VENTING APP ICATION
VSP Series are sealed combustion type boilers, they maybe
installed and vented either as direct vent boiler which all air for
combustion is obtained directly from outside or as non-direct
vent boiler which air for combustion is taken from inside the
boiler room.
VSP boilers must be vented by proper 3" diameter. Stainless
Steal venting system (see “vent material” on this page) through
the roof or sidewall.
BOI ER ROOM AIR SUPP Y AND VENTI ATION
An ample supply of air is required for combustion and ventila-
tion. When buildings are insulated, caulked and weather-
stripped, now or later on, direct openings to outside may be
required and should be provided. If the boiler is not near an
outside wall, air may be ducted to it from outside wall openings.
Provisions for combustion and ventilation air must be made in
accordance with section 5.3, Air for Combustion and Ventila-
tion, of the National uel Gas Code, ANSI Z223.1-latest edi-
tion, or applicable provisions of the local building codes. The
following recommendation applies to buildings of energy-saving
construction, fully caulked and weatherstripped.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES
TWO UNOBSTRUCTED OPENINGS OR PASSAGE O AIR
INTO THE BOILER ROOM:
A. NON-DIRECT VENT INSTA ATION
1. Air drawn horizontally from outdoors DIRECT Y
through an outside wall; one louvered opening near the
floor and one louvered opening near the ceiling, each open-
ing with a minimum REE air passage area of 1 square
inch per 4000 Btuh of total appliances’ input.
2. Air drawn horizontally through HORIZONTA DUCTS;
one opening near the floor and one opening near the ceil-
ing, each opening with a minimum REE air passage area
of 1 square inch per 2000 Btuh of total appliances’ input.
3. Air drawn VERTICA Y from outdoors; one opening at
the floor and one opening at the ceiling, each opening with
a minimum REE air passage area of 1 square inch per
4000 Btuh of total appliances’ input.
4. Air drawn from inside the building; one opening near
the floor and one opening near the ceiling, each opening
with a minimum REE air passage area of 1 square inch
per 1000 Btuh of total appliances’ input.
I BOILERS ARE INSTALLED ADJACENT TO OTHER UEL
BURNING EQUIPMENT, THE AREA O REE OPENINGS
MUST BE APPROPRIATELY INCREASED TO ACCOMMO-
DATE THE ADDITIONAL LOAD.
B. DIRECT VENT INSTA ATION
Adequate air supply should be provided to prevent overheating
of the boiler controls and boiler room. Openings for passage of
air into the boiler room for direct-vent installation must be at
least 1⁄2 of the openings required for the non-direct vent as men-
tioned above.
If additional non-direct vent appliances are installed in the same
space and adequate air openings are provided for them, there
are no additional air openings required for the VSP boiler.
or both direct and non-direct installation, the following must be
considered:
- Openings must never be reduced or closed. If doors or
windows are used for air supply, they must be locked open.
- Protect against closure of openings by snow and debris.
Inspect frequently.
- No mechanical draft exhaust or supply fans are to be
used in or near the boiler area.
- Boiler area must never be under negative pressure. The
flow of combustion and ventilating air to the boiler must
not be obstructed.
F UE GAS VENTING REQUIREMENTS
The Victory VSP series boiler is a high efficiency, mechanically
induced draft boiler and, therefore, requires different venting
arrangements than natural draft, lower efficiency boilers.
THE OLLOWING INSTRUCTIONS MUST BE CARE ULLY
READ AND OLLOWED IN ORDER TO AVOID ANY HAZ-
ARDOUS CONDITIONS DUE TO IMPROPER INSTALLATION
O THE AIR INTAKE AND LUE GAS VENTING SYSTEM.
The vent piping installation MUST be in accordance with these
instructions and with ANSI Z223.1-latest edition NATIONAL
UEL GAS CODE, Part 7, Venting of Equipment. Other local
codes may also apply and must be followed. Where there is a
conflict between these requirements, the more stringent case
shall apply.
The use of a vent damper is NOT permitted on this boiler series.
VENT MATERIA
The vent system for direct or non-direct vent installation must be
UL listed single wall 3” diameter AL29-4C* stainless steel materi-
al. The following manufacturers’ systems are approved for use
within a specified minimum and maximum equivalent vent length
for each model. Proper adapter must be used as a connector
between Victory VSP boilers flue collar and venting system as
shown below:
VICTORY VSP Models 5
*AL29-4C is registered Tr dem rk of Allegheny Ludlum Corp
He t-F b P rt Numbers for v rious items of vent system re listed in
Sl nt/Fin P rt List, Public tion No. VSP-10PL
Manufacturer Type/System Adapter art Sealant
No.
Heat- ab. Inc. Saf-T Vent Not Required RTV 106 or Dow
Corning 732
Heat- ab. Inc. Saf-T Vent Not Required Not Required
EZ Seal
ProTech asNSeal SA-SLB-3 Not Required
System, Inc.
lex-L StaR-34 SRA SA3 GE-1S806
International, Inc.
Z- lex, Inc. Z-Vent O2SVSSLA2 GE, RTV 106