20
8.3.3 Procedures for electric cabling
The electrical cabling of Solar Frontier SolarSets has to be done as described in Chapter 7, Table 2. Take care that the exact number of
modules in series are connected in accordance with Table 2, and that the respective number of parallel strings is adhered to.
String connection
The serial connection of modules should be done in accordance with 8.3.5, Figure 31 and 32.
Procedure by interrupted strings:
If it isn’t possible to connect modules directly, the plugs, sockets and DC-cable provided can be used to bridge gaps.
An exemplary approach is shown in 8.3.5, Figure 33 and 34. The basics on assembling an extension cable can be found in Chapter 8.3.2
Assembly. Please note that only a limited number of plugs/sockets are provided in the set, and that the cable provided is primarily for
the extension from the generator to the inverter.
If you should need extra material, please ensure that the compatibility to the SolarSet products is conrmed. If in doubt
please contact Solar Frontier.
Connecting the strings
The string connecting cable in the set is used to connect the strings and lead them to a mutual collection point. The number of strings
can be determined in Chapter 7, Table 2.
DC-cable
The DC-cable is used to extend the connecting cables in the PV generator with the inverter. Basics on assembling the cable can be
found in chapter 8.3.2
Connecting to the inverter
The connection of the PV generator to the inverter is described in detail in chapter 8.4. Please ensure that the instructions and proce-
dures described there are strictly adhered to to avoid possible danger sources and to ensure a safe installation.
8.3.4 Grounding
Grounding cautions
•Be aware of the necessary grounding requirements prior to installation. Your local authorities can help you further.
•Install arrestors, surge absorbers or any other appropriate lightning protection tools as needed.
•Module frames, mountings, connection boxes and metal conduits should be connected to an earth ground as lightning protection,
in accordance with local, regional and national standards and regulations.
•Grounding holes (ф 4 mm) on the aluminum frame of the SF modules are provided to accommodate grounding. Use a grounding
wire made of copper, not smaller than 2 mm² (14AWG). Temperature rating of the conductors must be between -40 °C to 85 °C. En-
sure that the crimping terminal is tightly tied to the module frame with a rolling thread screw and a lock washer to ensure electrical
contact.
•Grounding devices such as module clamps with an integrated grounding pin, serrated washers, grounding clips or lugs, designed
for bonding photovoltaic modules to the mounting structures may also be used for grounding as described in NEC section 250.
These grounding devices shall be made in conformance with the grounding device manufacturer instructions. Consult the ground-
ing device manufacturer to identify the appropriate grounding and bonding device for your mounting structure or design.
For alternative grounding methods please consult Solar Frontier.
UL: The module with exposed conductive parts is considered to be in compliance with UL 1703 only when it is electrically grounded
in accordance with the instruction presented below and the requirements of the NEC.