manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Reliance electric
  6. •
  7. Circuit Breaker
  8. •
  9. Reliance electric FEDERAL PACIFIC DST-2 User manual

Reliance electric FEDERAL PACIFIC DST-2 User manual

Popular Circuit Breaker manuals by other brands

Siemens 3VT9524-4TG30 quick start guide

Siemens

Siemens 3VT9524-4TG30 quick start guide

Acrel ASCB1 Series Installation and operation manual

Acrel

Acrel ASCB1 Series Installation and operation manual

ABB SACE Emax 2 E2.2 manual

ABB

ABB SACE Emax 2 E2.2 manual

Eaton NOVA LBS 15 Installation and operation instructions

Eaton

Eaton NOVA LBS 15 Installation and operation instructions

ABB SACE Emax E1 quick start guide

ABB

ABB SACE Emax E1 quick start guide

Siemens SIRIUS 3RV1742 Original operating instructions

Siemens

Siemens SIRIUS 3RV1742 Original operating instructions

WEG FHU ACW125 installation instructions

WEG

WEG FHU ACW125 installation instructions

TERASAKI NHP TemBreak PRO P160 Series installation instructions

TERASAKI

TERASAKI NHP TemBreak PRO P160 Series installation instructions

Siemens Sentron 3VA9157-0PK1 Series operating instructions

Siemens

Siemens Sentron 3VA9157-0PK1 Series operating instructions

hager TS 303 User instruction

hager

hager TS 303 User instruction

ETI EFI-4B Instructions for mounting

ETI

ETI EFI-4B Instructions for mounting

Gladiator GCB150 Installation instruction

Gladiator

Gladiator GCB150 Installation instruction

nader NDM3EU-225 operating instructions

nader

nader NDM3EU-225 operating instructions

Eaton 50DHP-VR Instruction handbook

Eaton

Eaton 50DHP-VR Instruction handbook

ABB SACE Emax 2 E6.2 Instruction handbook

ABB

ABB SACE Emax 2 E6.2 Instruction handbook

Gewiss 90 RCD Installation

Gewiss

Gewiss 90 RCD Installation

OEZ LFN Instructions for use

OEZ

OEZ LFN Instructions for use

Eaton Power Defense PDG2 Instruction leaflet

Eaton

Eaton Power Defense PDG2 Instruction leaflet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

'
4
*
1
*
'
.
4
S
•
?
c
/
INSTRUCTION
MANUAL
(
;
•
:
'
•
:
/
TYPEDST
-
I
5
KV
Sr
1510
f
MAGNETIC
AIR
CIRCUIT
BREAKER
IlimilA
DATE
&
APRIL
1372
I
;
i
*
'
!
!
*
PS
*
*
o
c
V
.
0
]
•
>
0
i
0
.
'
.
"
.
'
,
3
;
.
«
+
O
0
•
o
\
t
.
a
,
'
t
0
p
*
•
jfc
‘
-
9
•
*
i
»
7
.
'
I
:
:
•
•
’
>
.
$
.
*
1
O
*
•
l
«
*
O
I
/
-
'
>
-
J
.
-
-
FtotottH
Pacific
/
150
Avenue
l
/
Newark
.
New
Jersey
07101
/
201
-
589
-
7500
e
*
s
.
FEDERAL
PACIFIC
flflT
HSU
A
NQS
SLBerme
M
.
Sm
-
»
•
POINTED
IN
U
.
S
,
A
.
Courtesy of NationalSwitchgear.com
V
:
•
TABLE
OF
CONTENTS
c
PART
I
—
GENERAL
INFORMATION
1
.
Introduction
...
..
1.1
Foreword
1.2
General
Description
.
1.3
Construction
1
A
Features
2
.
Shipping
.
.
3
*
Inspection
.
4
,
Storage
Prior
to
installation
5
.
I
nstallation
.
5.1
Preliminary
Operations
5.2
Safety
Precautions
5.3
Mechanical
Checking
.
5.4
Installation
5.4
.
1
Lifting
5.4
.
2
Arc
-
chute
Fitting
.
.
.
,
.
5.6
Racking
Operations
5.0
Manual
Checking
of
Operating
Mechanism
5.7
Electrical
Checking
of
Operating
Mechanism
'
.
..
.
.
.
PART
If
—
GENERAL
MAINTENANCE
6.1
Periodical
Inspection
6.1
.
1
Arc
-
chute
Inspection
6.1
.
2
Arcing
Contact
inspection
.
6.1
.
3
Replacement
and
Adjustment
of
Arcing
Contacts
.
.
.
6.1
.
4
Main
Contact
Inspection
6.1
.
5
Main
Contact
Replacement
.
.
.
.
6
,
2
Operating
Mechanism
Maintenance
PART
Iff
—
D
ETA
I
LED
MAINTENANCE
PROCEDURES
7
.
Operating
Mechanism
7.1
Characteristics
7.2
Principles
of
Operation
.
,
7.2
.
1
Breaker
Open
-
Closing
Springs
Discharged
7.2
.
2
Breaker
Open
-
Closing
Springs
Charged
7.2
.
3
Breaker
Closed
with
Closing
Springs
Discharged
..
.
.
7.2
.
4
Breaker
Closed
with
Springs
Charged
7.3
Troubleshooting
•
7
,
3.1
The
Breaker
Cannot
be
Closed
•
7.3
.
2
Problem
with
the
Spring
Charging
Motor
or
in
the
Chain
7.3
.
3
The
Breaker
Cannot
be
Opened
Electrically
7.4
Checks
and
Adjustments
.
.
,
7.4
.
1
Adjustment
of
the
Closing
Spring
Mechanical
Lock
.
,
7.4
.
2
Checking
the
Trip
Bar
for
Breaker
Opening
7.4
.
3
Checking
the
Closing
Release
for
Closing
the
Breaker
7.4
.
4
Adjustment
of
the
Clearance
between
the
Ratchet
Pawl
and
the
Sprocket
Wheel
to
Prevent
Overstressing
the
Pitch
Chain
3
3
4
-
’
4
4
*
5
5
5
5
5
5
5
5
:
5
S
7
7
7
7
8
8
9
v
.
“
c
•
'
)
9
9
<
10
10
10
10
IP
V
12
12
12
.
.
flu
12
12
12
12
12
12
12
12
PART
IV
—
APPENDIX
13
7.5
Fitting
,
Replacement
and
Adjustment
of
the
Trip
Latch
7.0
Replacement
of
the
Closing
Spring
.
7.7
Hydraulic
Shock
Absorber
.
.
.
,
7.8
Fining
the
Operating
Mechanism
to
the
Breaker
.
.
,
8
.
Schedule
of
Maintenance
9
.
Operating
Time
&
Contact
Velocities
10
.
Control
Power
Requirements
11
.
Wiring
Diagrams
:
AC
dose
:
OC
close
12
.
Accessories
13
.
Spare
Parts
14
.
Breaker
Contact
Settings
15
.
5
&
15
KV
Arc
-
chute
Assembly
Descriptive
Drawings
j
Refer
to
IN
-
820
,
4
A
for
metahclad
switchgear
installation
,
operation
and
maintenance
instructions
;
13
13
14
14
15
Iff
16
<
17
-
19
19
-
22
23
:
24
'
Courtesy of NationalSwitchgear.com
PART
I
Generali
Information
1
INTRODUCTION
1.1
FOREWORD
Federal
Pacific
.
Electric
Company
apparatus
:
is
built
:
to
the
highest
standard
of
quality
to
insure
continuous
reliable
-
service
with
a
minimum
of
maintenance
.
Some
routine
preventative
maintenance
is
,
however
;
required
,
on
semi
-
annual
or
annual
basis
in
accordance
with
the
various
uses
of
the
product
.
It
is
suggested
that
,
due
to
the
precision
craftsmanship
involved
in
the
construction
of
this
,
appa
-
ratus
,
no
attempts
(
with
the
exception
of
few
minor
adjustments
)
should
be
made
by
the
customer
to
fix
or
adjust
clearances
.
Should
the
need
.
occur
,
the
Field
Service
Department
of
the
.
Power
Equipment
Systems
Division
of
Federal
Pacific
,
Electric
Company
is
equipped
to
assist
you
with
any
maintenance
or
repair
which
may
be
required
throughout
the
anticipated
long
life
of
this
equipment
.
FPE
“
On
-
Site
Tbst
Facilities
"
are
available
to
you
.
This
service
includes
engineering
inspection
and
testing
of
elec
-
trical
equipment
planned
to
supplement
your
regular
main
-
tenance
-
program
,
to
improve
equipment
reliability
and
to
protect
your
investment
.
Such
services
,
for
Metal
Enclosed
,
Metal
Clad
Switchgear
,
and
other
type
Electrical
,
Apparatus
;
are
as
follows
:
(
a
)
Cleaning
of
cells
with
low
pressure
air
,
or
vacuum
.
(
b
)
Inspection
of
cell
bushings
,
cable
connections
and
;
bus
joint
connections
,
(
c
)
General
inspection
of
control
wiring
and
;
components
.
(
d
)
2500
Volt
DC
Megger
Tests
and
DC
Hl
-
pot
Tests
for
Insulation
Reliability
.
(
e
)
Protective
Relay
Calibration
Tests
for
Response
and
Time
Delay
.
(
f
)
5
KV
and
15
KV
circuit
breaker
electrical
and
mech
-
anical
operating
checks
coordinated
with
relay
response
.
(
g
)
Transformer
oil
or
askarel
dielectric
Hi
-
pot
Tests
(
also
on
minimum
oil
breakers
and
tank
type
;
oil
:
breakers
)
.
For
further
information
regarding
service
,
please
contact
the
Manager
of
Field
Service
Department
at
Newark
,
New
Jersey
.
i
i
0
0
23
0
0
r
(
'
‘
-
2
5
kV
73
,
180
and
250
MVA
CIRCUIT
BREAKER
%
.
*
%
•
"
S
'
•
;
*
<
-
r
•
•
*
.
Courtesy of NationalSwitchgear.com
•
%
1.2
GENERAL
DESCRIPTION
fF
/
gw
*
/
/
The
DST
-
2
Magnetic
Air
Circuit
Breakeris
electrically
operated
,
horizontal
drawout
for
uae
in
indoor
and
out
-
door
metaLclad
switchgear
.
It
is
designed
for
international
application
and
service
;
therefore
*
the
dimensional
data
is
given
ixi
both
the
me
*
trie
and
English
systems
.
The
hardware
is
based
on
the
metric
system
.
It
is
composed
of
three
separate
poles
supported
by
a
welded
steel
frame
(
1
)
and
provided
with
wheels
(
2
)
so
it
can
be
easily
moved
in
and
out
of
its
cell
.
Each
pole
consists
of
two
separate
parts
:
(
a
)
Arc
-
chute
(
4
)
-
Is
a
chamber
filled
with
ceramic
baffles
.
It
has
a
magnetic
structure
that
forces
the
arc
into
constric
-
tions
provided
by
the
baffling
.
The
magnetic
field
is
generated
by
coils
(
S
)
within
the
arc
chute
.
Cooling
and
elongation
of
the
arc
within
the
baffle
structure
forces
quick
extinction
of
the
arc
,
(
b
)
Contact
unit
-
is
made
up
of
the
main
contacts
,
fixed
(
6
)
and
moving
(
9
)
and
the
arcing
contacts
,
fixed
(
7
)
and
moving
(
10
)
.
The
main
contacts
,
of
silver
plated
copper
,
carry
the
normal
service
current
.
They
are
not
affected
by
the
interruption
since
they
open
before
the
arcing
contacts
separate
.
The
fixed
and
moving
arcing
contacts
are
made
with
tungsten
-
copper
arc
resistant
inlays
and
are
capable
of
•
interrupting
.
high
short
circuit
current
without
damage
.
The
puffer
nozzles
(
8
)
are
located
under
the
fixed
contacts
.
The
.
moving
contact
group
is
operated
by
the
shaft
(
11
)
,
through
insulated
:
links
(
12
)
’
.
The
metal
frame
is
grounded
through
the
ground
contacts
(
16
)
.
A
welded
sheet
steel
front
barrier
is
grounded
thus
assuring
safety
to
operating
personnel
.
The
contact
structures
are
separated
by
insulated
interphase
barriers
.
Tire
breaker
can
be
either
manually
operated
by
means
of
a
knob
(
13
)
or
Temoteiy
operated
.
The
motor
charged
spring
closing
mechanism
(
3
)
is
espe
-
cially
designed
for
medium
voltage
circuit
breakers
.
It
is
.
.
completely
enclosed
for
safety
and
dirt
exclusion
.
breaker
,
covers
the
live
parts
providing
:
protection
,
to
.
personnel
.
(
1
,
4
DST
-
2
FEATURES
/
/
7
/
#
.
I
unless
otherwise
noted
)
All
breakers
are
equipped
with
the
following
parts
and
provisions
*
(
1
)
Arc
-
chutes
(
4
)
(
2
)
Barrier
(
1
*
Fig
.
2
a
)
(
3
)
5
Unit
auxiliary
switch
with
2
-
‘
a
”
and
2
‘
4
b
”
extra
contacts
(
1
,
Fig
.
5
)
,
Other
types
available
upon
request
,
(
4
)
Lockout
switch
.
(
Blocks
closing
and
motor
circuits
)
(
17
)
(
5
)
Latch
check
switch
(
2
,
Fig
.
5
)
(
6
)
Mechanical
operation
counter
(
counts
trip
operations
)
(
18
)
(
7
)
“
Y
”
relay
(
5
,
Fig
.
5
)
(
8
)
TC
trip
solenoid
and
52
X
close
solenoid
(
3
,
Fig
.
5
)
(
9
)
Charging
motor
(
4
,
Fig
,
5
)
(
10
)
Mechanical
indication
of
“
Charged
”
and
“
Discharged
"
'
“
Open
’
'
*
or
“
Closed
”
.
(
11
)
Mechanical
indication
of
“
Open
”
and
“
Closed
”
(
20
)
(
12
)
Mechanical
indication
of
“
Charged
”
and
“
Discharged
”
(
19
)
(
13
)
Mechanical
drawout
interlock
/
prevents
movement
.
of
breaker
in
or
.
out
of
ceil
with
contacts
dosed
}
(
14
)
(
14
)
Mechanical
interlock
discharges
closing
spring
when
.
inserting
or
removing
breaker
from
cell
.
.
f
(
15
)
Padlock
provision
.
{
Lock
breaker
tripped
with
pedal
,
down
or
lock
to
prevent
racking
in
or
out
with
pedal
up
.
(
.
14
)
(
16
)
Provision
for
manual
charging
of
springs
(
21
)
(
17
)
Manuai
trip
-
close
control
knob
(
13
)
(
18
)
Automatic
Secondary
contacts
in
“
Connected
”
posi
-
tion
t
22
)
(
19
)
Manually
operated
secondary
contacts
in
“
Test
”
position
,
(
20
)
Mechanism
is
mechanically
and
.
electrically
trip
free
,
:
:
{
-
.
V
•
•
A
y
2
SHIPPING
1.3
CONSTRUCTION
The
DST
-
2
is
a
drawout
type
breaker
.
It
is
built
to
allow
ease
of
maintenance
and
operation
.
The
breaker
is
available
complete
with
ceil
or
for
insertion
into
a
metal
-
clad
breaker
ceil
.
The
breaker
can
be
positioned
as
follows
:
1
.
“
Connected
”
position
—
where
primary
and
secondary
disconnects
are
automatically
connected
.
2
.
“
Test
”
position
(
“
Isolated
”
position
)
-
where
primary
disconnects
are
disconnected
and
secondary
discon
-
nects
,
can
be
manually
connected
or
disconnected
,
.
3
.
Removed
from
the
cell
by
operating
the
“
racking
in
”
lever
,
it
is
provided
with
a
pedal
operated
interlocking
device
(
14
)
,
The
circuit
breaker
is
fitted
with
spring
loaded
,
self
aligning
primary
disconnects
which
engage
the
stationary
studs
mounted
in
insulating
bushings
in
the
cell
(
15
)
.
When
the
breaker
is
in
“
Test
Position
”
or
drawn
out
of
the
.
ceil
,
the
ceil
shutter
,
operated
by
racking
action
of
the
All
circuit
breakers
are
assembled
and
tested
for
optimum
performance
in
the
factory
before
shipment
.
The
5
kV
250
MVA
circuit
breaker
is
shipped
completely
assembled
in
one
crate
.
The
5
kV
350
MVA
and
15
kV
circuit
breakers
.
are
shipped
in
two
crates
.
The
basic
circuit
breaker
on
its
truck
with
interphase
barrier
is
in
one
crate
.
The
three
arc
chutes
are
packed
in
a
second
crate
.
.
The
serial
number
of
each
circuit
breaker
is
on
its
nameplate
,
.
It
is
.
also
sunciied
.
on
both
breaker
frame
.
and
operating
mechanism
frame
as
indicated
in
(
24
,
Fig
.
1
)
,
The
crates
are
marked
with
the
factory
order
number
.
A
copy
of
the
packing
list
,
enclosed
in
a
waterproof
envelope
is
nailed
on
the
outside
of
the
circuit
breaker
crate
.
Only
one
envelope
is
furnished
with
orders
for
more
than
one
circuit
breaker
shipped
to
a
single
destination
.
Each
circuit
breaker
,
in
its
crate
,
is
enclosed
in
a
.
poiy
»
•
ethyelene
dust
-
and
-
moisture
-
proof
bag
.
»
.
•.•
X
.
»
W
+
*
-
.
•
•
•
«
.
•
•
%
—
Courtesy of NationalSwitchgear.com
*
«
•
.
.
i
m
’
Ts
(
a
)
Check
the
alignment
between
:
the
ground
contact
(
16
,
Fig
,
l
)
and
the
grounding
blade
located
on
the
cell
floor
,
(
b
)
Insure
that
the
arc
chutes
are
properly
connected
*
(
c
)
Check
,
the
main
and
secondary
electrical
.
connections
.
(
d
)
Never
rack
the
breaker
into
the
“
Operate
-
*
position
without
the
arc
chutes
and
intexphase
barriers
prop
*
erly
installed
.
5
*
3
MECHANICAL
CHECKING
Each
circuit
breaker
is
carefully
inspected
and
operated
at
the
plant
before
shipment
:
yet
it
is
advisable
to
carry
out
some
closing
and
opening
operations
before
putting
a
breaker
into
service
.
For
detailed
,
inspection
remove
arc
chutes
and
interphase
barriers
and
follow
the
instructions
for
“
Manual
Checking
of
Operating
Mechanism
”
(
Section
5.6
)
.
5.4
INSTALLATION
5.4
.
1
Lifting
Lifting
is
to
be
done
as
described
in
Section
4
(
a
)
.
Handle
the
breaker
with
the
utmost
care
,
lift
it
using
a
hoist
or
similar
means
.
Inspect
for
breakage
.
(
See
6
,
1.1
)
5
*
4.2
Arc
chute
fitting
IRg
,
2
a
#
2
b
,
2
c
)
5
kV
350
and
15
kV
Arc
Chute
Mounting
Arc
chutes
are
shipped
separately
from
circuit
breaker
and
must
be
mounted
before
installation
.
Arc
chute
re
*
,
turn
connection
(
8
)
and
.
arc
chute
must
be
positioned
as
follows
:
3
INSPECTION
1
UPON
RECEIPT
OF
SHIPMENT
c
When
a
shipment
of
circuit
breakers
is
received
,
each
crate
should
be
examined
before
it
is
removed
from
the
railroad
car
;
:
or
truck
.
If
any
damage
or
indication
of
rough
handling
,
is
evident
,
a
description
of
the
condition
should
be
written
on
the
freight
bill
,
a
claim
should
be
filed
against
the
carrier
immediately
,
and
notice
of
the
extent
of
damage
sent
without
delay
to
Federal
Pacific
Electric
Co
.
at
the
address
from
which
shipment
was
made
,
giving
serial
number
of
the
breaker
,
the
carrier
’
s
name
,
and
the
car
number
if
shipped
by
rail
.
This
information
enables
the
company
to
supply
needed
information
to
assist
the
purchaser
in
support
of
the
claim
.
(
See
6.1
.
3
)
4
STORAGE
PRIOR
TO
INSTALLATION
A
.
.
breaker
can
be
safely
stored
provided
that
the
following
Instructions
are
observed
:
(
a
)
Handle
the
breaker
with
the
utmost
care
,
lift
circuit
breaker
less
arc
chutes
using
a
hoist
or
similar
means
and
.
attach
the
-
siing
hooks
to
the
holes
on
the
sides
of
the
breaker
.
The
5
and
!
5
kV
circuit
breakers
with
.
arc
chutes
are
lifted
by
fitting
the
sling
under
the
wheel
channels
and
securing
top
to
prevent
tipping
.
(
b
)
Upon
receipt
of
the
breaker
an
inspection
should
be
made
.
;
.
The
.
circuit
,
breaker
should
,
be
stored
,
“
Opened
*
-
and
“
Discharged
”
,
in
its
original
shipping
container
.
The
)
5
kV
and
5
kV
350
arc
chutes
should
be
stored
in
the
original
shipping
crate
.
(
c
)
Keep
the
breakers
in
a
dry
place
,
protected
against
dust
and
chemical
agents
,
preferably
in
ceils
with
ceil
or
auxiliary
heaters
energized
.
/
v
7
i
5
INSTALLATION
5.1
PRELIMINARY
OPERATIONS
Before
setting
a
breaker
into
operation
,
the
following
operations
should
be
carried
out
:
(
a
)
Carefully
clean
all
parts
of
the
breaker
with
a
dry
cloth
.
(
b
)
Check
the
condition
of
contacts
and
terminals
.
The
main
contacts
are
coated
with
a
thin
layer
of
contact
lubricant
.
If
the
main
contacts
are
dirty
they
should
be
cleaned
with
acetone
and
sparingly
reiubricated
with
FPE
^
)
551
A
5853
contact
grease
.
The
terminals
and
arcing
contacts
should
,
be
cleaned
with
acetone
.
The
three
moving
arcing
contacts
must
close
and
open
simultaneously
.
See
.
section
6.1
,
3
,
Page
7
for
adjustment
specification
.
Tighten
all
the
parts
listed
in
Appendix
S
under
"
Maintenance
to
be
carried
out
.
”
r
\
K
a
i
\
v
.
v
5
*
2
SAFETY
PRECAUTIONS
The
following
checks
should
be
made
before
putting
a
breaker
into
service
.
5
kV
75
,
150
AND
250
:
MVA
Figure
2
a
'
Courtesy of NationalSwitchgear.com
It
is
imperative
that
the
arc
chutereturo
connection
(
8
)
:
is
securely
against
arc
chute
support
,
hracket
(
6
)
.
Check
that
both
;
,
nuts
are
tight
;
affording
a
.
good
electrical
;
connections
5
.
B
RACKING
OPERATIONS
'
(
Fig
.
3
a
,
3
b
,
3
c
)
A
-
Racking
In
Procedure
:
(
a
)
With
the
breaker
medianism
at
.
the
;
"
open
"
and
.
spring
“
discharged
"
position
,
roll
the
breaker
onto
die
cell
raua
using
the
;
handling
doily
and
check
that
it
movesfreely
.
NOTE
:
Whenever
the
-
breaker
is
opened
either
electrically
through
a
remote
-
control
switch
or
manually
through
the
trip
-
close
knob
on
the
mechanism
.
This
will
automatically
free
the
-
in
*
locklock
pedal
(
2
)
permitting
the
release
-
of
the
:
interlock
bar
(
1
)
and
removes
power
to
the
.
chafing
motor
.
Electrical
power
to
the
motor
also
may
be
disconnectedly
removing
fuses
in
the
-
power
source
to
the
circuit
breaker
prior
to
any
racking
operations
performed
.
It
is
imperative
that
arc
chute
return
connection
(
8
)
is
securely
against
arc
chute
support
,
plate
(
6
)
.
Check
that
both
nuts
are
tight
affording
a
-
good
electrical
connection
,
-
•
Before
,
fitting
the
arc
chutes
on
the
15
kV
circuit
breaker
or
5
kV
350
,
make
sure
there
is
no
foreign
matter
inside
them
.
Then
:
i
(
a
)
Remove
screws
(
2
)
and
remove
the
interphase
bar
-
rier
(
1
)
.
(
b
)
Lift
arc
chute
with
lifting
yoke
(
Page
18
)
and
fit
the
conductor
pin
(
3
)
-
into
saddles
-
(
4
)
.
Arc
chute
Lifting
station
is
provided
.
in
aide
units
.
(
c
)
Rotate
the
arc
chute
downwards
until
plates
(
6
)
are
fitted
to
stud
(
7
)
,
(
d
)
Fix
the
arc
chute
-
by
means
of
nuts
on
studs
(
7
)
,
making
sure
that
the
connector
(
8
)
is
assembled
outside
of
the
-
plates
(
6
)
.
See
Fig
.
2
b
and
2
c
.
.
support
oiatM
-
(
fT
)
Art
Chut
*
Stud
c
*
*
IXM
'
Washer
.
c
*
*
4
Washer
)
<
i
4
*
7
C
®
)
/
Nuts
adjusted
to
wlddvof
su
ppo
rt
,
platen
Front
.
Arp
.
\
ChuteSupport
.
Arc
Chute
return
connection
Figure
2
b
5
kV
,
75
,
150
and
250
Arc
Chute
Mounting
Arc
chutes
are
shipped
already
assembled
to
circuit
breaker
.
In
the
event
of
arc
chute
removal
,
the
arc
chute
return
connection
(
8
)
and
arc
chute
must
be
positioned
as
follows
:
Are
Chute
support
bracket
«
*
•
>
'
-
'
£
s
:
i
•
V
.
Figure
3
a
Figure
3
b
©
1
Stud
©
i
Washer
Washer
A
/
t
2
-
>
\
A
/
•
\
0
7
*
»
Front
Arc
Chute
support
Arc
Chute
return
connection
3
1
Figure
2
c
Figure
3
c
A
.
.
"
wv
.
\
.
k
b
wJ
lL
.
»
1
.
I
-
CAMV
-
C
Courtesy of NationalSwitchgear.com
•
'
-
•
-
i
.
tr
'
:
&
$
*
(
b
)
Move
the
breaker
to
the
“
test
”
position
using
'
the
racking
lever
(
Fig
.
3
a
)
.
Shift
the
lever
back
;
and
forth
until
hearing
a
clicking
sound
of
"
the
'
interlock
bar
(
1
)
engaging
the
cell
interlock
rail
.
The
interlock
pedal
will
come
upward
and
in
-
dicate
“
blocked
”
.
If
operation
of
the
circuit
,
breaker
.
in
the
"
teat
”
position
is
desired
,
the
se
-
condary
disconnect
contacts
must
be
engaged
;
,
manually
by
sliding
assembly
forward
until
con
-
tact
is
made
with
the
ceil
secondary
assembly
and
the
lockout
switch
(
3
)
must
be
manually
re
-
set
.
[
Replace
power
fuses
(
if
removed
previous
-
ly
)
and
remove
after
completion
of
breaker
oper
-
ations
in
“
test
"
position
.
)
NOTE
:
The
lockout
switch
(
3
)
located
below
the
interlock
pedal
(
2
)
prevents
recharging
the
motor
following
any
racking
:
operations
when
the
pedal
is
depressed
.
(
c
)
To
continue
racking
to
the
“
connected
”
position
,
,
insure
that
the
breaker
has
been
tripped
electri
-
cally
or
manually
and
that
the
closing
springs
:
are
discharged
.
With
the
racking
lever
inserted
{
Fig
.
3
a
)
,
depress
the
interlock
pedal
(
2
)
and
.
rack
breaker
until
the
interlock
bar
falls
secure
-
ly
into
the
interlock
rail
slot
.
Insure
the
inter
-
lock
pedal
position
indicator
shows
“
blocked
”
.
Reset
the
lockout
switch
(
3
)
.
to
permit
eiectricai
operations
and
replace
power
fuses
(
if
removed
previously
)
..
B
*
Racking
Out
Procedure
:
(
a
)
Trip
the
breaker
either
electrically
through
a
remote
,
control
switcn
or
manually
through
the
trip
-
close
knob
on
the
mechanism
.
[
Remove
con
-
trol
source
when
part
of
operating
procedure
)
.
.
(
b
)
With
the
breaker
“
open
'
’
,
place
the
racking
lever
as
shown
in
Fig
.
3
b
.
depress
the
interlock
pedal
(
2
)
and
proceed
racking
to
“
test
”
position
.
Lock
-
out
switch
(
3
)
opens
motor
circuit
.
(
c
)
To
continue
racking
to
the
fuily
withdrawn
po
-
sition
,
operate
the
breaker
manually
to
,
insure
:
that
the
breaker
is
“
open
”
and
“
discharged
”
;
In
-
sert
racking
lever
as
shown
in
Fig
.
3
b
,
.
depress
;
interlock
pedal
(
2
)
and
proceed
racking
until
,
breaker
has
been
fully
withdrawn
from
the
;
cubicle
.
(
d
)
Insert
handling
dolly
and
remove
breaker
;
5.6
MANUAL
CHECKING
OF
OPERATING
MECHANISM
(
Circuit
Breaker
Out
of
Call
)
Charge
the
closing
springs
by
means
of
manual
charging
handle
,
then
close
and
trip
the
breaker
manually
.
Check
mechanical
operation
of
the
mechanism
.
The
breaker
should
operate
smoothly
and
freely
without
any
indication
of
binding
.
Check
that
the
control
voltage
agrees
with
the
breaker
nameplate
and
is
within
the
limits
specified
in
Appendix
10
.
It
is
suggested
that
several
mechanical
closing
and
opening
operations
be
performed
.
5.7
CHECKING
ELECTRICAL
OPERAIION
OF
MECHANISM
The
circuit
breaker
may
be
electrically
operated
safely
in
the
cell
in
the
"
Test
”
position
.
Move
the
breaker
in
the
cell
until
the
interlock
.
bar
drops
into
the
first
notch
.
This
is
the
‘
Test
”
position
.
The
.
shutter
should
remain
down
isolating
the
breaker
from
the
high
voltage
bus
.
The
secondary
circuit
is
completed
by
manually
pushing
the
secondary
contact
operating
handle
(
right
side
of
breaker
.
frame
)
all
the
way
in
(
22
,
Fig
.
1
>
,
Reset
the
lockout
switch
(
17
,
Fig
.
1
)
by
lifting
the
toggle
handle
.
Close
and
trip
the
breaker
several
times
from
the
control
switch
,
After
each
closing
operation
the
motor
will
recharge
the
closing
springs
.
r
V
PART
II
General
Maintenance
ai
PERIODIC
INSPECTION
A
schedule
for
maintenance
of
a
breaker
in
service
is
included
in
Appendix
N
’
o
.
3
;
In
addition
\
o
the
listed
operation
it
is
recommended
to
carefully
clean
the
breaker
at
least
every
six
months
.
The
contacts
and
arc
chutes
should
be
frequently
and
carefully
inspected
,
as
instructed
in
6.1
.
1
-
6.1
.
5
,
if
the
breaker
has
been
subjected
to
frequent
operations
on
short
circuits
or
overload
.
The
breaker
,
and
in
particular
the
operating
mechanism
,
should
be
frequency
inspected
if
the
breaker
has
been
subjected
,
to
dust
or
corrosive
industrial
atmospheres
.
for
defects
,
especially
the
condition
of
the
con
-
strictor
piates
.
(
3
)
If
further
transportation
is
required
,
the
arc
-
chutes
must
be
repacked
,
as
they
were
received
,
in
the
original
crates
.
(
4
)
The
arc
-
chutes
must
not
be
transported
individ
-
ually
lying
on
their
sides
because
of
the
various
fragile
porcelain
parts
.
If
abused
during
hand
-
ling
,
these
critical
parts
will
be
damaged
and
re
-
placement
required
.
(
5
)
Refer
to
1500
B
0068
or
1500
B
0069
attached
as
tvpical
for
parts
description
identification
.
(
SEE
APPENDIX
15
)
Draw
(
he
breaker
out
,
remove
the
safety
barrier
(
!
)
as
instructed
in
5
,
4.2
.
loosen
the
nuts
of
studs
(
7
)
,
rotate
the
arc
chutes
approximately
45
°
backward
one
at
a
time
by
rotating
around
pins
(
3
)
then
check
the
conditions
of
the
arc
chute
plates
.
I
.
\
6
*
1
,
1
Arc
Chute
Inspection
,
Handling
£
r
Construction
(
1
)
Arc
*
chutes
are
to
remain
in
their
crates
until
they
are
to
be
installed
on
the
breakers
.
(
2
)
They
are
to
be
removed
carefully
from
the
crates
:
and
thoroughly
inspected
at
their
final
location
-
*
rtir
?
.
*
;
:
:
*
r
‘
..
iv
-
Tk
.
"
\
2
..
•
tX
-
Courtesy of NationalSwitchgear.com
•
—
*
>
l
.
I
-
i
•
•
•
:
'
^
(
b
)
5
kV
250
,
350
and
15
kV
750
MVAv
-
Remove
.
nut
from
contact
pivot
pin
and
remove
pin
.
Remove
spring
pin
retainer
and
spring
;
pin
;
Remove
?
2
:
shunt
.
;
screws
and
remove
moving
-
arcing
contact
.
Install
new
contact
in
reverse
procedure
.
.
ISkV
500
-
Remove
*
3
studs
securing
moving
.
arcing
contact
,
to
the
blades
;
Install
:
,
new
contact
making
certain
that
nuts
are
securely
tightened
.
(
c
)
Remove
stationary
arcing
contact
springs
(
5
)
(
Fig
.
4
b
and
4
c
)
by
removing
adjusting
nuts
and
stud
.
Remove
upper
shunt
screw
.
Remove
arcing
contact
assembly
,
remount
shunt
onto
new
arcing
contacts
and
install
in
reverse
procedure
.
(
d
)
Adjust
the
moving
arcing
contact
,
making
sure
that
.
•
'
all
3
poles
close
simultaneously
and
fixed
to
moving
:
main
contact
gap
as
arcing
contacts
touch
:
5
kV
250
3
8
t
l
.
mm
(
.
32
±
.
04
in
.
)
;
5
kV
350
»
4
i
1
mm
(
.
160
±
.
04
in
.
)
;
15
kV
«
ll
±
:
2
mm
(
,
44
±
.
08
in
.
}
.
Contacts
may
be
slowly
closed
using
the
mainte
-
.
nance
bar
(
23
,
Fig
.
1
)
for
the
5
kV
breaker
,
and
“
Maintenance
Close
Device
"
(
Page
.
19
)
for
the
.
15
kV
breaker
;
(
e
)
Close
the
breaker
(
Fig
,
4
c
)
and
adjust
the
length
;
of
springs
(
5
)
to
11
±
$
mm
(
.
44
±
in
.
)
for
15
kV
500
and
14.5
(
.
57
±
;
{
Jg
'
in
.
)
for
.
—
other
ratings
.
(
0
-
Open
and
close
,
the
breaker
several
times
to
check
mechanical
operation
.
.
(
g
)
Remount
.
the
arc
chutes
and
the
interphase
barrier
as
instructed
in
5.4
.
2
,
If
any
breakages
or
flaws
on
arc
chutes
or
ceramic
plates
or
burning
on
blow
-
out
coils
are
found
,
it
is
advisable
to
replace
the
arc
chute
.
Replacement
arc
chutes
may
b
®
ordered
direct
from
the
factory
,
by
contacting
Switchgear
Marketing
,
Newark
,
New
Jersey
.
6.1
*
2
.
Arcing
Contact
Inspection
Draw
the
breaker
out
.
remove
1
the
interphasc
barrierand
arc
-
chutes
.
The
arcing
contacts
should
be
reasonably
dean
,
without
pits
and
deformations
.
Small
pits
can
be
filed
without
modifying
the
shape
of
the
contacts
.
.
In
normal
use
,
when
currents
of
approximately
the
rated
value
are
being
inter
*
rupted
,
the
arcing
contacts
might
be
slightly
worn
;
replace
-
ment
,
however
,
is
unnecessary
.
In
more
severe
service
'
when
appreciable
wear
is
noticed
,
the
arcing
contacts
should
be
replaced
as
described
in
6.1
J
..
Appendix
No
.
8
indicates
the
maximum
number
of
oper
*
ations
the
breaker
should
be
expected
to
perform
without
replacement
of
the
contacts
.
6.1
.
3
Replacement
and
Adjusting
of
Arcing
Contact
(
Figure
4
)
Draw
the
breaker
out
,
remove
theinterphase
barrier
and
arc
chutes
(
Fig
.
2
)
.
Replace
the
arcing
contacts
as
follows
:
(
a
)
Open
the
breaker
and
discharge
the
closing
springs
.
r
©
©
\
2
s
Wk
Or
(
©
SkV
75
,
150
.
250
AND
350
,
o
.
)
AND
15
kV
750
O
.
©
3
©
“
Closed
”
Position
“
Open
”
Position
FIgure
4
a
Figure
4
b
"
.
JVI
'
I
*
'
"
:
'
.
-
.
'
7
,
Courtesy of NationalSwitchgear.com
I
*
.
6.1
.
5
Main
Contact
Replacing
Draw
the
breaker
out
,
remove
the
interphase
barrier
and
arc
,
chutes
;
Replace
.
the
main
con
tacts
:
as
follows
:
(
Fig
;
'
4
d
)
-
.
(
a
)
Open
the
.
breaker
and
discharge
the
closing
:
springs
.
(
b
)
Remove
the
spring
by
unscrewing
the
locknut
and
.
removing
the
adjusting
.
screw
,
Rfentove
main
contact
;
Install
new
contacts
in
reverse
procedure
;
NOTE
:
;
Mew
self
locking
nut
should
be
used
.
(
c
)
Adjust
the
main
contact
springs
so
that
the
-
length
is
10
±
.
5
mm
(
.
40
±
.
020
in
.
)
when
the
:
contacts
are
closed
.
8
L
1
.
A
-
Main
Contact
Inspection
Draw
the
breaker
out
,
remove
the
interphase
barrier
,
and
tilt
,
the
arc
chute
back
approximately
45
°
one
at
a
time
;
.
Inspect
the
main
contacts
making
sure
they
are
in
good
condition
and
see
that
the
face
of
the
contact
is
coated
,
lightly
,
with
FPE
#
1551
A
5853
Contact
Lubricant
.
Use
only
minute
quantity
.
Since
these
contacts
do
not
break
any
current
they
should
not
be
pitted
or
burnt
.
(
See
Appendix
8
for
the
number
of
operations
the
main
contact
can
withstand
before
replacement
is
necessary
.
)
1
SkV
SOOMVA
(
.
44
*
;
»
«
;
in
.
W
f
v
.
MINIMUM
CLEARANCE
WITH
CONTACTS
ENGAGED
-
.
25
mm
(
,
01
Im
)
Locknut
t
All
othvrrat
Ings
:
i
4
.
ai
(
.
S
7
ir
;
«
|
inr
|
/
.
1
0.5
mm
a
:
-
S
r
m
I
*
7777
T
/
n
'
u
J
l
\
s
10
lOiSmm
{
.
40
±
.
020
in
.
)
*
S
*
MINIMUM
CLEARANCE
WtTH
CONTACTS
ENGAGED
*
<
25
m
nr
LOT
In
.
)
;
i
/
.
•
.
"
4
MAIN
CONTACTS
Rgyr
«
44
\
"
\
:
ARCING
CONTACTS
Figure
4
o
/
(
r
-
6.2
OPERATING
MECHANISM
MAINTENANCE
f
Figure
9
a
and
9
b
)
To
check
1
contact
'
alignment
,
'
ustf
maintenance
close
handles
(
see
Accessories
Section
)
.
The
operating
mechanism
is
supplied
thoroughly
lubricated
and
does
not
need
any
special
care
during
its
lifetime
.
It
is
*
.
•
however
,
advisable
to
clean
it
carefully
after
every
2009
Check
primary
disconnect
lingers
to
assure
that
they
are
operations
or
once
a
year
,
whichever
comes
first
,
positioned
in
a
circle
,
not
bent
,
and
clean
of
residue
*
Primary
Disconnect
Inspection
The
cleaning
should
be
done
by
means
of
a
paint
brush
drenched
with
acetone
or
$
ther
similar
solvent
with
the
breaker
“
Open
’
*
and
springs
‘
"
Discharged
”
.
The
links
,
levers
,
pins
and
chain
drive
mechanism
.
.
should
be
lubricated
with
good
quality
grease
-
-
Exxon
.
Grease
Nebula
EP
-
1
is
recommended
.
Secondary
Disconnect
Inspection
Check
molded
contact
assembly
and
moving
carriage
assem
-
bly
to
assure
they
they
are
not
damaged
and
that
the
contact
pins
are
not
bent
.
p
m
ri
O
I
s
SPRING
CHARGING
MOTOR
<
4
)
1
i
I
J
1
O
O
H
L
<
c
O
ft
i
r
4
t
O
CD
^
LATCH
SWITCH
(
2
)
<
S
>
0
<
z
>
v
.
(
TC
)
SHUNT
TRIP
OR
-
?
(
52
X
)
CLOSE
ASSEMBLY
(
3
)
ML
<
D
l
4
?
AUXILIARY
SWITCH
(
1
)
Y
RELAY
ASSEMBLY
(
6
)
FIGURE
5
'
*
•
•
>
*
.
V
r
*
Vi
-
Am
.
Courtesy of NationalSwitchgear.com
.
1
:
'
f
.
•
.
PART
111
—
Detailed
Maintenance
Prctcedyli
T
OPERATING
MECHANISM
(
TYPE
”
AE
#
I
"
)
f
1
7.2
PRINCIPLES
QFOPERATIQN
The
operating
position
!
ofi
the
mechanism
:
are
-
described
and
:
.
shown
in
the
following
:
pages
,
7.2
.
1
Breaker
Open
—
ClosingSprings
(
1
)
Discharged
(
Figure
6
a
)
The
breaker
is
in
this
position
after
each
"
C
!
ose
*
Open
"
cycle
before
recharging
.
This
is
a
transient
position
.
7.2
.
2
Breaker
Open
—
Closing
Springs
(
1
)
Charged
(
Figure
6
b
)
This
is
the
usual
operating
position
of
the
open
breaker
.
The
springs
can
be
charged
as
follows
:
(
Fig
.
6
a
)
,
.
(
a
)
Manual
Charging
.
Turn
the
shaft
(
3
)
half
a
turn
clockwise
using
the
crank
(
2
)
.
This
corresponds
to
complete
charging
of
the
springs
.
When
the
shaft
(
3
)
is
rotated
,
it
drives
the
.
shaft
(
5
)
by
means
of
the
-
chain
(
4
)
.
The
-
shaft
,
being
con
-
nected
to
lever
(
6
)
through
connecting
,
rod
(
7
)
and
.
crank
.
(
8
)
causes
,
in
its
turn
,
the
charging
of
the
springs
.
7
;
T
CHARACTERISTICS
The
:
closing
-
springe
,
of
the
operating
mechanism
are
charged
by
the
motor
.
The
spring
charging
time
is
approximately
10
seconds
;
.
The
mechanism
performs
the
following
cycles
:
(
a
)
Starting
,
with
the
breaker
open
and
springs
charged
:
CO
CO
•
TC
CO
TC
Where
:
CO
is
a
“
Gose
«
Qpen
”
operation
TC
is
the
Spring
charging
time
(
b
)
Starting
with
-
the
breaker
closed
and
springs
charged
;
CO
TC
0
CO
-
t
Where
:
0
is
an
“
Open
”
operation
t
is
the
reset
time
;
*
BREAKER
OPEN
:
CLOSING
SPRINGS
DISCHARGED
0
.
©
®
®
0
©
16
®
©
@
v
.
>
;
©
Figure
6
A
.
~
..
7
i
^
’
^
^
,
nr
!
7
:
r
/
0
?
r
*
'
*
r
r
:
,
©
:
rTT
;
trrm
r
*
*
»
«
«
IV
—
'
“
•
*
Courtesy of NationalSwitchgear.com