Document No. 129-566
Installation Instructions
November 14, 2014
Siemens Industry, Inc. Page 3 of 8
oAux Heat (HP). Range: Yor N. By
default, this is set to N.
Enables or disables the auxiliary heat.
Typically, this is heat strips in a heat
pump system.
o2nd Stage Cool. Range: Yor N. By
default, this is set to N.
Enables or disables the second-stage
cool operation.
–Schedule Override. Range: Yor N. By
default, this is set to N.
When enabled, the scheduler function is
disabled, and the Run/Hold button does
not display on the main screen.
–H/C Delta. Range: 3to 15°. By default,
this is set to 4°.
Allows you to specify the amount of
separation between heating and cooling
setpoints. Once specified, the cooling or
heating setpoint is raised or lowered to
maintain the separation.
NOTE: The Delta T Setting is the delta,
or difference between, the setpoint
and current temperature, which is
used for determining when a heat
or cool call is activated.
–Heating Delta Stage 1 ON. Range: 1to
8°. By default, this is set to 1°.
Allows you to specifiy the delta from
setpoint that Stage 1 heating starts.
–Heating Delta Stage 1 OFF. Range: 0to
8°. By default, this is set to 0°.
Allows you to specifiy the delta from
setpoint that Stage 1 heating stops. Stage
1 turns off at setpoint + Delta Stage 1.
–Heating Delta Stage 2 ON. Range: 1to
8°. By default, this is set to 4°.
Allows you to specifiy the delta from
setpoint that Stage 2 heating starts.
–Heating Delta Stage 2 OFF. Range: 0to
8°. By default, this is set to 0°.
Allows you to specifiy the delta from
setpoint that Stage 2 heating stops. Stage
2 turns off at setpoint + Delta Stage 2.
–Heating Delta Stage 3 ON. Range: 1to
8°. By default, this is set to 6°.
Allows you to specifiy the delta from
setpoint that Stage 3 heating starts.
–Heating Delta Stage 3 OFF. Range: 0to
8°. By default, this is set to 3°.
Allows you to specifiy the delta from
setpoint that Stage 3 heating stops. Stage
3 turns off at setpoint + Delta Stage 3.
–Cooling Delta Stage 1 ON. Range: 1to
8°. By default, this is set to 1°.
Allows you to specifiy the delta from
setpoint that Stage 1 cooling starts.
–Cooling Delta Stage 1 OFF. Range: 0to
8°. By default, this is set to 0°.
Allows you to specifiy the delta from
setpoint that Stage 1 cooling stops. Stage 1
turns off at setpoint - Delta Stage 1.
–Cooling Delta Stage 2 ON. Range: 1to
8°. By default, this is set to 4°.
Allows you to specifiy the delta from
setpoint that Stage 2 cooling starts.
–Cooling Delta Stage 2 OFF. Range: 0to
8°. By default, this is set to 0°.
Allows you to specifiy the delta from
setpoint that Stage 2 cooling stops. Stage 2
turns off at setpoint - Delta Stage 2.
•Max Heat SP. Range: 5to 109. By default,
this is set to 109.
Allows you to specify the maximum heating
setpoint value. Once specified, the system
does not ramp or accept setpoints higher
than this maximum.
NOTE: High temperatures are for pool and
spa heating applications.
•Min Cool SP. Range: 6to 110. By default,
this is set to 6.
Allows you to specify the minimum cooling
setpoint value. Once specified, the system
does not ramp or accept setpoints lower
than this minimum.
NOTE: Low temperatures are for degrees
Celsius applications.
•Minimum Run Time. Range: 1to 9minutes.
By default, this is set to 6minutes.
Allows you to specify the minimum runtime
before a heating/cooling cycle turns off. This
prevents rapid cycling.
•Minimum Off Time. Range: 5to 9minutes.
By default, this is set to 6minutes.
Allows you to specify the minimum off time
before another heating/cooling cycle starts.
This provides protection against short
compressor cycles.