
Finned copper tube gas boilers & water heaters – Boiler Manual
12
OUTDOOR VENTING
WheninstalledoutdoorstheFuteraIII mustbe edwiththefactory
supplied outdoor hood, air intake adapter with lter and exhaust
terminal, see Figure 10. Multiple units must be spaced per Figure 11.
eboiler/heater mustbe atleast2 ,.62 m fromanydoor, window
or gravity air inlet into any building and at least 3 , 1 m from any
overhang unless local codes dictate dierently.
Avoid locations where wind deection o of adjacent walls, buildings
or shrubbery might cause a downdra. e unit(s) should be located
at least 3 , 1 m from structures. Outdoor installations are not
recommended in areas where the danger of snow blockage exists.
Do not place the boiler/water heater in a location that
would subject it to runo from adjacent buildings or
damage may occur voiding the warranty!
COMMON VENT SYSTEMS
On multiple boiler common vent applications, the master boiler
may be required to be rst on and installed closest to the verticle
chimney (consult factory).
If an existing boiler/water heater is removed from a common venting
system, the common venting system may then be too large for the
proper venting of the remaining appliances connected to it. At the time
of removal of an existing boiler/water heater, the following steps shall
be followed with each appliance remaining connected to the common
venting system placed in operation, while the other appliances remaining
connected to the common venting system are not in operation.
Aumomentduretraitd’unechaudièreexistante,lesmesuressuivantes
doiventêtreprisespourchaqueappareiltoujoursraccordéausystème
d’évacuation commun et qui fonctionne alors que d’autres appareils
toujours raccordés au système d’évacuation ne fonction-nent pas:
système d’évacuation
a) Seal any unused openings in the common venting system.
Scellertouteslesouverturesnonutiliséesdusystèmed’évacuation.
b) Visually inspect the venting system for proper size and horizontal
pitch and determine there is no blockage or restriction, leakage,
corrosionandotherdeciencieswhichcouldcauseanunsafecondition.
Inspecter de façon visuelle le système d’évacuation pour déterminer
la grosser et l’inclinaison horizontale qui conviennentet s’assurer que
le système est exempt d’obstruction, d’étranglement de fruite, de
corrosion et autres défaillances qui pourraient présenter des risques.
c) Insofar as is practical, close all building doors and windows and
all doors between the space in which the appliances remaining
connected to the common venting system are located and other
spaces of the building. Turn on clothes dryers and any appliance
notconnectedtothe common venting system.Turn on any exhaust
fans, such as range hoods and bathroom exhaust, so they will
operate at maximum speed. Do not operate a summer exhaust
fan for a boiler installation. Close replace dampers.
Dans la mesure du possible, fermer toutes les portes et les fenêtres
du bâtiment et toutes les portes entre l’espace où les appareils
toujours raccordés du système d’évacuation sont installés et les
autres espaces du bâtiment. Mere en marche les sécheuses, tous
les appareils non raccordés au système d’évacuation commun et
tous les ventilateurs d’extraction comme les hoes de cuisinère
et les ventilateurs des salles de bain.
S’assurer que ces ventilateurs fonctionnent à la vitesse maximale.
Ne pas faire fonctionner les ventilateurs d’été. Fermer les registres
des cheminées.
d) Place in operation the appliance being inspected. Follow the lighting
instructions. Adjustthermostatso appliancewill operate continuously.
Mere l’appareil inspecté en marche. Suivre les instructions
d’allumage. Régler le thermostat de façon que l’appareil fonc-
tionne de façon continue.
e) Test for spillage at the dra hood relief opening aer 5
minutes of main burner operation. Use the ame of a match
or candle, or smoke from a cigaree, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min ensuite,
déterminer si le coupe-tirage déborde à l’ouverture de décharge.
Utiliser la amme d’une allunee ou d’une chandelle ou la fumée
d’une cigaree, d’un cigare ou d’une pipe.
f) Aer it has been determined that each appliance remaining
connected to the common venting system properly vents when
tested as outlined above, return doors, windows, exhaust fans,
replace dampers and any other gas-burning appliance to their
previous condition of use.
Une fois qu’il a été d éterminé, selon la métode indiquée ci-dessus,
que chaque appareil raccordé au système d’évacuation est mis à l’air
libredefaçoradéquate.Remerelesporteset lesfenêtres,les ventilateurs,
lesregistresde cheminéesetlesappareils au gazà leurpositionoriginale.
g) Any improper operation of the common venting system should be
corrected so the installation conforms with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54. When resizing any portion of the
common venting system, the common venting system should be
resized to approach the minimum size as determined using the
appropriate tables in Appendix F in the National Fuel Gas Code,
ANSIZ223.1/NFPA54 and or CAN/CGAB149InstallationCodes.
Tout mauvais fonctionnement du systéme d’évacu-tion commun
devrait étré corrigé de façor que l’installation soit conforme au
National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes
d’installation CAN/CGA-B149. Si la grosseur d’une section du
système d’ évacuation doit étré modiée, le système devrait étré
modié pour respecter les valeurs minimales des tableaux pertinents
de l’appendice F du National Fuel Gas Code, ANSI Z223.1/ NFPA
54 et (ou) des codes d’installation CAN/CGA-B149.
GENERAL PIPING REQUIREMENTS
Improper piping of this boiler/water heater will void the
manufacturer’s warranty and can cause boiler failure
resulting in ooding and extensive property damage!
Excessivewaterhardness causingscalingin thecopper heat
exchangertubes isNOTcovered underthemanufacturer’s
warranty, see Table 9. Excessive piing and erosion of the
internalsurface ofthecopper heat exchanger tubesis NOT
covered under the manufacturer’s warranty if the result of
highwaterowrates, seeTable8.Returnwatertemperatures
below 125°F, 52°C will result in heat exchanger damage
from excessive condensation voiding the manufacturer’s
warranty, see Primary/Secondary Piping, Figure 13.