socomec ATyS FT User manual

www.socomec.com
To download, brochures,
catalogues and technical manuals:
www.socomec.us/resources/
Preliminary operations
Check the following upon delivery and after removal
of thepackaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
Qty 1 x ATyS FT
Qty 1 x C66 Controller
Qty 1 x Harness
Warning
Risk of electrocution, burns or injury to persons
and / ordamage to equipment.
This Quick Start is intended for personnel trained in
theinstallation and commissioning of this product.
For further details refer to the product instruction
manual available onthe SOCOMEC website.
• This product must always be installed and
commissioned by qualied and approved personnel.
• Maintenance and servicing operations should be
performed by trained and authorized personnel.
• Do not handle any control or power cables connected
tothe product when voltage may be, or may become
present on the product, directly through the mains or
indirectly through external circuits.
• Always use an appropriate voltage detection device
toconrm the absence of voltage.
• Ensure that no metal objects are allowed to fall in
thecabinet (risk of electrical arcing).
Failure to observe good engineering practices as well
as tofollow these safety instructions may expose the
user and others to serious injury or death.
Risk of damaging the device.
In case the product is dropped or damaged in any
way itis recommended to replace the complete
product. Installation standards must be respected.
Accessories
Accessories are not included and must be
ordered seperatly
• Terminal shrouds (see step 6A).
• Additional aux contacts (ref. 96990021).
• Digiware I/O 10 (ref. 48290140).
• Transformer 480 - 240 VAC (SPARTAN SP350MQMJ).
• Controller 24 VDC aux power supply
(6W minimum type SELV) mandatory with I/0 10 Modules.
• Power terminal lugs (see step 1D).
For further details refer to the product instruction
manual under chapter “Spares and Accessories”.
Spares
• ATyS C66 Controller (ref. 16000066).
• UL 1008 ATyS FT (ref. 960XXXXX).
• Connector kit (ref. 16090002).
• Controller Nema 3R gasket (ref. 16090001).
• Controller mounting screws (ref. 16090004).
• Controller mounting feet (ref. 16090005).
• Cable harness without transfomer (ref. 96964000).
• Cable harness with transfomer (ref. 96974000).
CORPORATE HQ CONTACT:
SOCOMEC SAS,
1-4 RUE DE WESTHOUSE,
67235 BENFELD, FRANCE
0: Without solid neutral
1: With solid neutral
N° of poles
2: 2P
3: 3P
4: 4P
9 6 X X X XXX
For Use on a Flat Surface of a Types
1, 3R, 12 and/or 12k enclosure.
Non contractual document. Subject to change without notice.
548695E
QUICK START GUIDE EN
ATyS FT
100 A, 200 A, 260 A, 400 A
Installation and Commissioning
Reference configurator
Switch installation
Cabinet / Back
Plate Installation
STEP 1
Connecting
the cable harness
STEP 2
Controller
interface
STEP 3
Operational limits
STEP 4
Manual operation
STEP 5
Accessories
STEP 6
1A
Rating
010: 100 A
020: 200 A
026: 260 A
040: 400 A
PE
Source 2
Load
Source 1
0: spare switch for networks up to 480 VAC
8: ATSE assembly for 480 V.a.c 3 wire network
A: ATSE Assembly for networks up to 480 VAC
Mounting orientation

D
18.31
465
5.7
144,8
14.92
379
7.13
181
min. 2.75
min. 70
Max. 14
Max. 355,6
Min. 13.3
Min. 338
4.23
107,5
L
2.02
51,4
8.01
203,4
1.77
45
PB
W
H
4x Ø 0.41
4x Ø 10.5
9.45
240
2.52
63,90
1.89
48,10
7.09
180
6.30
160
8.66
220
A
3.93
99,8
1.56
39,7
Dual Dimensions
in/mm
SWITCH DIMENSIONS MINIMUM ENCLOSURE SIZE
A B L P H W D
in mm in mm in mm in mm in mm in mm in mm
100-200A
2P 10.47 266,30 1.25 31,80 3.85 98,70 1.38 35 20 508 16 406 12 305
2P+N/ 3P 11.85 301,30 1.25 31,80 5.49 133,70 1.38 35 20 508 16 406 12 305
3P+N/ 4P 13.24 336,30 1.25 31,80 6.60 168,70 1.38 35 20 508 16 406 12 305
260-400A
2P 11.67 296,30 1.55 39,30 5128,60 1.97 50 48 1220 24 610 12 305
2P+N/ 3P 13.63 346,30 1.55 39,30 7178,60 1.97 50 48 1220 24 610 12 305
3P+N/ 4P 15.60 396,30 1.55 39,30 8.97 228,60 1.97 50 48 1220 24 610 12 305
Product dimensions
Switch & minimum enclosure size dimensions (4th pole represented with lugs installed.)
Controller dimensionsSwitch top view
1B

Screw Tightening torque
PH1 / 0.2 Nm 1.77 lb.in
For use on a at suface of Types 1, 3R, 12 and/or 12K enclosure.
Clip the mounting feet in
thedesignated slot
Screws notdelivered with product
5.9
+/-0.4
150
+/-1
6.77 - 7
172 - 178
0.25
6,4
R 0.24
R 6,25
0.12
3
1.53 ±0,01
39 ±0,3
0.86
22,05
0.05
±0,02
15,5
±0,5
135°
0.07
2
0.31 ±
0,004
8 ±0,1
Use terminal screws and washers supplied with the ATSE
Product
Rating (A) Designation Ref. lugs
Quantity
per
reference
Openings
per lug
Size / Section
(AWG)
Pressure screw
torque Bolt torque
Y
min. max. lb.in Nm Size in lb.in Nm Size in mm
100A
Ilsco D0957
Contact us 114 1/0 50 5,65 870.8 85 mm 0.625 15,9
200A
Ilsco D2831
Contact us 1 6250 KCMIL 275 31,1 5/16 70.8 85 mm 125,4
100-200 A
CMC LA-300R
39542020 2
1 6 300 KCMIL 275 31,1 5/16 70.8 85 mm 1.12 28,439543020 3
39544020 4
260-400 A
CMC LA-630R
39542040 2
14600 KCMIL 550 62,1 1/2 310 35 8 mm 1.79 45,739543040 3
39544040 4
260-400 A
Ilsco D3096
Contact us 14600 KCMIL 600 67,8 1/2 310 35 8 mm 1.79 45,7
Power cable connections : For 100A use 1/0 AWG / For 200A use 250 KCMIL / For 260A use 300 Kcmil / For 400A use 600 Kcmil copper cables.
Mount the load terminal lugs on the
switch terminals before mounting source
2 terminal lugs.
Door mounting
Backplate mounting
Mounting & connecting controller
1C
Installing terminal lugs (optional accessory)
1D
PE
Insert the 4 door
mounting screws in
thedesignated slot
and push back to
clip in lock in place.
1
2
Gasket for Type 3R/12
8.66
+/-0.4
220
+/-1
6.30+/-0.4
160+/-1
PE

TYPE TERMINAL N° DESCRIPTION CHARACTERISTICS RECOMENDED CROSS
SECTION
Switch power input 101-102 Order switch to position S1 194-304 VAC 8 A for at
least 100 ms 50/60 Hz
17-14 AWG
1-2.5 mm²
201-202 Order switch to position S2
Switch Signalization output
333-334 Contact closed if cover is closed Internal use for
ATyS C66 controller
313-314 Contact closed if the switch is in position S1
323-324 Contact closed if the switch is in Position S2
See step 6B
for Auxiliary
contacts
Connector tightening torque
0.5 N.m / 4.4 Lb.in
Mounting & connecting the cable harness
2A
Mounting the cable harness on the Switch
2B
SOURCE 2
A
A
B
B
C
C
N
N
SOURCE 1
For details on the cable harness wiring diagram and integration see Cable harness Quickstart guide ref 551401.
Cable harness without transformer (ref. 96964000) delivered with 96AX XXXX products.
Cable harness for connections with transformer (ref. 96974000) delivered with 968X XXXX products.
Note: transformers not delivered with the product.
Fix FASTON connectors
according to thetable in
step 2C.
(Max 2FASTON per pole).
Wires must not be in contact with active voltage points such as unused
FASTON connections and lugs. In order to do so any unused or loose
cables must be tensed then xed on a non conductive part of the transfer
switch (use cable tie xation points as shown in the images below).
1
Pass wiring harness in theintegrated
cable duct.
After all the faston cables have
been connected make sure
the cables are tight and x
them in place using the cable
tie point shown below.
This switch also includes provision
for additional cable ties these can be
used to maintain cables connected to
the auxiliary contacts.
Use the cable tie connection point on the side of the
switch shown above to maintain any unused cables
(for 2P, 2P+N or 3P switches).
3
4
5
After xing the FASTON
maintain thewires in place
wiring connexion point.
2
CONTROL
POSITION OUTPUTS
101
102
201
202
334
333
314
313
324
323
Connectors
Tightening
Torque:
0.5Nm/4.4lb.in
194-304Vac 50-60Hz (>100ms)
S2 S2
S2
S1
S1
S1
Cover Closed
black cables
for source 2
red cables
for source 1

RTSE FASTON CONNECTIONS
VOLTAGE TRANSFORMER
480 VAC 240 VAC
PRIMARY SECONDARY
NETWORK TYPE TYPE SOURCE A B C NH1 H4 X1 X4
240 VAC 2P S2 S2A & 201 S2B None
(1)
None
(1)
S1 S1A & 102 S1B None
(1)
None
(1)
120/240 VAC 2P + N S2 S2A & 201 S2B None
(1)
S2N
S1 S1A & 102 S1B None
(1)
S1N
208 VAC 3P S2 S2A & 201 S2B S2C None
(1)
S1 S1A & 102 S1B S1C None
(1)
120/208 VAC 3P+N / 4P S2 S2A & 201 S2B S2C S2N
S1 S1A & 102 S1B S1C S1N
277/480 VAC 3P+N / 4P S2 S2A S2B S2C S2N & 201
S1 S1A S1B S1C S1N & 102
480 VAC + transfo 3P S2 2xS2A 2xS2B S2C -T2A T2B T2A' T2B'
S1 2xS1A 2xS1B S1C -T1A T1B T1A' T1B'
(1) Cables which are not used are to be fastened as shown in image 4 of step 2B.
Connect the faston on the switch connexion according to your network and the table below:
Connection of harness on the switch
Controller connection details
2D
2C
TYPE TERMINAL N° DESCRIPTION CHARACTERISTICS RECOMENDED
CROSS SECTION
TIGHTENING
TORQUE
Sensing source 1 SOURCE 1
L1/L2/L3/N
Voltage sensing inputs source 1
& voltage supply (L1-L2) Sensing voltage
50 - 575 V.a.c P-P - 50/60 Hz (+/- 10%)
Supply voltage (L1-L2)
88 - 576 V.a.c - 50/60Hz (+/- 10%) Ui 600V
AWG 18-14
0.75-2.5mm²
0.5-0.6 Nm
4.4-5.3 lb.in
Sensing source 2 SOURCE 2
L1/L2/L3/N
Voltage sensing inputs source 2
& voltage supply (L1-L2)
Inputs
71 IN1: SWITCH IN POS1
Do not connect to any external power
supply AWG 20-14
0.5-2.5mm²
72 IN2: SWITCH IN POS 2
73 IN3: DOOR OPEN
74 IN4: programmable input 4
75 IN5: programmable input 5
76 IN6: programmable input 6
70 Common point for inputs
Aux power supply 81/82 - : negative terminal for aux supply
+: positive terminal of aux supply 12-24 Vd.c.
Outputs
12/14/11 OUT1: POS 1 ORDER
Dry contacts
8A / 277 VAC 50/60 Hz
5A / 24 VDC AWG 16-14
1.5-2.5mm²
22/24/21 OUT2: POS 2 ORDER
32/34/31 OUT3: programmable output 3
42/44/41 OUT4: programmable output 4
52/54/51 OUT5: programmable output 5 (latching)
62/64/61 OUT6: genset start relay
Current transformers IN/I3/I2/I1 CT neutal / CT phase C / CT phase B/ CT phase A CT input 1A or 5A
Serial connection RS485
Connection RS485
-: negative terminal of RS485 bus
+: positive terminal of RS485 bus
NC : Ground
RS485 bus insulated LiYCY shielded twisted pair
30-14 AWG / 0.14 to 1.5 mm²
1.9 - 2.2 Lb.in
0.22 -0.25 Nm
Digiware* DIGIBUS Connection point for I/O 10 optional accessories &
digiware connection (must use 24 VDC input) RJ 45 digiware cable - -
* For more information check I/O module instruction sheet ref 545597
Wiring harness connectors toplace on controller.
Bottom view
Top view

ATyS C66
AUTO
LCD display
Source and
switchsynoptic
Standard code for programming : 1000
Manual operation buttons
and indicator
Communication
indicator LED
Switch not in automatic mode
indicator LED
Automatic button and
LED indicator
Test button and indicator for
load tests / no load tests
Short press for lamp test /
Long press to reset faults
Power, Fault and alarm LED
Navigation buttons
Change dashboard / set screen
as favorite
3
Controller Interface
When powered for the rst time the controller will prompt the user to congure using the wizard.
To access the wizard input code 1000 then the conguration will go as follow:
SMART WIZARD CONFIG:
Foradvanced conguration go to parameters menu.
Language Source configTime & date Switch &
Application Product Name Communication
In STEP 5/8 of the wizard cong make sure the network detected matches your network.
In STEP 6/8 make sure the “switch technology” parameter is set to “ATyS FT”.
If a fault is shown on the controller, correct the associated fault and clear by doing a long press (>3s) on the lamp test button.
Left side hinge door Right side hinge door
Mounting the cable harness on the controller
2E
or
For details on the controller connectors refer to step 2D, after inserting the required connectors use the cable tie connection points shown below to
maintain the cables in place:
black cables
red cables
bbb
b
b
b
br
r
r
r
r

OPERATING VOLTAGE @ 50/60 (+/- 10%) HZ
NETWORK MINIMUM COIL
OPERATING VOLTAGE (VAC)
MAXIMUM COIL
OPERATING VOLTAGE (VAC)
277/480 VAC 194 (Ph/N) 304 (Ph/N)
120/208 VAC 194 (Ph/Ph) 304 (Ph/Ph)
120/240 VAC 194 (Ph/Ph) 304 (Ph/Ph)
480 VAC with transformer 194 (Ph/N) 304 (Ph/N)
OPERATING TIMES
(1)
RATING TRANSFER DESCRIPTION MINIMUM TRANSFER TIME (ms)
(NORMAL TO ALTERNATE)
MINIMUM TRANSFER TIME (ms)
(ATLTERNATE TO NORMAL)
MAXIMUM TRANSFER TIME (ms)
(NORMAL TO ALTERNATE)
MAXIMUM TRANSFER TIME (ms)
(ATLTERNATE TO NORMAL)
100-200 A Contact transfer time
(2)
24 21 31 27
Total transfer time
(3)
100 280 127 486
260-400 A Contact transfer time
(2)
30 27 45 32
Total transfer time
(3)
106 286 141 491
(1) All times measured without load and at 240 VAC at ambient temperature, actual times may vary depending on network and load.
(2) Time for which load is disconnected from both source 1 and source 2 with both sources available.
(3) Total time to transfer including detection of source total failure and transfer times.
OPERATING TEMPERATURE
SWITCH AND
TRANSFORMER I0 /10 CONTROLLER
32 to 131°F
0 to +55°C
14 to 158°F
-10 to +70°C
-22 to 158°F
-30 to +70°C
with limitation on the LCD screen that may
show distortion below 32°F / 0°C
Inspection of power contacts
WARNING More than one live circuit! Disconnect all sources of supply before servicing and/or before using the manual operation.
Clip to maintain
cover upright
Slide cover
to access
service
handle hole.
For manual operation
operate handle (4):
up from S2 to S1
down from S1 to S2
FAST OPERATION
Recommendation : carry out one ofoad manual operation with handle
(FAST OPERATION) before putting the switch back in service.
Reverse the procedure to close.
Ensure that all is closed properly before putting back in service.
In case any part of the ATyS FT switch is found to be damaged in any way, replace the
complete switch.
FAST OPERATION
Operational limits
4
5
Manual operation (for maintenance purpuses only)
Instructions for manual, non-electric, offload operations for service
1
2
3
4
After maintenance
operations are done
screw back the covers:
Tightening torque
17.7 lb.in / 2 N.m / PH2
A B C
WARNING Switch will be “not in auto”
whencover is open.
Unscrew handle cover and arc chutes cover
A
Open the cover and click in place and
open the arc chute
B
Use the slow or fast handle to visualize
the state of the contacts
C
For inspection use
a standard tool as
shown to operate
(not included).
0.25 in / 6mm diam max.
SLOW OPERATION
OPERATION ORDER

For 250, 300 & 600 KCMIL (200 , 260 400A) break off all removable
parts (highlighted on the picture).
For 1/0 & (100A ) do not remove any parts.
Terminal shrouds can
be locked in place
using locking points
Print: 90 g/m2 - open format 432 x 279 mm - folded 216 x 279 mm with staples - R/V - B&W
The ATyS FT shall be maintained in accordance with industry standards and as per instructions in the ATyS FT
instruction sheet.
As per NFPA 110 requirements for emergency and standby power systems the ATyS FT should be inspected
and should be exercised under load at least monthly.
Refer to step 5 for instructions for manual, "non-electric", ofoad operations for service.
Terminal shrouds
contain provisions for
voltage sensing
Push back to
click in place.
NO. OF POLES REFERENCE*
100-200A
2P 96982020
3P/2P+N 96983020
4P/3P+N 96984020
260-400A
2P 96982040
3P/2P+N 96983040
4P/3P+N 96984040
* Refs: top and bottom
Top and bottom protection against direct contact with terminals or connecting parts.
Fix the terminal shrouds in place and push back
V
Place the transparent
plastic piece to cover
the auxiliary conacts
and lock in place in
order to protect from
direct contacts.
Use the correct protection according to your
auxiliary contact circuit and your load
Switch has 2 pre-installed auxilliary contacts,
the kit below is for 2 additional contacts with
protection against direct contact.
Ref : 96990021
a
b
PH2 screwdriver
Tightening torque
17.7 lb.in / 2 N.m / PH2
Make sure contact
is correctly activated
AUXILIARY CONTACT ELECTRICAL CHARACTERISTICS
Rated current (125-480 VAC) 22 A
Rated current (125 VDC) 0.5A
Rated current (250 VDC) 0.25 A
Rated horse power up to 250 VAC ½ HP
Rated horse power up to 480 VAC ¼ HP
Recommended wire section for 22A 10 AWG
4 mm²
Terminal tightening torque
7.9 lb.in / 0.9 Nm
11
NO NC
COM
2
2
3
3
Installing power terminal shrouds (optional accessories)
PERIODIC MAINTENANCE
6A
Additional auxiliary contacts
6B
WARNING More than one live circuit.
Disconect all sources of supply before servicing and/or before using the manual operation.
Remove pre-installed auxillarycontact
1
Assemble contacts with parts from
kit as shown below
2
Assemble optional aux contact and
pre-installed aux contact together
3
4
1
2
3
Other manuals for ATyS FT
1
Table of contents