the paper roll is simply dropped into the purpose designed cradle and the
end of the roll is then offered up to the printer, which will then automatically load the
paper ready for use.
The printer can be set to either print automatically or to print on demand
When a printer is not fitted, a removable, flush fitting blanking plate is used to cover the
printer paper aperture to enhance the appearance of COP3000 and to preserve its
ingress protection rating.
Hinged lockable cover.
With a standard panel, access to all panel functions is controlled by a series of pass
codes, which are entered via the touch screen display, for maximum security, a facility is
built into the COP3000 to enable the user to alter the user pass code as required.
To provide a high level of resilience, a clear hinged lockable front cover is available
which allows the screen and all of the system status indicators to be clearly seen but
prevents access without first unlocking the cover.
A single concealed locking mechanism provides access to both the printer door and the
display cover. Additional buttons are provided to scroll the display and to silence the
fault buzzer without opening the lockable cover
System Overview
14
www.acornfiresecurity.com
www.acornfiresecurity.com

Technical Specification
Power Supply (Approved EN54 pt 4)
Mains
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
Maximum Current : 750mA
Input Fuse R1 : NTC SG39 Imax 4Amp
Output Voltage including tolerances : 26V = 18.5 to 29.5Volts
: 26V RAW = 18.5 to 29.5Volts
: 5Volt Output = 4.6V to 5.5V
Ripple Voltages : 26V = 800mV
: 26V RAW = 800mV
: 5Volt Output = 430mV
Maximum Loadings : 26V O/P = 0.98A
: 26V RAW O/P = 1.7A
: 5V = 0.5A
Standby Current (4 Loops Loaded) : 26V = 280mA
: 26V RAW = 150mA
: 26V = 280mA
: 26V RAW = 150mA
: 5V = 43mA
COP6000 is protected by an internal thermal device, this requires no maintenance
* I max a, I max b & I min = Current as specified in BSEN54-4 Published 2006 (Amendments 1 & 2)
Batteries
Number of Batteries : 2
Manufacturer: :YUASA NP12-12
Capacity : 12 Ah
Battery Fuse : 6.3A Anti-Surge (F4)
Maximum battery current; : 3.5 Amps
Standby current (mA) : 175 (4 loops), 125 (2 loops)
Maximum Charging Current to the Batteries : 1.0amp
Float Voltage : 27.4 Volts
Final Voltage : 21.0Volts
Charging Characteristics : Constant Voltage with 0.970A
limit with temperature compensation
Maximum current drawn from the batteries : 3.5Amps
when the mains is not available
Deep Discharge Protection : 20.6 Volts
Battery Internal Impedance Fault : >0.5 ohms
Inputs
Addressable Loops
Max Number : 1 - 4
Max Loop Load per loop : 220 mA
Max Number of Addressable Devices per loop : 220
Class Change : Operated by external volt free contact
Outputs
Conventional sounder circuits
Number of sounder circuits : 4
Total sounder Load : 1.5 Amps
Sounder Circuit Fuses (F1/2/3/4) : 1.6 Amp (Quick Blow)
End of line resistor : 6k8
Fire Routing Equipment
Max Load : 60 mA
Fused (PTC2) : 100mA polyswitch
End of Line resistor : 6k8
15
}
* I max a
}
* I min
}
* I max b
www.acornfiresecurity.com
www.acornfiresecurity.com

End of Line resistor : 6k8
Fire Protecting Equipment
Max Load : 60 mA
Fused (PTC3) : 100 mA Polyswitch
End of Line resistor : 6k8
Fault Routing equipment
Max Load : 30 mA
Fused (PTC1) : 100 mA Polyswitch
End of Line resistor : 6k8
Auxiliary Relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load : 24 Volts 1 Amp
Fuse (PTC4) : 1.35 Amps Polyswitch
Auxiliary 24V Supply
Nominal Voltage : 24 Volts ±10%
Fuse (PTC5) : 100 mA Polyswitch
Maximum current : 30 mA
This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment
Any power taken from the alarm system will effect the standby duration
RS485 Port
This is a serial output port for driving COP6000 Repeater panels, mimics etc..
This output is short circuit protected
Max Cable Length : 2 Km
Min Recommended cable size : 1 mm² (Screened)
RS232 Port
This is a serial output port for driving COP6000 Repeater panels, mimic etc..
This output is short circuit protected
Printer (Optional)
Type : High speed thermal
Number of Characters per Line : 40
Type of paper : 58mm x 46mm Thermal Roll
Replacement paper roll order code : .ADF6PRINTERPAPER
Mechanical Specification
Weight including batteries : 18 Kg
Weight excluding batteries : 9 Kg
Dimensions (Standard batteries) : 495 mm (L) x 395 mm(H) x 180 mm(D)
Type of Material (backbox) : Mild Steel (Power Coated)
Type of Material (Facia) : PC/ABS
Flammability Rating : UL 94 V0
Total Number of knockouts : 51
Diameter of Knock out : 20 mm
Anti-Tamper Cover ( Optional)
Weight : 250 g
Material used : Polycarbonate
Flammability Rating : UL 94 5VA
TERMINAL BLOCKS : DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON
THE TERMINAL BLOCK
CAUTION
RISK OF EXPLOSION IF BATTERY IS REPLACED
BY AN INCORRECT TYPE
DISPOSE OF THE USED BATTERIES ACCORDING
TO THE INSTRUCTIONS
Technical Specification
16
www.acornfiresecurity.com
www.acornfiresecurity.com

Optional Functions as per EN54 P2&4
COP3000 is approved to EN54 Parts 2 & 4 including all the following options which can be selected
as required
Panel Outputs
Panel Sounders: (OPTION 7.8 EN54 PT 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used.
Ensure the polarity of the connections are observed at all times and end of line resistors (6K8 5%)
are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp
All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread equally across the
4 sounder circuits.
WARNING: DO NOT EXCEED THE RATED OUTPUT CURRENT
Output Fire Alarm Routing Equipment (Option 7.9 EN54 PT 2)
This output, which is fused, and monitored using a 6.8k end of line resistor, is used for the
automatic transmission of the fire signals to fire alarm routing equipment (e.g. Fire brigade). It
operates by providing 24 Volt output to an auxiliary device ( e.g. relay).
It is current limited to 30 mA using a resettable polyswitch. Class change and test conditions do
not operate this output. If operated under a fire alarm condition, the indication will be displayed on
the Touch screen display and will remain until the fire alarm is reset.
Ensure the polarity of the connections are observed at all times and end of line resistors ( 6K8 5% )
are fitted for correct operation.
Output to Fire Alarm Protecting Equipment (Option 7.10 EN54 PT 2)
This output, which is fused, and monitored using a 6.8k end of line resisters used for the
transmission of the fire signals to controls for automatic fire protecting equipment (e.g. Door
released units etc).It operates by providing 24 Volt output to an auxiliary device ( e.g. relay).
It is current limited to 30 mA using a resettable. polyswitch. Class change and test conditions do
not operate this output. If operated under a fire alarm condition , this output remains energised
until the fire alarm is reset.
Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% )
are fitted for correct operation.
Output to Fault Warning Routing Equipment (Option 9.4.1C EN54 PT
2)
This output, which is fused and monitored using 6.8k end of line resistor, is used for the
transmission of fault signals to fault warning routing equipment This output is monitored using 6k8
end of line resistor and it current limited to 30 mA.Under normal condition it operates by providing
12vdc which can be connected directly to a 12v auxiliary device.
17
www.acornfiresecurity.com
www.acornfiresecurity.com

relay).It is current limited to 30 mA.
Under fault conditions or even if the COP3000 is powered down, this output will be switch to O
volts.
Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% )
are fitted for correct operation.
Delays to outputs (Option 7.11 of EN54pt 2)
The COP3000 has the option to delay the operation of panel sounders, the fire routing equipment
output and the fire protecting Equipment. This delay is selectable using the COP3000 site installer
download software .The delay is configurable in increments of 1 minute up to a maximum of 10
minutes.
This delay can be enabled and disabled at access level 2.
The COP3000 has the facility for a specific call point to override this delay by programming this call
point via an input interface to provide an evacuate signal using COP3000 site Installer.
Coincidence Detection (Option 7.12 of EN54 pt 2)
The COP3000 has the facility to inhibit the operation of the output sounders, Output to Fire routing
equipment and the output of the fire protecting equipment until one more confirmatory signals are
received from different zones. This feature is programmable using COP3000 Site Installer
Software.
Optional Functions as per EN54 P2&4
18
www.acornfiresecurity.com
www.acornfiresecurity.com

Alarm Counter : (OPTION 7.13 EN54 PT 2)
The panel records the number of instances that it enters the fire alarm condition. This is
abbreviated in the touch screen by "AC" and it is displayed in the fire window at access level 2.This
counter can only be reset by the manufacturer.
Optional Functions as per EN54 P2&4
Inputs/Outputs to the Fire Brigade Panel
Outputs
Output 1: AUX2 output
This output is ON in alarm condition to indicate that the COP3000 Control and indicating equipment
has operated the AUX output
Output 2: Fire Routing Equipment operated "Fire Brigade Link"
This output is ON in alarm condition to indicate that the COP3000 Control and indicating equipment
has operated the fire routing equipment (option 7.9 of EN54 pt2 ).
Output 3: Disablement of Fire Protecting Equipment
This output is ON to indicate that the fire Protecting equipment has been disabled either by the
COP3000 Control and indicating equipment or the Fire Brigade Panel.
19
www.acornfiresecurity.com
www.acornfiresecurity.com

Optional Functions as per EN54 P2&4
Inputs
Input 1: Reset
This input is used to reset the control and indicating equipment
Input 2: Testing of Fire Routing Equipment
This input is used to test the output to the fire routing equipment
Input 3: Disablement of the Fire Routing Equipment
This input is used to disable the fire routing equipment output of the COP3000. Whilst the FRE is
disabled by this input, it can not be re-enabled by the COP3000 control panel
Input 4: Disablement of the Fire Protecting Equipment
This input is used to disable the fire protecting equipment output of the COP3000. Whilst the FRE
is disabled by this input, it can not be re-enabled by the COP3000 control panel
Input 5: Disablement of Sounders
This input is used to disable the sounders of the COP3000. The disablement of sounders from the
Fire Brigade Panel can be re-abled from the COP3000 control panel only when the system is not
Alarm State.
Output 4: Disablement of the Fire Routing Equipment
This output is ON to indicator that the fire routing equipment has been disabled either by the
COP3000 Control and indicating equipment or the Fire Brigade Panel.
Output 5: Reset from Fire Alarm Condition
This output is ON to indicate that the COP3000 control and indicating Equipment is in alarm
condition. This output will remain on for at least 15mins after reset or when the reset has been
activated from the Fire Alarm Brigade Panel
Output 6: Disablement of Sounders
This output is ON to indicate that the sounders have been disabled either by the COP3000 control
and indicating equipment or the Fire Brigade Panel.
20
www.acornfiresecurity.com
www.acornfiresecurity.com