SJE Panel Link Light User manual

SJE PANEL LINK™
RTU
WEB-BASED CELLULAR
REMOTE MONITORING CONTROL PANEL
User Manual
SJE Panel Link
™
TM

SJE SJE Panel Link™RTU User Manual
WARNINGS
Failure to read and understand the information provided in this manual may result in personal injury or
death, damage to the product or product failure. Please read each section in its entirety and be sure
you understand the information provided in the section and related sections before attempting any of
the procedures or operations given.
Failure to follow these precautions could result in serious injury or death.
Keep these instructions with warranty after installation. This product must be
installed in accordance with National Electrical Code, ANSI/NFPA 70 so as to
prevent moisture from entering or accumulating within the controller housing.
ELECTRICAL SHOCK HAZARD
A qualified service person must install and service this product
according to applicable codes and electrical schematics.
Disconnect power prior to servicing an equipment with the
SJE Panel Link™RTU.
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable liquids. Do not install in
hazardous locations as defined by National Electrical Code,
ANSI/NFPA 70.
• Do not connect power to this equipment if it has been damaged or has
any missing parts.
• Do not install in areas with: excessive or conductive dust, corrosive or
flammable gas, moisture or rain, excessive heat, regular impact shocks,
or excessive vibration.

SJE® SJE Panel Link™RTU User Manual
TABLE OF CONTENTS
SJE Panel Link™RTU Introduction.............................................................1
Ordering Information...................................................................................2
Activation and Service ................................................................................4
Receiving and Inspection............................................................................5
SJE Panel Link™RTU Features .................................................................6
Mounting the SJE Panel Link™ RTU ...........................................................7
Activating the Battery..................................................................................8
Wiring..........................................................................................................9
Schematic .................................................................................................10
Sensor Wiring ...........................................................................................11
Mounting the Panel/Dimensions and Mounting........................................12
Wiring Methods.........................................................................................13
System View .............................................................................................14
Wiring........................................................................................................15
SJE Panel Link™Troubleshooting ............................................................16
Logging In .................................................................................................17
Access Levels...........................................................................................18
Viewing/Searching for RTUs.....................................................................19
Placing an RTU on the Map .....................................................................21
User Setup................................................................................................22
Dashboard ................................................................................................23
RTU Setup ................................................................................................24
Online/Offline Trigger Alert Setup.............................................................25
RTU Visualization .....................................................................................26
Main Screen Configuration .......................................................................28
Station Parameter Configuration ..............................................................29
Alarm Notification Setup ...........................................................................32
Connecting Alerts to Users.......................................................................33
Reports & Trending...................................................................................36
Customer Service Agreement and Terms of Use.........................................

SJE® 1 SJE Panel Link™RTU User Manual
INTRODUCTION
Designed for municipal wastewater lift stations and similar applications, the SJE Panel Link™is a simple
and eective RTU for management of a wastewater collection system via a cellular network. Alarms
are monitored and service personnel notied in the event of a failure.
Data logging and trending of critical information enables the User to visually track system performance
and recognize impending problems. The station data can be visualized in a simple and intuitive way
from your web browser on a PC, tablet or smart phone.
The SJE Panel Link™remote monitoring system is designed to be connected to most simplex or duplex lift
station type control panels. The SJE Panel Link™RTU monitors pump run, run time, cycles, amps*, and flow.
It can also monitor system in-flow*, power failure, level and level alarms*. All of this data is then relayed to the
cloud, via a cellular network, to a secure website, and can be accessed and monitored from virtually anywhere
in the world.
The SJE Panel Link™Gateway uses the RS-485 port to communicate with the following controllers:
TPC-X
The protocol used is Modbus RTU.
* Amps, flow, and level measurements require SJE Panel Link™Premium or Gateway services.

TM
ORDERING INFORMATION
Three versions are available:
• SJE Panel Link™Light (Digital I/O only)
• SJE Panel Link™Premium (Analog & Digital I/O)
• SJE Panel Link™Gateway (RS-485 - Modbus Communication)
The RTU module can be supplied for direct panel mounting, or pre-assembled in NEMA 4X enclosure
for outdoor mounting near an existing panel.
Note: SJE Panel Link™units include 1 year of cellular service, small antenna, & user manual.
SJE® 2 SJE Panel Link™RTU User Manual
SJE Panel Link™
1. SJE Panel Link™RTU
For installation inside a control panel.
Parts Included:
SJE Panel Link™
Premium
+
100/150/200A
Current Transducer
(Premium version only)
SJE Panel Link
™
TM
ID: 640012L
SJE Panel Link
™
TM
ID: 64000P
SJE Panel Link™
Light
or
2. SJE Panel Link™NEMA 4X Panel
For installation outside a control panel or for retrot applications
Includes:
• 10X8X6 NEMA 4X thermoplastic enclosure
• SJE Panel Link™
• DC Power supply and battery backup
*The battery backs up the digital inputs only.
• Requires 120/240 VAC supply power
• I/O terminals for hard wiring with existing control panel
• 100/150/200A to 4-20mA current transducer (Premium version only)
• Can monitor lift stations with up to 2 pumps
or SJE Panel Link
™
TM
ID: 640012L
SJE Panel Link™
Gateway

PRIMEX®3 SJE Panel Link™User Manual
3. Antenna Options
Standard Antenna
Small Antenna
1038339 - 3DB Antenna, with 1m cable
Small Antenna + Angle Bracket
1038339 - 3DB Antenna, with 1m cable
1031802 - SS angle bracket for antenna
(For side mount only)
1028317 - Cord seal
High Gain Antenna
Included with every SJE Panel Link™unit
suitable for installation of the module in a Fiberglass
or Thermoplastic enclosure
IP67 Compliant
Can be mounted directly to the panel
(through the top or side enclosure wall).
Use with steel/stainless steel enclosure or
when signal is weak.
1m cable with SMA connector.
Surge Protector Option
Mounts on a
1.5” - 2.0” pole
(Pole not included)
Part# Assembly part numbers
1038899 ANTENNA ASSEMBLY, 40FT PUMP WATCH
Assembly Includes
1038516 ANTENNA, CELL, PENTA BAND, OUTDOOR
1038517 BULKHEAD ADAPTOR, N-FEMALE TO SMA-FEMALE
1038518 CABLE ASSY, MA-MALE TO SMA-MALE, 48”
1038520 CABLE ASSY, N-MALE TO N-MALE, 40’
Part# Assembly part numbers
053788 ANTENNA, ADPT WITH SA, BULKHEAD, N-F TO SMA-F
1038518 1038517 1038520 1038516
Includes:
1053788
SJE Panel Link
™
TM
SJE Panel Link
™
TM
SJE Panel Link
™
TM
SJE Panel Link
™
TM

SJE Panel Link
™
TM
ID: 640012L
ACTIVATION AND SERVICE
The data management for Panel Link™remote cellular devices is hosted by: AMI Global Incorporated,
6280 S. Valley View Blvd. Suite 212, Las Vegas, NV 89118
All SJE Panel Link™RTUs are provided with a year of pre-paid cellular service. Activation of your
device is required for operation. An account needs to be setup with AMI if this is your first Panel Link™
device. AMI will contact you directly for service payment after the first year is completed.
Activate a new
SJE Panel Link™device.
User must send Activation request
to a SJE®contact person
including the device ID + existing
account name.
SJE® will forward request to AMI via:
Support @aquamanagement.com
Device typically activated within 2
hours
(During office hours 9am-5pm Pacific
time.)
User must fill in the Account Setup
form and send it to a SJE Panel
Link™contact person.
Data needed:
- Device ID number
- Name and email of End User
(will get the bill for service after the
first year)
- New Account name
(Example: City of Fargo)
- User login name request.
SJE® will forward request to AMI via:
Support @aquamanagement.com
New Account will be created within 24
hours + device activated.
End User
Will receive login instructions via email.
Will verify contact and billing information.
Existing account?
(User already has an
account and
SJE Panel Link™devices)
YES NO
SJE Panel Link™ID number (Located on the device)
LIGHT:
ID: 64XXXLIGHT - LTE
PREMIUM:
ID: 69XXXPREMIUM - LTE
GATEWAY:
ID: 67XXXGATEWAY - LTE
The Account Setup Form (on the next page) can be downloaded from:
https://www.sjerhombus.com/products/sje-panel-link/
https://csicontrols.com/product/sje-panel-link
SJE Panel Link™– Cellular RTU
SJE Panel Link
™Account Setup and Activation Form
Fill in for
New or Existing account information
Account
Name: Example: City of Fargo
First Name: Example: John
Last Name: Example: Doe
Email
Address: Example: jdoe@cfargo.gov
Phone: Example: (123) 456-7890
Billi
ng Address: Example: 1234 Elm St
Cit
y, State, Zip Example: Fargo, MN 58102
Logi
n User Name: Example: Fargo123
Pump Watch
Unit ID: Example: 68023
FAQ
Who sho
uld use this form?
End Users
who wish to create an account for monitoring Panel Link units.
End Users
will be responsible for the service fee after the initial period is complete.
(Panel Link
Lite = 1 year. Panel Link Premium = 1 year)
Example
of End Users: A City, Municipality, Water district, Utility Service Company, etc…
Why crea
te an account?
This form
provides contact and billing information to AMI (Service Company). This will allow them to contact the End
User dire
ctly with service renewal options after the initial period is complete.
A login an
d password will be setup to grant access to the SJE-Rhombus (www.sjerhombuslogin.com) web portal.
Where to
send this form?
Complete
this form and send to your SJE-Rhombus contact person:
Jeremy Drin
kwine (800-746-6287 x3345) Jeremy.Drinkwine@sjerhombus.com
Matt Huse
When to
create a new account?
This form
must be submitted at least 24 hours prior to the Panel Linkactivation.
What happ
ens next?
Once the
form is submitted, the End User will receive an e-mail (sent to the email address entered in this form) from
AMI with
a link and instructions for login and account verification. Click on the link or cut and paste it into our
browser.
Once the account is verified, power up the device for final activation and setup. The device is then ready for
use. Note:
For security reasons, this must be done within 48 hours or the link will de-activate.
For activ
ation of future Pump Watch RTUs
Once the
account is setup, the End User can activate additional Panel Links in the future by filling in the Account
Name and
the Device ID of the Panel Link device that needs to be activated.
SJE® 4 SJE Panel Link™RTU User Manual

SJE® 5 SJE Panel Link™RTU User Manual
RECEIVING AND INSPECTION
(Premium version only)
SJE Panel Link
™
TM
ID: 640012L
SJE Panel Link
™
TM
ID: 64000P
SJE Panel Link™PremiumSJE Panel Link™Light
No analog terminals Two analog inputsLight Unit ID
SJE Panel Link
™
TM
ID: 6400018G
SJE Panel Link™Gateway
Gateway Unit ID
Premium Unit ID

SJE® 6 SJE Panel Link™RTU User Manual
-
POWER
0V
(GATEWAY)
432112
Battery
ON/OFF
BATT
ON OFF
SJE PANEL LINK™ FEATURES

TM
MOUNTING THE SJE PANEL LINK™ RTU
5.5”W x 4.5”H x 3.5”D (with antenna at 90 degrees as shown)
Can be din rail mounted or panel mounted with 4 screws.
SJE® 7 SJE Panel Link™RTU User Manual

SJE® 8 SJE Panel Link™RTU User Manual
ACTIVATING THE BATTERY
Battery Connection
The SJE Panel Link™ module is equipped with a small Li ion battery. This battery will
enable operation during power loss (24 Vdc) and send out alert notifications for power
loss and any digital input alerts. Note: The battery is not able to power the 4-20mA loop
sensor (Digital inputs only). This battery is shipped disconnect and must be turned ON
when starting up the device.
Legacy version (external battery):
New version:

SJE® 9 SJE Panel Link™RTU User Manual
WIRING
SJE PANEL LINK™PREMIUM RTU SCHEMATIC
24 VDC
Supply
Power
REMOTE
ACTIVATION
CONTACTS
(NON-POWERED)
TORQUE TO: 4.4-7.1 IN-LBS
ATTENTION:
CONNECT CONTACT CLOSURE
INPUTS TO NON-POWERED
CONTACTS ONLY
LEVEL
XDCR
CURRENT
XDCR
PUMP 1 RUNNING
PUMP 2 RUNNING
ALARM 1
ALARM 2
ALARM 3
ALARM 4
COMCOM P1 P2 A1 A2 A3 A4 IN2IN1NC CNO 0V +24
BACKUP BATTERY CONNECTION
SJE PANEL LINK
™
SJE PANEL LINK™LIGHT RTU SCHEMATIC
24 VDC
Supply
Power
REMOTE
ACTIVATION
CONTACTS
(NON-POWERED)
TORQUE TO: 4.4-7.1 IN-LBS
ATTENTION:
CONNECT CONTACT CLOSURE
INPUTS TO NON-POWERED
CONTACTS ONLY
PUMP 1 RUNNING
PUMP 2 RUNNING
ALARM 1
ALARM 2
ALARM 3
ALARM 4
COMCOM
P1 P2 A1 A2 A3 A4 NC CNO 0V +24
NO CONNECTION
BACKUP BATTERY CONNECTION
SJE PANEL LINK
™

SJE® 10 SJE Panel Link™RTU User Manual
PUMP WATCH™ GATEWAY SCHEMATIC - PC-3000X CONTROLLER
LCX3
PUMP 1
PUMP 2
PUMP 3
ALARM
ESC
PRESS FOR ENTER
TM
When using the SJE Panel Link™ Gateway with the TPC-X controller, the following functions are
not available:
• Current monitoring (there is no analog input on the conroller for motor Amps).
• Today’s Cycle Starts and Runtime. The previous 24h total is displayed (the controller does
not have Real Time Clock.

SJE® 11 SJE Panel Link™RTU User Manual
SENSOR WIRING
CURRENT SENSOR EXAMPLE
Connect the current transducer as shown on the schematics. Open the core of the current tranducer
by pressing on the lever. Ensure that one (1) incoming power conductor passes through the center
of the current transducer.
PUMP RUN SIGNAL EXAMPLE
Wire the pump run inputs to
a non-powered auxiliary contact in the
control panel, which closes when the pump
is called to run. These must be wired for
each pump.
Motor contactor auxiliary contacts
for reference only. Actual contactor
conguration may dier.
*Premium version only

SJE® 12 SJE Panel Link™RTU User Manual
MOUNTING THE SJE PANEL LINK™ PANEL
Mount the SJE Panel Link™ panel using a solid base such as treated posts with a treated plywood
overlay. Mounting on Unistrut or other metal structure is also common. Please use the appropriate
hardware for securely anchoring the panel to the metal structure.
TM
8.5” Enclosure Width
11.125”
Mounting Screws
10.5”
Enclosure Height
5.625” Mounting Screws
6.3” Depth

SJE® 13 SJE Panel Link™RTU User Manual
WIRING METHODS
When wiring the SJE Panel Link™ panel, be sure to use liquid-tight conduit or strain relief fittings.
Liquid-tight
conduit ttings Liquid-tight conduit
OR
CONDUIT OPTIONS
Use liquid tight fittings and conduit to run cables between the SJE Panel Link™ and the
Lift Station control panel. Do not run conduit from the SJE Panel Link™to the wet well.
Conduit
TM

SJE® 14 SJE Panel Link™RTU User Manual
SYSTEM VIEW
SJE PANEL LINK™INSTALLATION EXAMPLE
6 7 F T
.
TM
TM
6 7 F T
.

SJE® 15 SJE Panel Link™RTU User Manual
WIRING
SCHEMATIC
-+
SJE
PANEL LINK™
SJE
Panel Link™
* SJE Panel Link™Premium is shown above. See pages 8 and 9 for additional versions.

SJE® 16 SJE Panel Link™RTU User Manual
SJ PANEL LINK™TROUBLESHOOTING
Indicating LED on the SJE Panel Link™ RTU
Function LED (top of RTU)
LD12 Green - External power (24Vdc). (Right)
LD1 Green - Cellular Modem Power.
LD2 Blue - Connecting to Cellular network (on power up).
LD3 Red - Alarm/Fault present (LIGHT or PREMIUM)
LD4 Yellow - Heartbeat Flash = ONLINE. Fast Flash = OFFLINE
I/O Status LED at the bottom of the RTU
Each input has a corresponding LED indicator above the input terminal
The relay output also has an LED indication.
(See page 12 for details.)
RTU COMMUNICATION
The user can check the RTU signal strength (RSSI) on the web portal. Hover your cursor over the signal
strength icon on the top of the main screen.
RSSI THRESHOLDS
RSSI is a measurement of the power present in a received radio signal (Received Signal Strength Indicator).
The larger the number, the better the reception.
Below is a guideline to appropriate strength thresholds:
1-5 = very poor (no communication)
6-8 = poor (inconsistent communication)
9-11 = good (little to no communication issues)
>12 = best
-
POWER
0V
(GATEWAY)
43
2112
Battery
ON/OFF
BA
TT
ON OFF
Function LED’s

Please Enter Your Information
LOGGING IN
Click on the following link or type in the following URL in your browser to open the login screen.
http://www.sjepanellink.com
Google Chrome or Mozilla Firefox are the recommended web browsers.
CUSTOMER SERVICE AGREEMENT AND TERMS OF USE
This agreement outlines the agreement between AMI and the end User and must be agreed to before
access to the cloud interface is allowed.
An automatic email is generated and sent to the email address you entered. Follow the link in the email
to verify and activate your account.
After logging in again, you will need to agree to the Terms of Use. These steps only need to be
completed during the initial setup and activation of your account.
Notes:
The end User should activate this product. When the initial 1 year of cellular service comes to an end,
AMI will contact you directly and review renewal options. The primary User (Account Admin) will be
able to add additional Users for login and alarm notification. The cellular service plan provided with the
Panel Link™only covers text (SMS), and data for the SJE Panel Link™unit. It does not cover SMS and
Data service charges incurred for the use of your personal cell phone or tablet.
SJE® 17 SJE Panel Link™RTU User Manual
This manual suits for next models
2
Table of contents