Smartscape DALI-RD20-M User manual

1
DALI-RD20-M
DALI Broadcast Controller
Installation
Manual

2
THE DALI-RD20-M MUST BE INSTALLED BY A LICENSED ELECTRICIAN
IMPORTANT INFORMATION
ELECTRICIANS MUST READ PRIOR TO INSTALLATION
•This product must only be installed by persons who are appropriately licensed by the applicable State
regulatory body.
•This product must be connected to circuits that incorporate 10 A rated circuit breaker protection.
•Hazardous voltage exists at the terminals of this product. Ensure the circuit is isolated before removing
this product from the wall or electrical enclosure.
•Damage caused by incorrect installation, force-majeure, electrical surges, lightning, power grid
fluctuations, water or by connection to alternative power supply sources (such as solar inverters, etc.) is
not eligible for warranty repair.
Device Overview
The DALI P20 is a DALI broadcast controller for control of up to 20 DALI fittings. Its integral DALI power supply
means no other hardware is required for this controller to operate.
With an input for a movement detector and programmable options for Turn on Level, Sensor mode, Run on Timer
and Minimum Level the DALI P20 is not only simple to install and use but also extremely flexible in its
functionality.
Installation Instructions
Before installing this product read all instructions carefully and please keep this installation manual for future
reference.
WARNING: To prevent electric shock, please ensure that power is isolated before installation.
This product is designed for indoor use only.
The DALI-RD20-M is designed to be mounted in the ceiling (typically near the first fitting) with the supplied cable
run down to the switch plate mounted rotary encoder. Suitable switch plate is provided by the installer.
Installation must be carried out by a qualified electrician in accordance with National Wiring Regulations and
other applicable regulations. Compliance to Low Voltage Directives may be invalidated if not used or installed
according to the published specification.
The DALI-RD20-M contains no user serviceable parts and should be returned to the manufacturer for repair.
Rotary Encoder
The encoder is an ELV device and connected with an ELV cable. The installer must adhere to Australian electrical
standards when installing this device near LV cables and devices.

3
Wiring Diagram –Basic Setup
Wiring Diagram –with Optional Extras

4
The Supply end of the DALI-RD20-M has a terminal block that accommodates up to 1.5mm2wire for electrical and
DALI cable connection.
Connection
Description
240V
N
Electrical Neutral
A
Electrical Active
SENSOR
Sensor Input (220-240VAC trigger input)
NC
not connected
DALI
-
DALI Data -
+
DALI Data +
The rotary encoder end has two RJ12 sockets for connection to the rotary encoder/s. Two encoders are
used when 2-way switching/control is required.
DALI TECHNICAL INFORMATION
Installer technical information for DALI based products:
•DALI requires 2 wires to connect between devices. These wires are not polarity dependant.
•These DALI wires are classed as FELV (functional Extra Low Voltage) and due to isolation issues should
always be treated as being at mains potential, therefore requiring so a suitable mains rated
•DO NOT CONNECT 240V TO THIS CABLE
•Cable size
DALI Cable Run Length
Recommended Minimum DALI Cable Conductor Size
Less than 100 Meters
0.5mm²
100 to 150 Meters
0.75mm²
More than 150 Meters
1.5mm²
More than 300 Meters
Not recommended, avoid runs over 300 Meters
•DALI Standard –IEC 62386
SPECIFICATIONS
Electrical
Nominal Operating Voltage 220 to 240V a.c.
Nominal Operating Frequency 50Hz
Maximum Load 24VA
Maximum Wire Size 1.5mm2
Environmental
Ambient Operating Temperature Range 0 to 50oC
Relative Humidity 5 to 95% non-condensing
Altitude 0 to 3000m MSL%
Control
Load Per DALI ballast 2mA
Maximum Number of DALI Ballasts 20
DALI Operating Mode Broadcaster

5
DALI Data Encoding Manchester
DALI Data Baud Rate 1200
DALI Data Cable Requirement 2 wire double insulated
Maximum DALI Cable Length 300m with 16AWG cable (2V line drop maximum)
Physical
Product Dimension 125mm (L), 40(W), 30mm (D)
Installation Cut-out 63mm (L), 50mm (W), 50mm (D)
(Switch plate supplied by others)
Installation Indoor Use Only
Programming Information
How to change programmable Options;
1. Press and hold the push button for 10 seconds to enter programming mode (at 5 seconds you will
see one Blue flash, keep holding for 10 seconds). Once in programming mode;
•The Blue LED will flash a number of times to indicate which programming option you have
selected.
•The Red LED will then flash a number of times to indicate what mode that option is set to.
2. Press the push button to change the current option to the next mode.
3. Rotate the knob a quarter turn clockwise to change to the next option or anticlockwise to change to
the previous option.
4. To exit programming press and hold the push button for 10 seconds or wait 30 seconds and it will
exit automatically.
List of Programmable options, modes of each and defaults.
Option 1. Turn on level
Mode 1. 100% - default
Mode 2. Last level
Mode 3. User Defined
Option 2. Sensor mode.
Mode 1. Manual on, Auto off - default
Mode 2. Auto on, Auto off
Mode 3. Disabled
Option 3. Sensor run on time.
(Amount of extra time after no 240 input from sensor)
Mode 1. 0 Minutes - default
Mode 2. 15 Minutes
Mode 3. 30 Minutes
Mode 4. 60 Minutes
Option 4. Minimum Level.
Once this mode is selected (flashes twice for the mode) rotate the knob to the desired
minimum level and press the knob again to save this level.
Default is 1% but many fittings show little result below 15-20%
Option 5. Power-on state
Mode 1. Do Nothing
Mode 2. Force to 0%
Mode 3. Force to 100%
Mode 4. Force to last known level - default
Blue flashes = Option #. Red flashes = Mode #.

6
Optional input board –DALI-RD20-INVF & DALI-RD20-INVS
-INVF = Volt fee inputs for local push buttons
-INVS = 12-24VDC inputs for remote switching
Input wire colour codes;
Black and Green - 0V/Common
Input 1 –Brown
Input 2 –Red
Input 3 –Orange
Input 4 –Yellow
Function of Inputs set by Dip Switches.
Only 1 dipswitch to be on at a time.
Mode 1(default on INVS). Dip switch 1 on.
Input 1 –On
Input 2 –Off
Input 3 –Toggle between On/Off
Input 4 –Not used
Mode 2. Dip switch 2 on.
Input 1,2,3,4 –Preset 1,2,3,4
Mode 3(default on INVF). Dip switch 3 on.
Input 1 –Toggle between Preset 1/Off
Input 2,3,4 –Preset 2,3,4
Mode 4. No dip switches on.
Spare –no function implemented.
Preset Defaults:
Preset 1= 100%
Preset 2 = 75%
Preset 3 = 50%
Preset 4 = 25%
CONTACT DETAILS
Smartscape Connected Lighting Systems
Unit 1, 84 Newmarket Road,
Windsor Qld. 4030 Australia
Phone +61 (07) 3357 1922
Website http://www.ssqld.com.au
Email [email protected]
DISCLAIMER
Smartscape Qld Pty. Ltd. reserves the right to alter specifications and design without further notice.
Smartscape Qld Pty. Ltd. will not be held responsible for the misinterpretation of printed material
contained in this manual. Further enquiries should be directed to Smartscape Qld Pty. Ltd. using the
listed contact details.
Table of contents
Popular Controllers manuals by other brands

Hanwest
Hanwest HAN-L62 User operating instructions

Dell
Dell H310 user guide

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series Migration guide

Enttec
Enttec DMXEtherGate Mk2 manual

HighPoint
HighPoint RocketRAID 3G mini-SAS HBA Series installation guide

Helios
Helios KWL-MZB-BE Installation and operating instructions