socomec ATyS g M Series User manual

ATySgM
Automatic Transfer Switching Equipment
EN
INSTRUCTION
MANUAL
www.socomec.com

2EN
www.socomec.com
www.socomec.com/en/atys-g-m
To download, brochures, catalogues and technical manuals :
This manual is available for download in French, English, German, Italian, Spanish, Dutch, Portugese, Russian, Polish, Turkish and Chinese.

3
EN
INDEX
1. GENERAL SAFETY INSTRUCTIONS .......................................................6
2. INTRODUCTION.............................................................................7
2.1. THE ATYS FAMILY PRODUCT RANGE .......................................................7
2.2. THE ATYS M RANGE KEY FEATURES .......................................................8
2.2.1. SELECTION GUIDE ...................................................................9
3. QUICK START ..............................................................................10
..............................................................10
..............................................................14
......................................................................17
................................................................17
......................................................17
...........................................................................17
5. OPTIONAL ACCESSORIES ................................................................18
6. TECHNICAL DATA..........................................................................19
..........................................................20
8. PRODUCT INSTALLATION.................................................................21
8.1. CHANGING THE PADLOCKING CONFIGURATION ...........................................21
8.2. RECOMMANDED ORIENTATION ...........................................................21
8.3. DIMENSIONS OF THE SINGLE PHASE PRODUCT ...........................................21
.........................................21
8.5. DIMENSIONS OF THE THREE PHASE PRODUCT ............................................22
.........................................22
8.7. DIN RAIL MOUNTED ......................................................................22
9. INSTALLATION OF OPTIONAL ACCESSORIES ...........................................23
9.1. AUXILLIARY CONTACTS ..................................................................23
.............................................23
......................................................................23
......................................................................24
9.5. TERMINAL SHROUDS.....................................................................24
........................................................................24
.......................................25

EN
10.1. MODULAR PLASTIC ENCLOSURE ........................................................25
.........................................................25
10.2.1. WIRING IN A POLYCARBONATE ENCLOSURE .........................................26
10.2.2. EXTENSION UNIT ..................................................................26
..............................................27
..............................27
.......................27
............................................................28
11.3.1. 230VAC NETWORK CONFIGURATIONS (2P) ...........................................28
11.3.2. 230/400VAC NETWORK CONFIGURATIONS (4P) .......................................28
11.3.3. THREE PHASE WITHOUT NEUTRAL NETWORK........................................29
12. CONNECTION OF CONTROL/COMMAND CIRCUITS...................................31
12.1. TERMINAL CONNECTORS DESIGNATION .................................................32
12.2. AUXILIARY CONTACT OPERATING SCHEDULE ............................................33
13. OPERATION ...............................................................................34
13.1. PRESENTATION OF THE PRODUCT INTERFACE ...........................................34
13.1.1. 2P PRODUCT INTERFACE ...........................................................34
13.1.2. 4P PRODUCT INTERFACE ...........................................................34
13.1.3. RESET.............................................................................35
13.2. MANUAL MODE .........................................................................35
13.2.1. MANUAL SWITCHING ...............................................................35
13.3. PADLOCKING ...........................................................................36
........................................................................37
13.4.1. SINGLE PHASE VERSION............................................................37
13.4.2. THREE PHASE VERSION ............................................................38
13.4.3. SEALABLE CONFIGURATION COVER .................................................39
13.5. AUTOMATIC MODE ......................................................................39
13.5.1. SEALABLE AUTO/MANUAL COVER...................................................39
.....................................................................39
13.7. MANUAL & AUTOMATIC MODE / MAINS RESTORATION CONDITIONS .......................40
13.7.1. MODE 1: AUTOMATIC RETRANSFER .................................................40
13.7.2. MODE 2A: CONTROLLED RETRANSFER ..............................................42
13.7.3. MODE 2B: CONTROLLED TRANSFER.................................................44
13.7.4. MODE 3: NETWORK - NETWORK APPLICATION WITH PRIORITY ........................45
13.7.5. MODE 4: NETWORK - NETWORK APPLICATION WITHOUT PRIORITY ....................47
.........................................................49
............................................................50

5
EN
This page intentionally left blank

6EN
1. GENERAL SAFETY INSTRUCTIONS
This manual provides instructions on safety, connections and operation of the ATy
Whether the ATyS is sold as a loose product, as a spare, as an enclosed solution or as any other
personnel, in line with the manufacturers recommendations, following good engineering practices and after
This instruction manual must be made accessible so as to be easily available to anyone who may need to
read it in relation with the ATy
The ATy
yS should be opened (with or without voltage) as there
Do not handle any control or power cables connected to the ATyS when voltage may be present
on the product directly through the mains or indirectly through external circuits.
DANGER WARNING CAUTION
RISK:
Electric shock, burns, death
RISK:
Possible personal injury
RISK:
Equipment damage

7
EN
2. INTRODUCTION
2.1.
Just the right ATyS for your application…
ATyS: Small Footprint
125A - 3200A
ATyS M: Modular Profile
40A - 160A
40A - 125A
(RTSE)
Transformer
RTSE
ATyS
RTSE
Transformer (building)
Side by Side

8EN
2.2. The ATy
Selecting the right ATy
installation in which the ATy
each product to help you select the right ATy
ATyS dM ATyS tM ATyS gM ATyS pM
160 A
40 A
OPEN TRANSITION MOTORISED CHANGEOVER SWITCH
DUAL POWER SUPPLY
BUILT-IN ATS CONTROLLER
COMMUNICATION*
TRIPPING**
* Specific version. ** Return to zero without external energy source.
>
Network / Genset
>
Genset / Genset
>
Network / Network
Applications with an
External ATS Control
>Network / Genset
>
Network / Network
ATyS dM
GS
UPS
>Network / Network
Building applications
ATyS p M
ATyS t M
UPS
ATyS pM
loads
loads
loads
>
Network / Genset
Genset Applications for
Standby Power
UPS
ATyS gM
loads
loads
loads

9
EN
2.2.1. Selection guide
ATyS dM ATyS tM ATyS gM ATyS pM
APPLICATIONS
Normal /Backup without automatic controller
Normal /Backup with built-in automatic controller
Stable positions
Load changeover
FUNCTIONS
POWER SUPPLY
External
Integrated
OPERATION
Backup manual operation of the 3 positions
Electrical (dry contact) control of positions I, 0
and II
Automatic control of positions I, 0 and II
Return to 0 position feature upon loss of source
MONITORING
3 voltages on networks I and II
Frequency on networks I and II
Phase rotation on networks I and II
Asymmetry of networks I and II
AUTOMATIC CONTROLLER CONFIGURA-
TION
By potentiometer and micro-switch
By screen + keyboard
Vn, Fn, V threshold, F threshold
Driving with or without priority
Adjustable operating timers
Control type (impulse or switch /contactor)
DISPLAY
Position, fully visualised breaking
LED: source status, automatic mode, fault LED
LED: switch positions, supply, tests, control
V, F, timers, number of operations, last event
REMOTE CONTROL
Outputs
Generator start / stop order
Product availability
(not fault and not manual mode)
Source available
Programmable output (source, availability, fault)
Inputs
Test on load
Retransfer
Automatic mode inhibit
Position O order
Priority
Other programmable inputs
(test off-load, position control, etc.)
Remote control
Human / Machine Interface (D10 and D20)
RS485 communication (MODBUS)
* 3 inputs/3 outputs (programmable).
** Product reference is different: communication by RS485 connection (MODBUS) allows up to 31 ATyS M to be connected to a PC or a PLC over 1500 m.

10 EN
3.
3.1. Quick Start ATy
542 955 B - 06/14 - EN
QUICK START
EN
ATyS gM
Automatic
Transfer Switching Equipment
Printing informations: 1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
Sub
j
ect to chan
g
e without notice.
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
■ Packaging and contents are in good condition.
■ The product reference corresponds to the order.
■ Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
■This product must always be installed and commissioned
by qualified and approved personnel.
■Maintenance and servicing operations should be
performed by trained and authorised personnel.
■Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
■ Always use an appropriate voltage detection device to
confirm the absence of voltage.
■ Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
■ In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
■ Bridging bars and 125A or 160A.
■ Control voltage transformer (400Vac -> 230Vac).
■ Voltage sensine and power supply TAP.
■ Terminal shrouds.
■ Additionnal aux contact block.
■ Polycarbonate enclosure.
■ Polycarbonate extension box.
■ Power Connection Terminals.
■ Sealable cover.
STEP 1
Cabinet / Back
Plate Installation
STEP 3
CONTROL /
AUX POWER
terminal
connections
STEP 2
Connecting the
POWER section
STEP 4
CHECK
STEP 5
Programming
Installation and Commissioning STEP 6A
Automatic Operation
STEP 6C
Padlocking
STEP 6B
Emergency Manual
Operation
STEP 3
CONTROL / AUX POWER Terminals and wiring
www.socomec.com
www.socomec.com/en/atys-g-m
To download, brochures, catalogues and technical manuals.
Type Terminal no. Application Status of the
contact Description Output
characteristics
Recommended
connection
cross-section
Inputs I1: 207 / 208 Network/Network With priority
Dry potential free
contact
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
Without priority
Network-Genset. Automatic retransfer
Manual Retransfer
I1: 207 / 209 Network/Network Source priority 1
Dry potential free
contact
Source priority 2
Network-Genset. Stop the test on load
Test on load
I3: 207 / 210 Network-Network or
Network-Generating
set
AUTO mode Dry potential free
contact
Automatic mode inhibition
Outputs O1: 63 / 64 Network-Network or
Network-Generating
set
Product not available :
- Manual mode
- Command default
- Electronic default
- No source
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Product available
O2: 73 / 74 Network-Genset.
No start command genset
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Generating set starting

11
EN
Ensure that the product is in Manual
Mode (front cover open).
Slotted head 3mm 0,5 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 0001
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 0011
2 4 6 8
1 3 5 7
2468
1357
207 208 209 210
63 64 73 74
/
I1 I2 I3
O1 O2
LOAD
STEP 1
The ATyS M is delivered with
padlocking configured to the
O position.
To allow padlocking in all
positions (I - O - II), configure
installation. (Screw is located
at the back of the product).
STEP 3
Posidriv PZ2
2,2 lb-in 0,25Nm
Posidriv PZ2
2
Posidriv PZ2
Posidriv PZ2
Installation Padlocking configuration
Caution: Ensure that the product is installed on a flat rigid surface.
Recommended orientation
Recommended Ok Ok Ok Ok Ok
Posidriv PZ1
1 Nm
Tighten to avoid
2x
2x
DIN RAIL
IEC 60715
MAX : 2
235
26
116
245
143
350
18
13
222
235
131,5
131,5
47
52 176
224
53
46
73,5
45
4 mounting brackets
6x M6 screw - 2,5 Nm
STEP 2
Power Terminal Connections
Source supply side
Hexagonal Metric
Allen size 4
5,0 Nm
It is essential to tighten
!"
"!
#"$$!%&'*;
2
connections.
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
Load side
bridging bar.
125A: 1309 2006
160A: 1309 2016
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
10 to
70 mm²
15mm
Type Terminal no. Status of
Description Output
characteristics
Recommended
connection
cross-section
Auxiliary contact
block
1309 0001
11/12/14 11 14
12 Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
21/22/24 21 24
22 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 01 04
02 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
Auxiliary contact
block
1309 0011
11/12/14 11 14
12
21 24
22
01 04
02
Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
21/22/24 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
Pozidriv PZ2 - 1 Nm
Use 20mm
screws for
1 module
U
s
1
m
r
se
20
m
c
r
e
w
s
mo
du
U
sc
1
Use 35mm
screws for
2 modules
Auxiliary contacts:
Fitting of auxiliary contacts:
1309 0001 or 1309 0011
To fit an AC, the switch must first be put in position 0.An auxiliary contact module comprises: one NO/
NC changeover contact for each position (I-0-II). To install use the long screws supplied with the module.
!X4
Step 1
Step 2
Step 3

12 EN
STEP 5
Programming
Check
STEP 6A
Automatic operation
Close the front cover as shown to put the
product into automatic mode.
STEP 4
Whilst in manual mode, check the
wiring and if ok power up the
product.
STEP 6B
Manual operation
Open the front cover as shown to put
into manual mode.
Use the handle situated in the front
panel under the cover to operate the
transfer switch.
Check the changeover switch position
on the indicator before operating.
To simplify operation
use the handle with the
extension provided. (Max 8 Nm)
90º 90º
Extension
The LED signalling and operation is only active when the product supply is available.
To set the dip switches, it is necessary to open the Auto/Manual cover.
Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the defined thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
Source LED ON LED OFF LED blinking
Source 1 available Source 1 not available
or out of range
- a timer is counting down
- test mode
Source 2 available Source 2 not available
or out of range
- a timer is counting down
Source availability LED
E: No stop in O position
F: 2s stop in O position
Stop in 0 position: E-F
G: Network - Genset
H: Network - Network
Type of application: G-H
Dip switch settings
LED info
Source supply voltage
Auto-Configuration
A
E
Hysteresis settings
B
Loss of priority source timer
FT: 0-60 sec.
FT
RT
U/F [HYST]
[HYST]
RT: 0-30 min.
U/F
Timer settings
C D
Fault reset
LED ON LED OFF LED blinking
Fault Product OK or
*<%
Please wait
Auto mode Manual mode Manual retransfer
Fault and state of the product LED's
STEP 6C
Padlocking mode
In order to padlock put the product in
manual mode.
Pull the locking mechanism and insert
a padlock as shown.
As standard padlocking in the 0 position.
Configurable to I-0-II (see step 1).
1x 4-8 mm
LED state Auto Conf result Action
Steady ON OK Ready
Blinking Not OK Go back to step 4
Ensure that the supply
voltage is available and
within the following limits:
Un: 176-288VAC
Fn: 45-65Hz
==?@JY%
HYST: 20 %6U/F
6U: 5-20%
6F: 3-10%

13
EN
This page intentionally left blank

EN
542 932 B - 06/14 - EN
QUICK START
EN
ATyS gM
Automatic
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
■ Packaging and contents are in good condition.
■ The product reference corresponds to the order.
■ Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension ROD
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
■This product must always be installed and commissioned
by qualified and approved personnel.
■Maintenance and servicing operations should be
performed by trained and authorised personnel.
■Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
■ Always use an appropriate voltage detection device to
confirm the absence of voltage.
■ Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
■ In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
■ Bridging bars and 125A or 160A.
■ Control voltage transformer (400Vac -> 230Vac).
■ Voltage sensine and power supply TAP.
■ Terminal shrouds.
■ Additionnal aux contact block.
■ Polycarbonate enclosure.
■ Polycarbonate extension box.
■ Power Connection Terminals.
■ Sealable cover.
Printing informations: 1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
Sub
j
ect to chan
g
e without notice.
STEP 1
Cabinet / Back
Plate Installation
STEP 3
CONTROL /
AUX POWER
terminal
connections
STEP 2
Connecting the
POWER section
STEP 4
CHECK
STEP 5
Programming
Installation and Commissioning STEP 6A
Automatic Operation
STEP 6C
Padlocking
STEP 6B
Emergency Manual
Operation
STEP 3
CONTROL / AUX POWER Terminals and wiring
Type Terminal no. Application Status of the
contact Description Output
characteristics
Recommended
connection
cross-section
Inputs I1: 207 / 208 Network/Network With priority
Dry potential free
contact
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
Without priority
Network-Genset. Automatic retransfer
Manual Retransfer
I1: 207 / 209 Network/Network Source priority 1
Dry potential free
contact
Source priority 2
Network-Genset. Stop the test on load
Test on load
I3: 207 / 210 Network-Network or
Network-Generating
set
AUTO mode
Dry potential free
contact
Automatic mode inhibition
Outputs O1: 63 / 64 Network-Network or
Network-Generating
set
Product not available :
- Manual mode
- Command default
- Electronic default
- No source
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Product available
O2: 73 / 74 Network-Genset.
No start command genset
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W or 125VA
Umax : 30Vdc or
230Vac
Generating set starting
www.socomec.com
www.socomec.com/en/atys-g-m
To download, brochures, catalogues and technical manuals.
3.2. Quick Start ATy

15
EN
Type Terminal no. Status of
Description Output
characteristics
Recommended
connection
cross-section
Auxiliary contact
block
1309 0001
11/12/14 11 14
12 Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
21/22/24 21 24
22 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 01 04
02 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
Auxiliary contact
block
1309 0011
11/12/14 11 14
12
21 24
22
01 04
02
Changeover switch in position I 250V AC 5A AC1
30 Vdc 5 A
21/22/24 Changeover switch in position II 250V AC 5A AC1
30 Vdc 5 A
01/02/04 Changeover switch in position 0 250V AC 5A AC1
30 Vdc 5 A
207 208 209 210
63 64 73 74
2 4 6 8
1 3 5 7
2 4 6 8
1 3 5 7
2468
1357
2468
1357
/
I1 I2 I3
O1 O2
LOAD
Ensure that the product is in
Manual Mode (front cover
open).
230/127V~
3ph 4wires
230/127V~
3ph 3wires
Slotted head 3mm 0,5 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 0001
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 0011
Pozidriv PZ2 - 1 Nm
Use 20mm
screws for
1 module
U
s
1
m
r
se
20
m
c
r
e
w
s
mo
du
U
sc
1
Use 35mm
screws for
2 modules
Auxiliary contacts:
Fitting of auxiliary contacts:
1309 0001 or 1309 0011
To fit an AC, the switch must first be put in position 0.An auxiliary contact module comprises: one NO/
NC changeover contact for each position (I-0-II). To install use the long screws supplied with the module.
STEP 1
The ATyS M is delivered with
padlocking configured to the
O position.
To allow padlocking in all
positions (I - O - II), configure
installation. (Screw is located
at the back of the product).
STEP 3
Posidriv PZ2
2,2 lb-in 0,25 Nm
Posidriv PZ2
2
Posidriv PZ2
Posidriv PZ2
Installation Padlocking configuration
Caution: Ensure that the product is installed on a flat rigid surface.
53
46
73,5
45
340
326
131,5
131,5
52 104 176
47
Recommended orientation
Recommended Ok Ok Ok Ok Ok
Posidriv PZ1
1 Nm
Tighten to avoid
DIN RAIL
IEC 60715
6 mounting brackets
6x M6 screw - 2,5 Nm
2x
2x
STEP 2
Power Terminal Connections
Source supply side
Hexagonal Metric
Allen size 4
5,0 Nm
It is essential to tighten
!"
"!
WG
m2
m2*
WG
!
X8
#"$$!%&'*;
2
connections.
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
Load side
bridging bar.
125A: 1309 4006
160A: 1309 4016
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
10 to
70 mm²
15mm
MAX : 2
340
26
116
245
143
350
18
13
324
Step 1
Step 2
Step 3

16 EN
FT
STEP 5
Programming
Check
STEP 6A
Automatic operation
Close the front cover as shown to put the
product into automatic mode.
STEP 4
Whilst in manual mode, check the
wiring and if ok power up the
product.
STEP 6C
Padlocking mode
In order to padlock put the product in
manual mode.
Pull the locking mechanism and insert
a padlock as shown.
As standard padlocking in the 0 position.
Configurable to I-0-II (see step 1).
STEP 6B
Manual operation
Open the front cover as shown to put
into manual mode.
Use the handle situated in the front
panel under the cover to operate the
transfer switch.
Check the changeover switch position
on the indicator before operating.
To simplify operation
use the handle with the
extension provided. (Max 8 Nm)
90º 90º
Extension
1x 4-8 mm
The LED signalling and operation is only active when the product supply is available.
To set the dip switches, it is necessary to open the Auto/Manual cover.
Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the defined thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
Source LED ON LED OFF LED blinking
Source 1
available
Source 1
missing or
out of
range
- a timer is
counting
down
- test mode
Source 2
available
Source 2
missing or
out of
range
- a timer is
counting
down
Source availability LED
E: No stop in O position
F: 2s stop in O position
Stop in 0 position: E-F
C: 50 Hz
D: 60 Hz
Frequency: C-D
A: 3P
B: 1P
Type of network: A-B
G: Network - Genset
H: Network - Network
Type of application: G-H
HYST: 20 %6U/F
6U: 5-20%
6F: 3-10%
Dip switch settings Led info
A
Source voltage
supply configuration
B
Loss of priority source timer
127/230 Vac version 230/400 Vac version
Un (P-P):
208-240 Vac
Un (P-N):
120-138 Vac
Un (P-P):
380-420 Vac
Un (P-N):
220-240 Vac
FT: 0-30 sec.
U/F [HYST]
[HYST]
RT: 0-30 min.
U/F
Timer settings
C D
Fault reset
LED ON LED OFF LED blinking
Fault Product OK Wait
Auto mode Manual
mode
Manual
retransfer
Fault and state of the product Leds
RT

17
EN
4.
4.1.
2
4
3
5
1
2
4
3
5
1
CAUTION
Ensure that the load is connected
to the top of the switch with the
motorisation on the right hand side
as shown.
4.2.
A fully integrated and interlocked transfer switch, with high electrical performance offering microprocessor
4.3. Supply types

18 EN
5.
contacts
Ref. : 1309 0001
Ref. : 1309 0011
To provide a common point on the outgoing side of the
Single phase product:
Three phase product:
Terminal
shrouds
Ref
Enclosure
enclosure provides easy access to a compact, enclosed
Ref. : 1309 9007
Single phase
residential
enclosure
Three phases product:
Single phase product:
connection
terminals
The power connection terminals allow conversion of the
Ref. :
For complete conversion,
order 3 times the
reference.
transformer
Ref. :

19
EN
6. TECHNICAL DATA
Ratings 40A 63 A 80 A 100 A 125 A 160 A
Frequencies
circuit)
Rated impulse withstand voltage U
imp
(kV) (power circuit)
Rated insulation voltage U
i
(V) (control circuit)
Rated impulse withstand voltage U
imp
(kV) (control circuit)
Rated operational
currents (A)
Rated operational
circuit withstand if using
circuit withstand (kA eff)
(kA eff)
sensing time and
state (VA)
characteristics
Number of changeovers
(not compatible with
aluminium cables)
AAAAAA
This is a class A product. In a domestic environment, this product may cause radio interference in
which case the user may be required to take adequate measures.

20 EN
7.
Temperature
Altitude
UE
Storage
ø 1 mm
This manual suits for next models
2
Table of contents