SMART-HOUSE BGP-COD-BAT User manual

User Manual
Over Hadstenvej 40, DK-8370 Hadsten
Phone +45 89606100, Fax +45 86982522
Certified in accordance with ISO 9001
MAN BGP-COD-BAT rev.10-07.07
15-029-276
Programming unit
Type BGP-COD-BAT
Mode of operation
The BGP-COD-BAT is a portable programming unit used for
reading or programming channel code(s) in the ASIC-based
series of smart-house products.
Once the battery is installed, the BGP-COD-BAT is ready for use.
Connect the cable between the programming unit and a smart-
house module type G..
5 keys provide the means of operating the BGP-COD-BAT: two
keys are used for reading and programming, two keys for
changing Groups and Channels and one key for selecting the
desired Input/Output.
The current coding is displayed by 4 x 8 LEDs. The top row of
LEDs displays the selected input or output. The two middle rows
display the current channel group, while the bottom row dis-
plays the current channel code.
« In/Out » - Key
This key is used to scroll through the I/O's of a module. If a new
module is connected or if consecutive channel codes are allo-
cated to the I/O's, pressing the « In/Out » key has no effect
since all smart-house modules are preprogrammed to their
physical number of inputs/outputs. This key is also used to
switch between consecutive and individual coding of the I/O's.
To change the mode, keep « In/Out » pressed for more than 2
seconds.
« Group » - Key
Used to select the Group address within the range A to P. The
Group LED will shift one position right for each key activation.
« Channel » - Key
Used to select the channel(s) within the group. The Channel
LED will shift right one, two or four positions, depending on the
number of inputs/outputs. If consecutive channels are select-
ed, then pressing the « Channel » key will have no effect.
« Read / On » - Key
Used to turn on the BGP-COD-BAT and to read the channel
codes of the connected module. When the reading is complet-
ed, the display will show the channel code of the module: either
1, 2, 4 or 8 inputs/outputs.
2, 4 or 8 In/Out LED's being ON indicates that consecutive
channel codes are allocated to the I/O's, e.g. input 1 coded to
P1, input 2 to P2 input 8 to P8.
If only one In/Out LED is ON, then the I/O's are coded individu-
ally, e.g. input 1 to C5, input 2 to D4 etc. The code for each
I/O is
indicated by a group LED and a channel LED.
If the BGP-COD-BAT is not connected to a smart-house system,
it will turn off within two seconds.
15-029-276_BGP-COD-BAT MAN.qxp:BGP-COD-BAT MAN 9/25/07 11:52 AM Page 1

« Prog » - Key
When the displayed I/O-coding corresponds to the desired
channel configuration, the codes will be downloaded to the
smart-house module when pressing the « Prog » key.
After programming is executed, a verification takes place. If this
verification fails, all activated LEDs in the display will flash two
times, and the programming unit will switch off.
If such behaviour occurs repeatedly on the same module, the
module may be faulty. If several modules fail to download, the
BGP-COD-BAT may be faulty.
Individual In/Out channel programming
The BGP-COD-BAT features an additional mode of single-channel
editing. Pressing « In/Out » for more than 2 seconds will
change the operating mode to singlepoint programming. The «
In/Out » key is now used to select one of the eight possible
inputs/output, thus making individual channel coding possible.
The In/Out-LEDs assign the display channel code to the corre
-
sponding physical input/output of the module.
In singlemode the « Channel » key also has the ability to disable
an In/Out-position. « Channel » must simply be pressed past
channel 8, whereby both the Channel LED and the Group LED
will turn off. To reenable, just press « Channel » again.
It is possible to change all eight Inputs/Outputs, even though
some smart-house modules are built for only 1, 2 or 4
Inputs/Outputs.
To exit single channel programming, just keep the
« In/Out » key pressed for 2 seconds.
Output status setting
On receivers it is possible to configure the status of the outputs
during smart-house failure. Normally, any output of a receiver
will go off during smart-house failure. In some cases the invert-
ed function is desirable (e.g. light applications - turn on light if
the smart-house is down).
To change output status, the BGP-COD-BAT must be put into
configuration mode. This is done as follows:
•Remove any connect
ed smart-house system.
• Keep both « In/Out » and « Group » pressed, while pressing
« Read/On ».
The first In/Out LED now turns on. Connect the smart-house
system, and press « Read/On ». If output status is set, then
channel LED 1 will illuminate. Pressing « Channel » will toggle
the output status On/Off.
Press « Prog » to store.
If « Read/On » is pressed when no smart-house system is con-
nected, the LEDs will flash to indicated a false condition. Only a
successful reading will reset this condition.
Other features
To code a smart-house module off-line, neither smart-house nor
power to supply the module is required. Simply connect the
module to the programmer and start coding.
If On-line coding (module connected to an operating smart-
house system) is performed, the module automatically discon-
nects ifself from the smart-house and returns to normal opera-
tion after the programmer cable is disconnected.
The BGP-COD-BAT automatically turns off when no key has been
pressed within the last 30 seconds.
If the connection cable is removed from the smart-house
module, the BGP-COD-BAT will switch off within 2 seconds.
Low battery indication
When battery is low, the In/Out row of LEDs will roll center-
wards in an eye-catching manner.
Warning
When using the BGP-COD-BAT you must connect the cable to
the BGP-COD-BAT before connecting the cable to any smart-
house module that is to be coded. Even so, the cable must first
be removed from the smart-house module before disconnecting
it from the BGP-COD-BAT.
Without observing these precautions you may destroy the ASIC
inside the smart-house module through static discharges.
Caution
To ensure long battery life, always remember to remove the
cable from the smart-house modules. The smart-house
modules will be kept in an inactive state as long as the BGP-
COD-BAT is connected.
Addition
al information
Scope of supply:
1 x programming unit
BGP-COD-BAT
1 x cable
GAP CAB
1 x user manual
MAN BGT-COD-BAT
Not supplied:
1 x 9 V battery type 6LR61
15-029-276_BGP-COD-BAT MAN.qxp:BGP-COD-BAT MAN 9/25/07 11:52 AM Page 2
Popular Controllers manuals by other brands

IDEC
IDEC SmartAXIS Touch FT1A Series instruction sheet

Sensibo
Sensibo Sensibo Air installation manual

Quantum
Quantum qpod 2e instruction manual

StoneL
StoneL Axiom AN Installation maintenance and operating instructions

Norden
Norden NVS-AC10006VC user manual

Vaillant
Vaillant VAZ CPC installation instructions