BASIC OPERATION
A. General. This water boiler is an induced draft
applianceandisequippedwithcontrolsfor proper
operation. All controls must be in proper working
order.Contactaqualifiedservice agency to provide
annual maintenance as specified in Installation,
OperationandMaintenanceManual.
1. Limit. See Figure 1.A device which automati-
callyinterrupts boiler operationwhenthewater
temperature exceeds the set point. Maximum
allowabletemperatureis 220°F (104°C).
Original equipment with this boiler is a
Honeywell L4080B1253. Boiler operation is
interrupted when system temperature reaches
cut-out temperature.Boiler operation resumes
automatically when system temperature falls
approximately 15°F (8°C) below the cut-out
temperature.
2. Flame Rollout Switch. SeeFigure1.Adevice
whichautomaticallyinterrupts boiler operation
when flames or excessive heat are present in
thecombustionarea.Thecontrolis a single use
device. If the control is activated to interrupt
boileroperation,do not attempttoplaceboiler in
operation.Contactaqualifiedservice agency.
3. Pressure Switch. SeeFigure1.Adevicewhich
automaticallyinterrupts boiler operationwhen
thereisexcessiveblockagein the ventsystem
orfan motordoesnotoperate.Thiscontrolisan
automaticresetdevice.Ifcontrolisactivatedto
interrupt boiler operation, do not attempt to
place boiler in operation. Contact a qualified
serviceagency.
4. Pilot.The pilot providestheignitionsourcefor
themainburners.Your boiler has an intermittent
pilot. The intermittent pilot ignites only when
there is a call for heat and extinguishes when
thecallforheatends.See Figure 5.
5. GasValve.The gas valve monitors pilot flame
andregulatesgasflowto the burners and pilot.
SeeFigure1.
6. Safety Relief Valve. A device which protects
the boiler against excessive pressure.The safe-
ty relief valve can discharge a large amount of
hot water - the installer should provide piping
to discharge water near floor at a floor drain.
See Figures 2 and 3. If the safety relief valve
discharges water, follow instructions TO TURN
OFF GAS TO APPLIANCE (see Figure 4), and
contact a qualified service agency.
B. Instructions to place boiler inoperationandtoturn
offtheboilerareshown on the OperatingInstruction
Labelpostedontheinnerjacketpanelof the boiler.
Theinstructions are also showninFigure4.
C. SequenceofOperation.
1. Thermostat calls forheat,energizes circulator.
2. Limit senses boiler water temperature.Prevents
operation until water temperature falls approxi-
mately 15°F (8°C) below the cut-out tempera-
ture.
3. Fanenergizes.
4. Gasvalveenergizes.
a. Igniteron.
b. Pilotgason,ignitingpilot.
5. Pilotflamedetected.
a. Igniteroff.
b. Maingason,ignitingmainburners.
Note: If pilot flame is not detected within 30
seconds, the igniter is turned off for 30 seconds,
and then turned back on. If the pilot is not
detected within 30 seconds, the igniter and pilot
gas are turned off for 5 minutes. The sequence
then resumes at Step 4a.
6.Call forheat ends.
Pilot and main gas off, extinguishing pilot and
mainburners.
If this sequence is not followed exactly, follow
instructions TO TURN OFF GAS TO APPLIANCE
(see Figure 4) and contact a qualified service
agency.
WARNING
Service on this boiler should be undertaken
only by trained and skilled personnel from a
qualified service agency.
HVX USER’S INFORMATION MANUALPAGE 2
CAUTION
Should overheating occur or the gas supply fail
to shut off, do not turn off or disconnect the
electrical supply to the pump. Instead, shut off
the gas supply at a location external to the
appliance.
Do not use this boiler if any part has been under
water. Immediately call a qualified service
agency to inspect the boiler and to replace any
part of the control system and any gas control
which has been under water.