Sigma SDA 2000 User manual

AIR CIRCUT BREAKERS
INSTRUCTION
MANUAL
ISO 2001: 2008

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
2
ACB
CONTENTS
GENERAL
STRUCTURE
MAIN TECHNICAL PARAMETERS
CHARACTERISTIC OF THE INTELLIGENT CONTROLLER
ACCESSORIS
DIMENSIONS
SECONDARY WIRING DIAGRAM
SETTING VALUE BEFORE LEAVING FACTORY
TROUBLES AND SOLUTIONS
3
3
3
4
5
5
6
7
7

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
3
ACB
Sınıflandırma
GENERAL
Sigma SFA/SDA series intelligent Air Circuit Breakers are suitable
for use in commercial buildings or industrial plants where safety
and reliability of power supply is an important requirement.
Main Features;
• Fixed and Drawable versions
• Rated current from 630A to 6300A AC and rated voltage of 690 V.
• Short Circuit Breaking Capacity 80kA~120kA (effective value);
• Rated working voltage 690V AC
• Three or four poles;
• Microprocessor controlled intelligent trip unit for all round protection
• Manual or motor operated stored energy drive mechanism for direct or remote actutation.
• Ambient temperature: -5 ~ +40, and average temperature in 24 hours below +35 (except for special orders)
• Comply with EN 60947-2 and VDE 0660.
Environment conditions For Operation and Installation
• Altitude should be less than 2000m.
• Relative humidity: not exceeding 50% at the maximum ambient temperature. higher humidity would be permitted, but the
lowest average temperature in a month not exceeding +35°C during the most moist moth, and the maximum monthly average relative
humidity not exceeding 90% in that month, and giving consideration the dews on the goods surface, which would appear due to
temperature change.
• Pollution degree 3 grade.
• The breakers used on ships can operate reliably under normal vibration.
• The breaker should be installed in compartment of switch - board and door frame should be fixed additionally. Protection grade
is up to IP40

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
4
ACB
STRUCTURE
Front View Of The Air Circuit Breaker
SDA Series Draw-out Air Circuit Breaker
breakdown showing/return button
handle for manual energy-storage
closing button
energy storage/ energy release indicating
closed / broken showing
face
device for passing in or out
breaking button
handle and its holder position indicator
SDA-6300 SDA-4000 SDA-3200 SDA-2000

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
5
ACB
Draw-out circuit breaker
1. Terminals of secondary circuit
2. Drawer base
3. Safety separator
4. Handle
5. Terminals of secondary circuit
6. Auxiliary switch
7. Under-voltage release
8. Shunt release
9. Closing electromagnet
10. Operation mechanism
11. Motor-drive charging device
12. Intelligent controller
13. Cover

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
6
ACB
Position Of Draw-out Type Air Circuit Breakers
Connected position: Main circuit and control circuit are connected.
Test position: The main circuit disconnected and control circuit connected. Testing is possible with the panel door closed.
Disconnected position: The main circuit and auxiliary circuit are disconnected. Safety seperator is closed.
Unit door
Auxiliary circuit is ON
Back of the draw-out socker
Safety seperator
Main circuit is ON
Unit door
Auxiliary circuit is ON
Back of the draw-out socker
Safety seperator
Main circuit is ON
Unit door
Auxiliary circuit is ON
Back of the draw-out socker
Safety seperator
Main circuit is ON

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
7
ACB
Intelligent controller
Panel caption:
1. Reset button for fault releasing
2. Rated current of the breaker
3. Unit of voltage
4. Voltage indicator
5. Voltage of each line and the min, value
6. Key for selecting voltage
7. Current-time indicator
8. Unit of current and time
Indication of three phase current, neutral phase current,
grounding fault-current and the max. value
9. Key for selecting current
10. "clean " key
11. Fault showing for instantaneous
12. Fault showing for over-load short-delay
13. Fault showing for over-load long-delay
14. Fault showing for earthed error
15. Showing the long-delay current setting
(alarm simultaneously)
16. Showing the long-delay action time setting
17. Showing the short-delay current setting
(alarm simultaneously)
18. Showing the short-delay action time setting
19. Showing the instantaneous current setting
(alarm simultaneously)
20. Key for inspecting fault
21. Key for detecting wearing of contacts
22. Load supervision signal 2 (alarm simultaneously)
23. Load supervision signal 1 ( alarm simultaneously
24. Setting's decrease progressively
25. Setting's increase progressively
26. Supply socket ( DC24V) for test power
27. Memory key
28. Memory indicator
29. Non-release test key
30. Release test key
31. Setting key for various protection value
32. Indication of the earthed fault action time setting
33. Indication of the earthed fault current setting
(alarm simultaneously)
34. Release indicating
35. Test indicating
Other function:
1. Auto-diagnosis
2. Thermo-simulation
3. Fault-memory
4. MCR
The panel here in belongs to the circuit breaker of four poles,
If the breaker is of three poles, the mark IN in item 9 indicating
current of neutral phase will disappear. Other than the type
M intelligent controller with voltage indication, the other one
without voltage indication is also available (there aren't items 3,
4, 5 and 6 on the panel in this case).
NOTE:

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
8
ACB
Type SDA 2000 / SFA 2000 SDA 3200 / SDA 3200 SDA 4000 / SFA 4000
Kind Of assembly
No Of Poles
3-4 3-4 3-4
Electrical Specifications
Rated Current at 40°ºC A630, 800, 1000, 1250,
1600,2000 2500, 3200 4000
Raqted Voltage Ue V AC 680 680 680
Rated Insulation Voltage Ui V 1000 10000 1000
Rated Impulse Withstand
Voltage Uimp kV 8 8 8
Rated Short-circuit Break-
ing Capacity
Rated Ultimate Short-circuit
Breaking Capacity Icu kA
690 V
AC 50 65 65
415 V
AC 80 100 100
Rated Service Short-circuit
Breaking Capacity Ics kA
690 V
AC 40 50 50
415 V
AC 50 65 65
Category A,B A,B A,B
Pollution degree 3 3 3
Electrical life ope. 415 V 1500 1000 500
Mechanical life ope. 10000 5000 5000
Tripping Unit Electronic Electronic Electronic
Long-time delay current Ir A (0,4-1)xIn (0,4-1)xIn (0,4-1)xIn
MAIN TECHNICAL PARAMETERS

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
9
ACB
CHARACTERISTIC OF THE INTELLIGENT CONTROLLER
Current ratings
Range (Ir2)
Error Current Actions Time Time Error
(1~15)Ir1
+OFF
(OFF Position)
±10%
≤0.9Ir2 Non-trip
>1.10Ir2 Delayed-trip
Time setting (ts) 0.1 0.2 0.3 0.4 ±15%
Returnable Time 0.06 0.14 0.23 0.35 ±15%
Short-circuit short-delay protection
Current Ratings Range (Ir3) Error Current Action Characteristic
1.0 In~50A/ 75kA/100A
+OFF (OFF Position) ± 15% ≤0.85lr3 Non-trip
>1.15lr3 Trip
Short-circuit instantaneous protection
Current ratings
Range (Ir1) Error Current Actions Time Time Error
(0.4~1)In ±10%
≤1.05Ir1 <2h Non-trip
>1.30Ir1 <1h trip
1.51 Ir1 (setting time) 15 30 60 120 240 480 ±10%
2.0Ir1 8.4 16.9 33.7 67.5 135 270 ±10%
Overload long time-delay protection
Phase N Overload and Over-Current Characteristic 100% or 50% (Applicable to 3p+N or 4P)
30 40 50 60 70 80 100.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20
x ln
t (a)
kA
10000
5000
2000
1000
500
200
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
Ir1=(0. 4~1)In
Tr=(15~480)s
I2t
off
Ir2=(I.0~I5)Irl
0.4s
0.3s
0.2s
0.1s
Ir3=1.0In~50kA/75kA/100kA
Over-current protection characteristic curve
ACMIDPAV

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
10
ACB
Current ratings
Range (Ir4) Error Current Actions Time Time Error
(0.2~0.8)In
+OFF
(OFF Position)
(NA1- 2000,mi-
n160A)
±10%
≤0.9Ir2 Non-tripping
>1.10Ir2 Tripping
Setting time (Tg) 120 240 480 ±15%
Returnable time 67.5 135 270 ±15%
Single phase earth fault protection technical data:
1000
500
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
Ir4=(0.2~0.8)In
xln
t(s)
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
0.4s
0.3s
0.2s
0.1s
0.4s
0.3s
0.2s
0.1s
Earth fault protection characteristic curve

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
11
ACB
ACCESSORIES
UNDER VOLTAGE TRIP COIL UNIT
SHUNT TRIP COIL
CLOSING COIL
CHARGING MOTOR MECHANISM
When the supply voltage is reduced or below certain value, the device will then trip the breaker.
Supply voltage if reduces or below a value between from the range of 35 - 75 %, the UVT coil will then trip the breaker
instantaneusly. If the supply voltage recover above 75%, the breaker will stil remain as close.
When shunt trip coil is energized, the breaker will trip instantaneously.
When closing release is charged, this device activates closing mechanism ACB can be closed.
The closing spring is charged by electrical motor automatically. For breaker’s remote operation, Closing Coil and Shunt
Trip coil are required. Automatic recharging of closing spring makes fast operations of the O-C-O cycles.
Rated control power voltage Us(V) AC400
Action voltage(V) (0.35-0.7)Us
Reliable making voltage(V) (0.85-1.1)Us
Reliable non-making voltage(V) ≤0.35Us
Power loss(W) 48VA
Rated control power voltage Us(V) AC230
Work voltage (V) (0.7-1.1)Us
Power loss (W) 40VA
Breaking time 30~50ms
Rated control power voltage Us(V) AC230
Work voltage (V) (0.85-1.1)Us
Power loss (W) 56VA
Closing time (50±10)ms
Rated control power voltage Us(V) AC230
Work voltage (V) (0.85-1.1)Us
Power loss (W) 110VA
Energy - Storage time <5s
Operations Frequency No more than 3 times per minute

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
12
ACB
AUXILIARY SWITCH
MECHANICAL INTERLOCK BETWEEN 2 AIR CIRCUIT BREAKERS
Auxiliary switch of 4a + 4b are provided as standard.
Rated voltage (V) AC230
Conventional free air thermal current Ith (A) 10
Rated control capacity 300VA
It can realize the interlock of two horizontal or vertical-installed, three poles, drawout type or fixed type circuit breaker.
a. If need bend the cable, make sure the radian is more than 120O
b. Chack and make sure enough lubricating oil of the cable.
c. The maximal distance between two interlock circuit breaker is 2m.
2m max
R≥120 mm

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
13
ACB
OUTER AND MOUNTING DIMENSIONS
¡Fixed Circuit Breaker Mount & Outer Dimensions refer to chart 8, 9.
413(4P)
318(3P)
435(4P)
340(3P)
(Lever Connect)
(Vertical Connect)
435(4P)
340(3P)
Cabinit door
32
Chart 8 Fixed CB mount & Outer Dimensions (SFA/SDA-2000¡2000/4)
Chart 8 Fixed CB mount & Outer Dimensions (SFA/SDA-2000¡2000/4)
493(4P)
378(3P)
Chart 9 Fixed CB mount & Outer Dimensions (SFA/SDA-3200¡3200/4)
515(4P)
400(3P)
Cabinit door
(Lever Connect)
(Vertical Connect)
515(4P)
400(3P)
32
SFA-3200
SFA-2000

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
14
ACB
SDA-2000
SDA-3200
¡Drawer Type CB Mount & Outer Dimensions refer to chart 10, 11, 12, 13, 14, 15, 16.
430(4P)
335(3P)
470(4P)
375(3P)
(Lever Connect)
(Vertical Connect)
360(4P)
265(3P)
Chart 10 Drawer Type mount & Outer Dimensions (SFA/SDA-2000¡2000/4)CB
Cabinit door
461(Connect)
507(Disconnect)
20
510(4P)
395(3P)
550(4P)
435(3P)
Cabinit door
(Lever Connect)
(Vertical Connect)
400(4P)
325(3P)
461(Connect)
507(Disconnect)
c(Disconnect)
d(Disconnect)
Chart 11 Drawer Type CB mount & Outer Dimensions (SFA/SDA-3200¡3200/4)

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
15
ACB
SDA-4000
4000A
(Lever Connect)
(Vertical Connect)
Chart 14 Drawer Type CB mount & Outer Dimensions (SFA/SDA-6300¡6300/4 In=4000¡5000)
Cabinit door
504(Connect)
550(Disconnect)
569(Connect)
615(Disconnect)
Note: Panel Centre to CB Centr
Left Right Dimension is
189(3P) 2465.5(4P)
e
928(4P)
813(3P)
952(4P)
837(3P)
703(3P)
818(4P)
6300A
(Lever Connect)
(Vertical Connect)
Chart 12 Drawer Type CB mount & Outer Dimensions (SFA/SDA-4000)
Cabinit door
494(Connect)
540(Disconnect)
559(Connect)
605(Disconnect)
Note: Panel Centre to CB Center
Left Right Dimension: 57.5

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
16
ACB
Recommended Connection Busbar Information
Door Frame Dimensions and Mounting Hole Distances
Rated Current
(A)
Busbar dimension
(mm)
Number of busbar
(pcs.)
Rated Current
(A)
Busbar dimension
(mm)
Number of busbar
(pcs.)
630 40X5 2 2000 100X5 3
800 50X5 2 2500 100X5 4
1000 60X5 2 3200 120X10 3
1250 80X5 2 4000 120X10 4
1600 100X5 2 6300 120X10 6
Type a (mm) b (mm) c (mm)
2000 306 345 0
3200 306 405 0
4000 306 405 0
6300 306 405 20

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
17
ACB
SECONDARY CIRCUIT WIRING DIAGRAM
Note:
If the control power voltage of F, X, M is different, it should be connect into. different power or follow with a NO auto
energy pres to re Terminal to power supply directly manual advance energy storage. button then connect to the power
supply can output often close contact. If user put forward, terminal (4) Impressed accessories is done by users them selves.
It need to, When the intelligence work of controllers for the DC power supply. At this point, terminal cannot directly access
AC increase the DC module power.
Secondary wiring is showed by the chart ±DC V or V U(+)\U (-) input, the out of DC power module should be respectively
connect to the Seco nd two fan Block wiring terminal (+),-(x) Shunt buton (User-owned) X closing electromagnet DF Aux-
iliary contact SB voltage release or under-voltage delay time release SB undervoltage Q Under button (User-own ed) M
charging motor F shunt release O NO contact (A/AC V) SB switch-on button XT Terminal SA Micro-motor switch.
For the M-type controller with additional functions, or H-RS485/232
M a i n
circuit
intelligent controller
Electric
closed
Auxiliary switch
Electrical
disconnect
Electric
disconnect
Error Closing Energy-shorage
Disconnect
Process-
ing Unit
or
or
Main
circuit
power
Control
power
Working power
DC power module
Additional templates
10 11 12 13 14 15 16 17 18 20 21 19
J12 J13 J14 J15 J16 J17 J18 J20 J21
PN
XT
J12 J13 J14 J15 J16 J17 J18 J20 J21
FU
MXF
FU
RS485/232
converter
or DP module
Output AC/DC24V AC220V
AC380V
input
power supply transformer
Master computer
load 1F load 2F
Back-up protection
power supply
relay coil N O- contact signal lamp Fuses

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
18
ACB
SOME TROUBLES AND SOLUTIONS
FACTORY SETTING VALUES
The intelligent controller would be configured as follows, If no special demands was put forward when ordering:
Overload long-delay Current setting Ir1 In
Delay time setting t1 15S
Short-circuit short-delay Current setting Ir2 8Ir1
Delay time setting t1 0.4S
12In
Earthed errors Current setting Ir4
SFA/SDA-2000 SFA/SDA-3200, 4000 SFA/SDA-6300
0.8In or 1200A
(choose smaller-
value)
0.6In or 1600A
(choose smaller-
value)
2000A
Delay time setting t4 OFF
Load monitoring Monitoring setting C1 In
Monitoring setting ILC2
In
Fault description Reasons analysis Maintenance method
Tripping of circuit breaker
Over load tripping (IL indicator flashing)
1. Check the breaking current value and operation
time of intelligent release.
2. Analyze the load and electric network, exclude the
overload if it happens.
3. Match the actual operating current with long time-
delay current setting value.
4. Press the reset button to reclose the breaker
Circuit breaker
1. Check the breaking current value and operation
time of intelligent release.
2. Exclude the short circuit fault if it happens
3. Check the setting value of intelligent release
4. Check the normal state of breaker
5. Press the reset button to reclose the breaker
Earthing fault tripping (IG indicator flashing)
1. Check the breaking current value and acting time of
intelligent release.
2. Exclude the earthing fault if that happens.
3. Match the fault current setting value with the actual
protection.
4. Press the reset button to reclose the breaker.
Under-voltage release fault:
1. Rated working voltage is less than 70%Ue
2. Fault of control unit
1.Check the power is on or not
2.Check the power voltage of under-voltage release, it
shouldn't be less than 85%Ue.
3.Replace the control unit of under-voltage release
Mechanical interlock acting
Check the working state of two circuit breakers fixed
with mechanical interlock

AIR CIRCUIT BREAKERS
www.sigmaelektrik.com
19
ACB
SOME TROUBLES AND SOLUTIONS
The breaker can't be
closed
Intelligent release don't reset (panel is raised)
Press the reset button to reclose the breaker
Secondary circuit of drawerouttype breaker isn't
connected
Make the breaker to "making" position ("click" sound will
be heard)
Breaker hasn't stored energy
Check the secondary circuit:
1. Power voltage of motor shouldn't less than 85%Ue.
2. Check the storage mechanism, replace it if necessary.
Closing electromagnet:
1.Rated control voltage is less than 85%Us;
2.Closing electromagnet is damaged
1. Power voltage of closing electromagnet shouldn't
less than 85%Us.
2. Replace the electromagnet.
Tripping after closing the
circuit breaker (Fault indi-
cator flashing)
Closing electromagnet:
1.Rated control voltage is less than 85%Us;
2.Closing electromagnet is damaged
1. Power voltage of closing electromagnet shouldn't
less than 85%Us.
2. Replace the electromagnet.
Circuit breaker can't be
pened
Tripping immediately:
1. Short circuit current is closed
2.Delay tripping because of transient current is
high when closing;
3. Overload current is closed
1. Check the breaking current value and operation
time of intelligent release;
2. Exclude the short circuit fault if it happens;
3. Exclude overload fault
4. Check the normal state of breaker
5. Modify the current setting value of intelligent release
6. Press the reset button to reclose the breaker
can't be opened
1. Check the mechanism, if there is fault happened.
Circuit breaker
can't store energy
The breaker can't be opened by motor re-
motely
1. There is fault with mechanical operating
mechanism
2. Power voltage of shunt release is less than 70%Us;
3. Shunt release is damaged
1. Check the mechanism, if there is fault happened.
2. Check the Power voltage of shunt release is less than
70%Us or not
3. Replace shunt release
Circuit breaker can't store
energy
Manual storage can't be realized
Mechanical fault with the energy-storage device
Motor storage can't be realized
1.Power voltage of motor energy-stored device
is less than 85%Us;
2.There is mechanical fault with energy-storage
device
1. Power voltage of motor energy-stored device
shouldn't less than 85%Us
2. Mechanical fault with the energy-storage device
Handle of drawerouttype
circuit breaker can't be
drawn in or out
1. There is padlock at the "opening" position
2. Slideway or breaker body isn't pulled into its
position
1.Take away the padlock
2.Pull the slideway or breaker body into its position
Drawerout-type breaker
can't be drawn out at the
"opening" position
1.Handle isn't pulled out
2.Breaker is not totally at the "opening" position
1.Pull out the handle
2.Keep the circuit breaker totally at “opening” position
Drawerout-type breaker
can't reach the "making"
position
1. Something drop into the drawer base, and lock
the mechanism or mechanism fault happens.
2. Breaker body not match with the frame-size
rated current of drawer base
1. Check and clean the drawer base, or contact with
manufacturer
2. Match the body with relevant drawer base
No display on intelligent
release panel
1. Release isn't connected with power
2.There is fault with release
1.Check the power is connected or not
2.Cut off the power, then connect again. Otherwise
contact with manufacturer
Closing electromagnet:
1. Rated control voltage is less than 85%Us;
2. Electromagnet is damaged
1. Check the electromagnet power voltage shouldn't
be less than 85%Us.
2. Replace the closing electromagnet.
Fault indicator still flashing
after pressing the clear
button
Fault happened with intelligent release
Cut off the power, then connect again. Otherwise
contact with manufacturer
Fault description Reasons analysis Maintenance method

Yunus Emre Mah. Yenidoğan Yolu Cad. No: 30/A 34792 Sancaktepe/ Istanbul / TURKEY
Phone : +90 216 429 72 01 (pbx)
Fax : +90 216 484 41 01
www.sigmaelektrik.com
Do not risk your safety!
This manual suits for next models
4
Table of contents
Popular Circuit Breaker manuals by other brands

Siemens
Siemens 3VA9977-0UA10 operating instructions

TERASAKI
TERASAKI NHP TemBreak PRO P160 Series installation instructions

Siemens
Siemens SIRIUS S3 3RV1.4 Original operating instructions

Eaton
Eaton SBN-508 Instructions for installation, operation and maintenance

Siemens
Siemens 3VT3 Series operating instructions

Siemens
Siemens 3MT8080 Series quick start guide