manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. SOMMY
  6. •
  7. Temperature Controllers
  8. •
  9. SOMMY TFY-A User manual

SOMMY TFY-A User manual

Environment
Storage
enenvironment
Indoor use only, temperature: 0~50℃no condensation,
humidity<85%RH, altitude<2000m
-10 ~60℃, no condensation
1. Electrical parameters:
IV. Specifications
Sample rate 2 times per second
Relay capacity AC 250V /3A Life of rated load>100,000 times
SSR output DC 24V pulse voltage, load<30mA
Communication port
Current output
Insulation impedance
ESD
Pulse traip
anti-interference
DC 4 ~20mA load<500Ω, temperature drift 250PPM
RS485 port Modbus-RTU protocol, max input 30 units
Input, output, power VS meter cover >20MΩ
IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
IEC/EN61000-4-4 ±2KV perf.Criteria B
Power supply
Power consumption
AC/DC 100 ~240V(85-265V)
< 10VA
Intelligent Temperature Controller
User Manual
Applicable TFY-A version
1
⊙Optional input signal types and models
⊙With functions of measurement display, control output, alarm output, analog
output, RS485 communication, etc.
⊙Multi PID control algorithms for option, and with auto-tune function.
⊙This product is used in industrial machinery, machine tools, general measuring
instruments and equipment.
Features
The instruction explain instrument settings, connections,name and etc, please read
carefully before you use the temperature controller. Please keep it properly for necessary
reference.
TFY4□-□R C 1 8 □-A
II. Ordering information
1
2
3
A: Version
10: Single input without RS485
18: Single input with RS485
Blank: TC/RTD/mV/Rt input X: mA/V input
4
5
B: 1 alarm output C: 2 alarm output
R: Relay output S: SSR output
D: DC 4~20mA output (can be changed to analog
output by ACT menu) K: SCR output (can be
ordered) M: SSR or relay (switched by ACT)
6Blank: No this function. I: DC 4~20mA analog
output (can be switched to control output by
ACT menu, available for TE6 & TE9)
7
8
9
4: 48H*48W*73L 6: 96H*48W*73L 7: 72H*72W*73L
8: 48H*96 W*73L 9: 96H*96W*73L
TFY series temperature controller
Blank: AC/DC 100~240V F: AC/DC 24V
2
Analog
output Comm. Auxiliary
power
RELAYSSR 4~20mA AL1
OUT2AL2 4~20mA RS485 24V
TFY4-DC18□● ● ● ◎● ●
TFY4-DC10□● ● ● ◎
◎
●
TFY4-RC18□● ● ● ●
●
TFY4-SC18□● ● ●
TFY4-MC10□●● ● ●
TFY7-DC18□●● ● ●
◎●
●
TFY7-DC10□● ● ●
TFY7-MC18□●
●● ● ●●
TFY7-MC10□●● ●
TFY6/8/9-IMC18□●● ● ● ● ◎●
● ● ◎●
●◎●
●
●
TFY6/8/9-IMC10□● ● ●
TFY6/8/9-DC18□● ●
●
●
●◎●●
TFY6/8/9-DC10□●
TFY6/8/9-MC18□● ● ● ● ●
TFY6/8/9-MC10□● ● ● ●
OUT1 control output
Alarm output
ModelNo.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
●
III. Models
□:Blank: input signal is TC/RTD/Mv/Rt; “X” : input signal is 4 ~20mA/0 ~10V
●:Standard configuration function
◎:The meter has this function, but it is combined with another function. This series only have
one loop 4~20mA output, but the user can modify menu ACT to use it as main control output or
analog output.
I. Safe Caution
Warning
Caution
1)When the failure or abnormal of products lead to a system of major accidents, please set
the proper protection circuit in the external.
2)Please don`t plug in before completing all the wire.Otherwise it may lead to electric shock,
fire, fault.
3)Not allow to use outside the scope of product specification,otherwise it may lead to
fire,fault.
4)Not allow to use in the place where is inflammable and explosive gas.
5)Do not touch power terminal and other high voltage part when the power on, otherwise
you may get an electric-shock.
6)Do not remove,repair and modify this product,otherwise it may lead to electric shock, fire,
fault.
1)The product should not be used in a nuclear facility and human life associated medical
equipment.
2)The product may occur radio interference when it used at home.You should take
adequate countermeasures.
3)The product get an electric shock protection through reinforced Insulation. When the
product is embedded in the devices and wiring,please subject to the specification of
embedded devices.
4)In order to prevent surge occurs,when using this product in the place of over 30m indoor
wiring and wiring in outdoor, you need to set the proper surge suppression circuitry.
5)The product is produced based on mounting on the disk.In order to avoid to touch the
wire connectors,please take the necessary measures on the product.
6)Be sure to observe the precautions in this manual, otherwise there is a risk of a major
injury or accident.
7)When wiring, please observe the local regulation.
8)To prevent to damage the machine and prevent to machine failure, the product is
connected with power lines or large capacity input and output lines and other methods
please install proper capacity fuse or other methods of protection circuit.
9)Please don't put metal and wire clastic mixed with this product,otherwise it may lead to
electric shock, fire, fault.
10)Please tighten screw torque according to the rules.If not,it may lead to electric shock and
fire.
11)In order not to interfere with this products to dissipate heat, please don't plug casing
around the cooling vent hole and equipment.
12)Please don’ t connect any unused terminal.
13)Please do the cleaning after power off, and use the dry cleaning cloth to wipe away the
dirt. Please don’ t use desiccant, otherwise, it may casue the deformation or discoloration
of the product.
14)Please don`t knock or rub the panel with rigid thing.
15)The readers of this manual should have basic knowledge of electrical,control, computer
and communications.
16)The illustration, example of data and screen in this manual is convenient to
understand,instead of guaranteeing the result of the operation.
17)In order to use this product with safety for long-term,regular maintenance is necessary.
The life of some parts of the equipments are by some restrictions, but the performance of
some will change for using many years.
18)Without prior notice, the contents of this manual will be change. We hope these is no
any loopholes, if you have questions or objections, please contact us.
Caution of Install & Connection
1. Installation
1) This product is used in the following environmental standards. (IEC61010-1)[Overvoltage
categoryⅡ、class of pollution 2]
2)This product is used in the following scope:environment, temperature, humidity and
environmental conditions.Temperature:0~50℃;humidity: 45~85%RH; Environment
condition:Indoor warranty.The altitude is less than 2000m.
3) Please avoid using in the following places:
The place will be dew for changing temperature;with corrosive gases and flammable gas;with
vibration and impact;with water, oil, chemicals, smoke and steam facilities with Dust, salt,
metal powder;and with clutter interference, static electric and magnetic fields, noise;where
has air conditioning or heating of air blowing directly to the site; where will be illuminated
directly by sunlight; where accumulation of heat will happen caused by radiation.
4) On the occasion of the installation, please consider the following before installation.
In order to protect heat saturated, please ensure adequate ventilation space.
Please consider connections and environment,and ensure that the products below for more
than 50mm space. Please avoid to installed over the machine of the calorific value (Such as
heaters, transformer, semiconductor operations, the bulk resistance). When the surrounding
is more than 50 , please using the force fan or cooling fans.But don't let cold air blowing
directly to the product. In order to improve the anti - interference performance and security,
please try to stay away from high pressure machines, power machines to install.
Don`t install on the same plate with high pressure machine and the product.
The distance should be more than 200mm between the product and power line.
2. Cable caution:
1)Please use specified compensation wire in the place of TC input; Please use insulated TC
if the measured device is heated metal.
2)Please use the cable of lesser resistance in the place of RTD input,and the cable(3 wire)
must be no resistance difference,but the total length is within 5m.
3)In order to avoid the effect of noise,please put the input dignal away from meter
cable,power cable,load cable to wiring.
4)In order to reduce the power cables and the load power cables on the effect of this
product,please use noise filter in the place where easy to effect.
You must install it on the grounding of the disk if you use the noise filter,and make the wiring
to be shortest between noise filter output side and power connectors. Don`t install fuse and
switch on the wiring of noice filter output side,otherwise it will reduce the effect of noise filter.
5)It takes 5s from input power to output.If there is a place with interlocking actions circuit
signal,please use timer relay.
6)Please use twisted pair with a shield for analog output line, can also connect the
common-mode coil to the front-end of the signal receiving device to suppress line
interference if necessary, to ensure the reliabilty of signal.
7)Please use twisted pair with a shield for remote RS485 communication cable, and deal with
the shield on the host side earth, to ensure the reliabilty of signal.
8)This product don’ t have the fuse; please set according to rated voltage 250V,rated current
1A if you need; fuse type:relay fuse.
9)Please use suitable slotted screwdriver and wire.
Terminal distance: 5.0mm. Screwdriver size: 0.6X3.5, length of slotted screwdriver >130mm.
Recommended tightening torque: 0.5N.m.
Proper cables: 0.25 ~ 1.65mm single cable/multiple core cable
10)Please don`t put the Crimp terminal or bare wire part contact with adjacent
connector.
National High-tech Enterprise/ National Standard Drafting Unit
Version code: KKTFY-A01E-A/1-20220421
Hotline: 400-8866-986
中山市中大电力自动化有限公司
SOMMY Automation Group Shares co.,Ltd
ISO9001
国家高新技 术企业
3
VII. Panel Illustration
4
PV
SV
AATT RR//SS
1
2
3
6
5
7
4
PV
SV
AATT RR//SS
1
2
3
6
5
7
4
VI. Connections
SSR
AC/DC 100~240V
POWER
AL1/OUT2
RS485
AL2
OUT1
OUT1
TC
RTD
+ +-
mA
V
1
NO COM NC
2 3 4 765
13 14 15 16 191817
8
COM
910 1211
B- A+ - +
NC
+24V DC 4~20mA
- +
COM NO
SSR
AC/DC 100~240V
POWER
AL1/OUT2
RS485
AL2
OUT1
OUT1
TC
RTD
+ +-
mA
V
1
NO COM NC
2 3 4 765
13 14 15 16 191817
8
COM
910 1211
B- A+ - +
NC
+24V DC 4~20mA
- +
COM NO
TFY4 TFY7
TFY6/8 TFY9
型号中带“M”,SSR输出端口
Note:
13
SSR
OUT 1
14
+
-
5
NO
A+
B-
DC 4~20mA AC/DC 100~240V
POWER
24V- ++
+ -
COM
RELAY
NC
4
13
14
3 2 1
10
TC
RTD
- +B +B
mA
V
9
8 7 6
AL1/OUT2
RS485 AL2
11
12
SSR
OUT1
型号中带“M”,SSR输出端口
Note:
13
SSR
OUT 1
14
+
-
5
NO
A+
B-
DC 4~20mA AC/DC 100~240V
POWER
24V- ++
+ -
COM
RELAY
NC
4
13
14
3 2 1
TC
RTD
- +B +B
mA
V
7 6
AL1/OUT2
RS485 AL2
11
12
SSR
OUT1
POWER
AC/DC
100 240~V
COMNO
OUT1
AL1/OUT2
V
mA
RTD
B+
A-
NO NC +-
OUT1
SSR
B- A+
RS485
-+
DC 4 20~m A
24V
AL2
NC
TC
B+
123456789 10
11 12 13 1 4 1 5 1 6 17 1 8 1 9 2 0
COM
POWER
AC/DC
100 240~V
COMNO
OUT1
AL1/OUT2
V
mA
RTD
B+
A-
NO NC +-
OUT1
SSR
B- A+
RS485
+DC 4 2~m A
24V
AL2
NC
TC
B+
123456789 10
11 12 13 1 4 1 5 1 6 17 1 8 1 9 2 0
COM
POWER
AC/DC
100 240~V
COMNOC
OUT1
AL1/O TU 2
V
mA
RTD
B+
A-
+-
OUT1
SSR
B- A+
RS485
-+
DC 4 20~m A
24V
N
TC
B+
POWER
AC/DC
100 240~V
OUT1
AL1/O TU 2
V
mA
RTD
B+
A-
+-
OUT1
SSR
B- A+
RS485
-++ DC 4 2~m A
24V
TC
B+
NO NC
AL2
COMNO NC
AL2
COM
2. Measured signal specifications:
V. Dimension and installation size
Panel size   Side size    Hole size
B
C
E
D
G
K
J+0.5
-0
+0.5
-0 H
A
F
B
J+0.5
-0
+0.5
-0
F
Input type
K1
K2
J1
J2
E1
E2
T1
T2
B
R
S
N1
N2
PT100-1
PT100-2
JPT100-1
JPT100-2
CU50-1
CU50-2
CU100-1
CU100-2
0~50mV
0~400Ω
*
4~20mA
*
0~10V
-50 ~1200
-50.0 ~999.9
0~1200
0.0 ~999.9
0~850
0.0 ~850.0
-50 ~400
-50.0 ~400.0
250 ~1800
-10 ~1700
-10 ~1600
-50 ~1200
-50.0 ~999.9
-200.0 ~600.0
-200 ~600
-200.0 ~500.0
-200 ~500
-50.0 ~150.0
-50 ~150
-50.0 ~150.0
-50
~
150
-1999
~
9999
-1999
~
9999
-1999
~
9999
-1999
~
9999
1℃
0.2℃
1℃
0.2℃
1℃
0.3℃
1℃
0.4℃
1℃
1℃
1℃
1℃
0.2℃
0.2℃
1℃
0.2℃
1℃
0.2℃
1℃
0.2℃
1℃
12bit
12bit
12bit
12bit
0.5%F.S±3digits
0.5%F.S±1℃
0.5%F.S±3digits
0.5%F.S±1℃
0.5%F.S±3digits
0.5%F.S±1℃
0.8%F.S±3℃
0.8%F.S±3℃
1%F.S±2℃
1%F.S±2℃
1%F.S±2℃
0.8%F.S±1℃
0.8%F.S±1℃
0.5%F.S±0.3℃
0.5%F.S±3digits
0.5%F.S±0.3℃
0.5%F.S±3digits
0.5%F.S±3℃
0.5%F.S±3℃
0.5%F.S±1℃
0.5%F.S±3digits
0.5%F.S±3digits
0.5%F.S±3digits
0.5%F.S±3digits
0.5%F.S±3digits
>500KΩ
>500kΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
0.2mA
0.2mA
0.2mA
0.2mA
0.2mA
0.2mA
0.2mA
0.2mA
>500kΩ
0.2mA
<50Ω
>1MΩ
Measure rangeSymbol
Resolution
Accuracy
Input impedance
/auxiliary current
Comm.
parm. code
0
16
1
17
2
18
3
19
4
5
6
7
20
8
21
9
22
10
23
11
24
12
13
14
15
*:Please indicate the requirement when choose the model.
3. Isolation diagram:
(Ⅰ)
控制输出
电源
MCU(AD)
measure input
4-20mA
output
RS485
comm. output
Auxiliary
power
SSR
output
“ // ”:Isolation. ” ̄ ̄” : No isolation
Note: when the auxiliary power is used as power supply for external sensor, if the sensor is non-
isolated, then there is no isolation between input and 4-20mA output, nor between input and
RS485 comm.. If 4-20mA output coexists with RS485 comm., there is no isolation between them.
Relay
control
output
Power supply
(Ⅰ)
控制输出
Relay
alarm
output
Surge immunity IEC/EN61000-4-5 ±2KV perf.Criteria B
Voltage drop & short
interruption immunity IEC/EN61000-4-29 0% ~70% perf.Criteria B
Isolation voltage Signal input, output, power: 1500VAC 1min,
<60V low voltage circuit: DC500V,1min
Total weight About 400g
Cover material
Panel material
Power failure memory
Safety Standard
The shell and panel frame PC/ABS (Flame Class UL94V-0)
PC
10 years, times of writing: 1 million times
IEC61010-1 Overvoltage category Ⅱ,pollution level 2,
levelⅡ(Enhanced insulation)
1. Operation process & method
VIII. Operation process and menu illustration
1). Modify SV Value
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PV
SSVV
AATT RR//SS
PPVV
SSVV
A
ATT RR//SS
PPVV
SSV
PPVV
SSV
AATT RR//SSA
ATT RR//SS AATT RR//SSA
ATT RR//SS
AATT RR//SSA
ATT RR//SS
Press “ ”
Increase SV value
Press “ ”
SV value flash
Press “ ”
Reduce SV value
Press “SET”
Save SV value
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
AATT RR//SS
PPVV
SSVV
A
ATT RR//SS
AATT RR//SSA
ATT RR//SS AATT RR//SSA
ATT RR//SS
AATT RR//SSA
ATT RR//SS
PPVV
SSVV
AATT RR//SS
PPVV
SSVV
A
ATT RR//SS
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
AATT RR//SSA
ATT RR//SS
Press “ ”,
parameter
value flash
Press “ ” or
“ ”, move
among menus
2)、Common Menu
Press“ ”or“ ”,
modify
parameter value
Press “SET”
> 3 sec, exit
Common Menu
Press “SET”,
save modified
value
Press “SET”
> 3 sec, enter
Common Menu
PPVV
SSVV
PPVV
SSVV
AATT RR//SSA
ATT RR//SS
PPVV
SSVV
AATT RR//SS
PPVV
SSVV
A
ATT RR//SS
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
PPVV
SSVV
AATT RR//SS
PPVV
SSVV
A
ATT RR//SS
AATT RR//SSA
ATT RR//SS AATT RR//SSA
ATT RR//SS
PPVV
SSVV
AATT RR//SS
PPVV
SSVV
A
ATT RR//SS AATT RR//SSA
ATT RR//SS
Press “ ”,
parameter
value flash
Press “SET”
to find LCK
menu
Press “SET”
to enter Adv-
anced Menu
SET LCK=33
3)、Advanced menu
Press “SET”
>3 sec,enter
Common Menu
Press“ ”or
“ ”, modify
parameter value
Press “SET”,
save modified
value
Display (red)
Set value / parameter display window, the control
is stopped when it displays “STOP”
Measured value/ parameter code display window
1
2
AL1
AL2
Alarm 2# (Orange)
3
AT (Orange)
COM (Orange)
SET key
OUT1
OUT2
AT
COM
SET
5
4
7
6
OUT2 (Orange)
The communication indicator will keep flashing when
communication is in progress
Display (green)
℉/℃ (Orange)
℉/℃Temperature Unit Selection
SV
PV
No. Symbol Name Function
OUT1 (Orange)
Alarm 1# (Orange)
Add key, in measure and control mode, long press it to
shift RUN/STOP mode, or check the menu in reverse order.
Reduce key, check the menu in sequence
Menu key/confirm key, to enter or exit the modification
mode, or to confirm and save the modified parameter.
Activate key/ shift key/ AT auto tune key (in measure
and control mode, long press to enter/exit auto tune)
Auto tune indicator, lights on when it is under auto tune status.
2nd alarm output indicator, lights on when alarm output,
lights off when no alarm output.
1st alarm output indicator, lights on when alarm output,
lights off when no alarm output.
Cooling output indicator, lights on when output ON.
Main control output indicator, lights on when output ON.
UP key/ R/S
DOWN key
SHIFT/AT key
Connection diagram symbols and function description
Type
Input
Input
TC
RTD
Thermocouple
Thermocouple input connection, distinguish
positive and negative. Support K, J, E, T, N, R,
S, B type, switched by INP menu.
Thermal
resistance
Input mA Analog signal
Input V
Communication
Alarm 1 /
control output 2
AL2
RS485 A+Send
B-Receive
AL1/
OUT2
NO
+ Positive
- Negative
COM common port
NO
NC
Relay output OUT1
RELAY
SSR output
4-20mA
Output
4-20mA
OUT1
SSR
4-20mA input (this function can be customized)
0-10V/0-5V input (this function can be customized)
RS485 communication port, COM is connected
to shield wire, A+ send , B - receive
COM
common port
Alarm 2, need to adjust AL2,AD2,HY2
parameters.
OUT1 is the analog output or current control
output terminal, which is set by OT and ACT menu.
Auxiliary power
supply DC 24V Output power for sensor.
Illustration Function
Thermal resistance input, normally 3 wires, +B
and +B are the same color wire or short circuit
wire, -A and B connect to thermal resistance.
For 2 wires RTD, B and B need to be short
circuited. Support PT100,CU100,CU50 etc,
switched by INP menu.
When it is used as Alarm 1, please adjust the
parameters AL1, AD1 and HY1.
When it is used as OUT 2 cooling output,
please set OT as PID heating-cooling control,
AL1 does not work when it is user as OUT2,
and related menus for AL1 are hidden.
OUT1 is the relay control output terminal, which
is set by OT and ACT menu. COM common
port, NO, NC.
Symbol
Analog signal
+ Positive
- Negative
+ Positive
- Negative
COM common port
NO
NC
Alarm 2
OUT1 is the SSR control output terminal, which
is set by OT and ACT menu.
4:(48*48)
6:(48*96)
7:(72*72)
8:(96*48)
9:(96*96)
48
48
72
96
96
A型号 H(Min)
BC D E F G
J
48
96
72
48
96
73
73
73
73
73
6.5
6.5
6.5
6.5
6.5
66.5
66.5
66.5
66.5
66.5
45
91.5
67.5
45
91.5
25
25
25
25
25
45
45
67.5
91.5
91.5
44
90
66
44
90
K
(Min)
25
25
25
25
25
Symbol description: “☆” means HY, “▲” means alarm value, “ ” means SV value
7
8
9
10
11
12
SV
SV
SV
SV
SV
SVSV-AL1
SV-AL1
SV-AL1
SV+AL2
SV+AL2
SV+AL2
AL2
AL2
AL2
AL1
AL1
AL1
1
2
4
5
6
SV+AL
SV+AL
SV-AL
SV-AL SV
SV SV+ALSV-AL
AL
SV
SV
SV
SV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
AL
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
▲
▲ ▲
▲
▲▲
▲
▲
△
△
△
☆
▲
△
△
△
△
▲▲
△
▲▲
△
▲▲
△
▲
▲
▲
▲
△
△
▲
SV
SV
SV
SV
SV
SVSV-AL1
SV-AL1
SV-AL1
SV+AL2
SV+AL2
SV+AL2
AL2
AL2
AL2
AL1
AL1
AL1
2
3
SV+AL
SV+AL
SV-AL
SV-AL SV
SV SV+ALSV-AL
AL
SV
SV
SV
SV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
AL
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
▲
▲ ▲
▲
▲▲
▲
▲
△
△
△
△
☆
▲
△
△
△
△
▲▲
△
▲▲
△
▲▲
△
▲
▲
▲
▲
△
△
▲
(1) Alarm parameters and output logic diagram:
Alarm
code
Alarm mode Alarm output(AL1 & AL2 are independent from each)
Image:the hatched section means the alarm action
High limit absolute value
alarm
Low limit absolute value
alarm
※High limit deviation
value alarm
※Low limit deviation value
alarm
※High/low limit deviation
value alarm
※High/low limit interval
value alarm
Alarm
code
Alarm mode The below two alarm parameters(AL1,AL2) are used in
combination, AL1 alarm output, AD2 must be set as 0
High and low limit absolute
value interval alarm
※High and low limit deviation
value interval alarm
※High limit absolute value
and low limit deviation value
interval alarm
※High limit deviation value
and low limit absolute value
interval alarm
High/low limit absolute value
alarm
High/low limit deviation value
alarm
※ For deviation alarm, if alarm value is set as a negative number, it will be used as an absolute
value.
No.
NameSymbol
Illustration Setting range Factory
setting
1
2
4
AL1
HY1
AD1
(1)
AL2
HY2
AD2
(1)
FL ~FH
0~1000
0~12
FL ~FH
0~1000
0~6
-1999 ~9999
10
1
3
5
1
4
0
6
5
OT 0~5
INP K1
1
0~9999 120
1~200 20
4~200 20
PC 10.0
OVS 0 ~9999 5
DB -1000~1000 5
LCK 0~9999 0
0~9999 30
8
9
0~9999
30
A-M AUTO~AM AUTO
10
3AD1
(1)
PS
0~12 3
7
I
CP
CP1
0.1 ~100.0
OVS
LCK
P
12
13
14
15
16
17
18
19
11
D
1st alarm hystersis
2nd alarm value,
2nd alarm hystersis
2nd alarm mode
OUT1 control cycle, 1: SSR control output,
4-200: relay control output. Unit: s
OUT2 relay output cycle. Unit: s
OUT2 cooling proportionality coefficient, the higher of
value,the stronger of cooling
ON/OFF control hystersis(positive and negative
numbers work the same); when OT=3, it is the dead
zone for cooling control(positive and negative
numbers work differently);after change the INP
setting, please change this parameter according to
the decimal point position.
Lock function. 0001:SV value can’ t be modified.
0010: menu set value can be checked only, can’ t
be modified. 0033: enter to advanced menu.
0123: menus reset to factory setting.
Overshoot limit, during PID control process, when
PV(measured value) > SV(set value) + OVS
(overshoot limit), force to close output. The smaller
this value is, the smaller the PID adjustment range
is, the worse the control stability is. Please set the
appropriate value according to the actual situation.
Differential time, the greater the value is, the stronger
the differential actiontion is, otherwise, it is weeker.
When D=0, no differential action. Set D=0 when
controlling fast systems, e.g., pressure, speed; unit: s
Integral time, the smaller the value is, the stronger the
integral action is, otherwise, it is weeker. When I=0,
no integral action, unit: s.
Proportional band, the smaller the value is, the faster
the system responds, otherwise, it is slower. When
P=0, no PID control, unit same as PV
Amend value, display value= actual measured value
+ amend value
Control mode, 0:ON/OFF heating control, relevant
parameter: DB.
1: PID heating control, relavant parameters:
P, I, D, OVS, CP, ST, SPD, PDC.
2: ON/OFF cooling control, relevant parameter DB;
need to set PT when it is used for compressor control.
3:PID heating & cooling control (cooling control OUT2
will output through AL1 relay), relevant parameters: P,
I, D, OVS, CP, CP1, PC, DB, ST, SPD, PDC.
4: Over temperature cooling output,relevant
parameter: DB
5. PID cooling, relevant parameter: P, I, D, OVS, CP,
ST, SPD, PDC.
Optional input signal. Note: after selecting the signal,
pls properly set below relevant parameters: SV, AL1,
HY1,AL2, HY2,P,OVS,DB.
Auto-manual control switch, AUTO(0): auto control
only; MAN(1): manual control only;
AM(2): auto-manual shortcut switch
refer to input
signal para-
meters table
(page 3)
1st alarm mode. Note:when AL1 is used as OUT2(co-
oling output), should set AD1=0(close alarm function).
When AD1>6, 2nd alarm function is invalid.
No.
NameSymbol
Illustration Setting range Factory
setting
IX. Menu Illustration
1. Regular Menu
:No mater what model, what control mode it is, it will always display these parameters.
:According to different model, control mode, these parameters will be hidden.
1st alarm value, note: the minus is dealed as absolute
value when it is set as deviation alarm. Refer to
(1) Alarm parameters and output logic diagram
56
2、Operation examples
1. Set target
temperature
SV=100
2、Advanced Menu
22
20
21
ACT
Control execution type. 0: relay or SSR output.
1:SSR output (Code type M select this item).
2: 4~20mA control output, 3: 4~20mA retransimition
output for size 4/7 products. Note:For size 6/8/9
products, when this menu is set as 0 or 1, 4-20mA
output is used as retransimition output.
0~2
(6/8/9 size)
0~3
(4/7 size)
0
AE1 1st alarm extensions function, refer to (2) alarm
extension function table 0~5 0
0~5 0
0~3 0
AE2
DP
2nd alarm extensions function, refer to (2) alarm
extension function table
Decimal point setting, maximum 1 decimal place for
TC & RTD input
23
2. Set menu
INP=K
3. Set menu
OT=0
4. Set menu
DB=2
5. Set menu
ACT=0
6. Set menu
AL1=110
7. Set menu
HY1=5
8. Set menu
AD1=1
1. Set target
temperature
SV=150
2. Set menu
INP=pt
3. Set menu
OT=1
4. Set menu
OVS=5
5. Set menu
ACT=0
6. Set menu
AL1=5
7. Set menu
HY1=7
8. Set menu
AD1=3
25
→→→
150
inp
pt
ot
15
→
ACT
0
→
AL1
5
→
HY1
7
→
AD1
3
1)Example 1, ON/OFF control:
Sensor:K type, measure range -50~1300℃; target temperature: 100℃; control mode:
heatin; control requirement: ON/OFF control, when current temperature PV reaches 100℃,
stop heating; when PV is lower than 98℃, start heating again; control output: relay; alarm: 1
alarm, when PV>110℃, alarm output on; when PV<105℃, alarm output off.
2)Example 2, PID control:
Sensor: PT100, measure range -200~600℃; target temperature: 150℃; control mode:
heating; control requirement: PID control (note: in order to get stable temperature control,
please use the auto-tuning function when the controller is powered on for the first time; if the
temperature control is stable after the auto tuning, there is no need to repeat this step in the
future usage.); control output: SSR; alarm: 1 alarm, when PV>SV+5℃, alarm output on,
when PV<SV-2℃, alarm output off.
25
→→→
100
inp ot
0
db
2
→
ACT
0
→
AL1
110
→
HY1
5
→
AD1
1
42
43
45
CAL
CAH
VER
YES/OK
YES/OK
YES
YES
44 SSM 0 ~1 0
Software version, read only
Self-calibration low limit input operation, after adding
the low end signal to the signal input terminal, flash
YES to activate, after confirm and display OK, the
input signal low end calibration is completed.
Self-calibration high limit input operation, after adding
the high end signal to the signal input terminal, flash
YES to activate, after confirm and display OK, the
input signal high end calibration is completed.
Enable R/S key to switch RUN / STOP operation.
0: Forbidden 1: Enable This setting is only for
panel operation, not for communication operation.
CAE 0(N)
1(Y)N
41
User self-calibration enable function, this parameter
is only for the input signals except TC/RTD;
Y:enable the self-calibration parameters;
N: don’ t use the self-calibration parameters.
No.
NameSymbol
Illustration Setting range Factory
setting
27
28
FL -50
FH 1200
29
30
31
32
33
34
35
BRH
OLH
ST
SPD
0.0 ~105.0
0~1
0~1
1200
100.0
BRL FL~FH
FL~FH
OLL 0
0
0~6 N
PDC
FUZ
-5.0~100.0
-50
36
PT
0~9999 0
37
38
BAD
ADD
DTC
9.6
11~247
0
Modbus Communication ADD
39
40
0~2
0~2
N0
PRTY
PV fuzzy tracking value, properly set this value on
some occasions, it can get a more stable control
display value, this value is unrelated with actual
measured value. Note: after setting this value, when
alarm setting value is equal to SV set value, alarm
output operation is subject to actual measured value.
Set as 0 to close this function.
26
Filter coefficient, the higher of value, the stronger of
filter function
UT Temperature unit: ℃: Celsius degrees. ℉: Fahrenheit
degrees. Note: No unit for linear signal (25)℃
(25)℃
(26)℉
25 FT 0~255 10
(0~20)
DTR 0.0 ~2.0
(10)
1.0
24
0
0~2
Measuring range low limit and high limit.
For temperature sensor input, please keep the factory
setting value. For 4 ~ 20mA / 0 ~ 10V input, please
set the corresponding range for the low limit and the
high limit. For example, 0~10V corresponds to -20~50,
set FL to - 20, set FH to 50. Setting range:
-1999~9999, associated with DP decimal point menu.
4~20mA analog output low limit and high limit. For
example, 4~20mA corresponds to 0~100, set brL to 0,
set brH to 100. Note: it can be set as reverse analog
output, for example, 100~0 corresponds to 4~20mA.
Current control output low limit and high limit, only
valid for 4~20mA current control output. It is used to
limit the output current amplitude. For example, in the
control of frequency converter, if the motor cannot be
stopped, please set the output low limit OLL to 10%;
in heating control, if the user don’ t want full-power
output at the beginning of heating, please set the
output high limit OLH to 80%.
Compressor start delay time, unit: sec
Baud rate 0 (4.8): 4800; 1 (9.6): 9600;
2 (19.2): 19200
Communication parity check setting,
0:NO 1:ODD 2:EVEN
Communication data transport sequence 000;
1st bit function reserved; 2nd bit is byte sequence
exchange; 3rd bit function reserved.
Auto-tune activation after power-on, 0: work normally
after power-on, 1: automatically enter PID parameters
auto-tune status after power-on; long press “ AT ” key
to exit auto-tune.
PID control speed adjustment,option
: 0 (N) no function,
1 (s) slow, 2 (ss) medium slow, 3 (SSS) very slow,
4 (F) fast, 5 (FF) medium fast, 6 (FFF) very fast
PID algorithm option: 0(FUZ): Advanced fuzzy PID
arithmetic; 1(STD): normal PID arithmetic
Refer to
measured
signal
parameter table
Refer to
measured
signal
parameter table
Refer to COMM.
protocol
note③
XI. Key function operation
1. RUN/Stop mode
1)Under the measure mode, press and hold “R/S” key > 3 sec to enter STOP mode, SV
window will display “STOP”, main control output stops or keep the minimum output.
2)Under STOP mode, press and hold “R/S” key to exit STOP mode. Press “ ” key to
modify SV value.
3)Under STOP mode, alarm output and analog output work normally.
2. PID auto-tune operation:
1)Before auto-tuning, please switch off the load power, or set the meter as STOP mode.
2)Before auto-tuning, PV value should meet below condition: when it is PID heating
control, PV needs to be much smaller than SV; when it is PID cooling control, PV needs
to be much greater than SV.
3)Before auto-tuning, please set a proper alarm value or eliminate the alarm condition, in
order to prevent the auto-tuning procedure from being affected by alarm output.
4)Set PID type and SV value; the factory default setting is fuzzy PID.
5)Set as PID control, if there is OLL & OLH output limitation, please set the output to a
proper range; factory default setting is OLL=0%, OLH=100%.
6)Exit STOP mode, or switch on the load power, and immediately press and hold “AT ”
key to enter auto-tuning mode, then the AT indicator light is on.
7)The auto-tuning procedure will take some time, in order not to affect auto-tune result,
please don`t modify the parameters or power-off.
8)When AT light turns off, it automatically exits auto-tune mode, PID parameters will be
updated automatically, and then the meter will control automatically and precisely.
9)During the auto-tuning procedure, below actions will cause the termination of the
precess, press and hold “AT” key, measure beyond the scope, abnormal display, switch
to STOP mode, power-off, etc.
10)Note: In the occasions with output limiting operation, sometimes, even if the
auto-tuning is carried out, the best PID parameters still cannot be obtained.
11)Experienced users can set a proper PID parameter according to their experience.
3.PID heating and proportional cooling control operation
1)Set the control mode OT as 3.
2)PID heating control operates on OUT1; proportional cooling control operates on OUT2.
3)Proportional cooling control OUT2 outputs via AL1 alarm function terminals.
4)Please set the cooling start hystersis DB to a value greater than 5, to ensure the cooling
output will not affect the PID heating control.
5)Please set the cooling control cycle CP1 and the cooling proportionality coefficient PC
to the proper value.
6)When PV value > SV+DB value, the cooling control start to effect; the bigger value of
PV, the longer output time of OUT2
4. Auto-manual switch function
1)Enter common menu, set parameter A-M as “AM”.
2)After return back to measure control interface, press “ ” key to switch auto-manual
operation.
3)When it is switched to manual control, lower line LED will display output percentage:
M0~M100 (corresponding to 0%~100%), press UP key and DOWN key to modify the
output percentage.
4)Before the switch from manual control to auto control, in order to ensure the smooth
switch, please press Shift key to modify the SV value first.
5)After the meter is rebooted, the default setting is manual control and output 0%.
SET
SET
Display
LLLL/HHHH
Checking methods
Checks whether the input disconnection and whether normal of FH/ FL value,
working environment temperature and whether input signal is selected correctly.
X. Checking methods of simple fault
(2)Alarm extension function table
AE1/AE2
value
0
1
2
3
4
5
Alarm handling method when
it displays HHHH/LLLL Power on, alarm inhibition
Power on, no alarm inhibition
(As long as the alarm condition is met, alarm
output immediately.)
Power on, alarm inhibition
(After power on and before the PV value reaches
the SV for the first time, the alarm will not output.
After that alarm work normally)
Alarm status remains the same
Forced alarm output
Forced alarm close
Alarm status remains the same
Forced alarm output
Forced alarm close
87
Handling of abnormal communication:
When abnormal response, put 1 on the highest bit of function code. For example: Host request
function code 0x03,and slave response function code should be 0x83.
Error code:
0x01--- Illegal function: the function code sent from host is not supported by meter
0x02--- Illegal address: the register address designated by host beyond the address range of
meter.
0x03--- Illegal data: the written data value sent from host exceeds the corresponding data range
of meter.
Communication cycle:
Communication cycle is the time from host request to slave response data, i.e.: communication
cycle= time of request data sending +slave preparation time + response delay time + response
return time, e.g.: 9600 Baud rate:communication cycle of single measured data ≥250ms.
Meter adopts Modbus RTU communication protocol, RS485 half duplex communication.
Read function code 0x03, write function code 0x10 or 0x06. Adopt 16 digit CRC check, the
meter does not return for error check. Factory default setting: slave address 1, baud rate 9600,
no check, 8 digits data bit, 1 digit stop bit, data type is 16 digits signed (unsigned) int.
Data frame format:
1. Read register
For example:Host reads integer SV(set value 200)
The address code of SV is 0x2000, because SV is integer(2 dyte), seizes 1 data register. The
memory code of decimal integer 200 is 0x00C8. Note: when reading data, should read DP
value or confirm DP menu value first to ensure the decimal point postion, after that transform
the read data to get the actual value. Conversely, it should transform the data to
corresponding ratio before writing the data in meter
XII. Communication protocol
Start bit
Data bit
1 8 1Set in Menu PRTY
Stop bit Check bit
XIII. Version and Revision History
2021.06.30 1st editionA/0 version
Date Version Revision content
Meter
ADD
Function
code
Start
ADD
high bit
Start
ADD
low bit
Data byte
length
high bit
Data byte
length
low bit
※CRC
code
low bit
※CRC
code
high bit
Host request (Read multi-register)
1 2 3 4 5 6 7 8
0x01 0x03 0x20 0x00 0x00 0x01 0x8F 0xCA
Function code abnormal answer: (For example: host request ADD is 0x2011)
1 2 3 8 9
0x01 0x83 0x02 0xC0 0xF1
Meter ADD Function code Error code
Slave abnormal answer(Read multi-register)
※CRC code
low bit
※CRC code
high bit
Slave normal answer(Read multi-register)
Data
low bit
Data
high bit
※CRC
code
low bit
※CRC
code
high bit
1 2 3 4 5 6 7
0x01 0x03 0x02 0x00 0xC8 0xB9 0xD2
Meter
ADD
Function
code
Data byte
length
2. Write multi-register
For example: Host use 0x10 function code write SV(set value 150)
ADD code of SV is 0x2000, because SV is integer(2 dyte), seizes 1 data register. The hexadecimal
code of decimal integer 150 is 0x0096.
0x01 0x10 0x20 0x00 0x00 0x01 0x02 0x00 0x96
Meter
ADD
Function
code
Start ADD
high bit
Start ADD
low bit
Data byte
length high bit
Data byte
length low bit
※CRC code
low bit
※CRC code
high bit
Slave normal answer (write multi-register)
87654321
0x090x0A0x010x000x000x200x100x01
Data
low bit ※CRC code
low bit
※CRC code
high bit
ADD
low bit Data
high bit
Meter
ADD Function
code ADD
high bit
Data
low bit
※CRC code
low bit
※CRC code
high bit
ADD
low bit
Data
high bit
Meter
ADD
Function
code
ADD
high bit
Host write SV with 0x06 function(set value 150)
Slave normal answer(write single-register)
87654321
0x000x000x200x060x01
Host request(write single-register)
87654321
0x640x020x96
0x640x020x96
0x000x000x200x060x01
Meter ADD Function code Error code ※CRC code low bit ※CRC code high bit
54321
0xA10x01 0x86 0x02 0xC3
Slave abnormal answer ( write single-register)
Meter
ADD
Function
code
Start
ADD
high bit
Start
ADD
low bit
Data byte
length
high bit
Data
high
bit
Data
low
bit
Data byte
length
low bit
Data
byte
length
1 2 3 4 5 6 7 8 9 10 11
Host request (write multi-register)
0x07 0xFC
※CRC
code
low bit
※CRC
code
high bit
Default 1 decimal point
Meter parameters address mapping table
0x2000(48193)
0x2001(48194)
1
2
No.
Add(Register No①)
Register R/W Remark
1
1
R/W
R/W
0x2003(48196)
41R/W
0x2002(48195)
31 R/W
24
25 Output mode ACT R/W
26 RUN/STOP operation R/W
1st alarm extended function AE1 R/W
22
23
Control mode OT
2nd alarm extended function AE2 R/W
R/W
20
21
1st alarm mode AD1
Reserve
2nd alarm
mode
AD2
R/W
R/W
1:RUN 2:STP
3:Run auto-tune
4:Stop auto-tune
0x2004(48197)
0x2005(48198)
0x2006(48199)
0x2007(48200)
0x2008(48201)
0x2009(48202)
0x200A(48203)
5
6
7
8
9
10
11
Default 1 decimal point
Engineering work
without decimal point
1
1
1
1
1
1
1
1
1
1
1
1
1
1
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0x200B(48204)
0x200C(48205)
0x200D(48206)
0x200E(48207)
0x200F(48208)
0x2010(48209)
12
13
14
15
16
17
1
1
1
R/W
R/W
R
0~100
0x2011(48210)
18
1
1
1
1
0:Auto; 1: Manual
2:Auto-Manual
switch
0x2012(48211)
19
Set value SV
1st alarm value AL1
Variable name
2nd alarm value AL2
1st alarm hysteresis HY1
2nd alarm hysteresis HY2
Display low limit FL
Display high limit FH
Analog output low limit BRL
Analog output high limit BRH
Control output low limit OLL
Control output high limit OLH
Heat & Cool control dead zone DB
Overshoot limit OVS
Proportional coefficient of cooling PC
Amend value PS
PV fuzzy tracking value DTR
Measured value PV
Output percentage MV
Auto-Manual switch A-M 1R/W
R
0x2105(48454)
0x2106(48455)
0x2102(48451)
0x2103(48452)
0x2104(48453)
0x2101(48450)
0x2100(48449)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
27
28
29
30
31
32
33
34
35
36
37
Decimal pointDP
Unit display UT
Filter constants FT
Proportional coefficient P
Integral time I
Differential time D
Control speed fine-tune SPD
Heating control cycle CP
Cooling control cycle CP1
Cooling delay time PT
Optional input signal INP
25(℃)26( F)
No decimal point
No decimal point
No decimal point
No decimal point
No decimal point
No decimal point
Refer to signal table
41
42
43
44
PID arithmetic type PDC
Lock LCK
Meter name
Output state
38
39
40
Meter address ADD
Communication baud rate BAD
Comm. data transfer sequence DTC
R
R
R
R
R
R
Note ②
Note ③
0x2107(48456)
0x2108(48457)
0x2109(48458)
0x210A(48459)
0x210B(48460)
0x210C(48461)
0x210D(48462)
0x210E(48463)
0x210F(48464)
0x2110(48465)
0x2111(48466)
0x2115(48470)
0x2116(48471)
0x2117(48472)
0x2118(48473)
0x2112(48467)
0x2113(48468)
0x2114(48469)
0x2119(48474)
45 Parity Check PRTY 1R
R:Read only;R/W:Read & write
D7 D6 D5 D4 D3 D2 D1 D0
AT AL2 AL1 OUT2 OUT1STOP HHHH LLLL
Note①: The register number is the address converted to decimal plus 1 and then the register
identification code 4 is added in front; for example: the register number of the data address
0x2000 is 8192 + 1 = 8193 and then 4 is added in front, that is, the register number 48193;
Related applications can be seen, such as Siemens S7-200 PLC.
Note ②: Measurement status indication. When the data bit is 1, it means execution, and when it
is 0, it means no execution.
Note③: DTC communication data transmission sequence description
Reserve
Byte transfer order: when it is 0, the sequence is 1, 2; and when it is 1, the
sequence is 2, 1
Reserve
□ □ □
DTC:

Popular Temperature Controllers manuals by other brands

Ropex Resistron RES-430 Series operating instructions

Ropex

Ropex Resistron RES-430 Series operating instructions

MULTISPAN UTC-122 operating manual

MULTISPAN

MULTISPAN UTC-122 operating manual

Novus N1020 instruction manual

Novus

Novus N1020 instruction manual

Xetron STC-1000Pro user manual

Xetron

Xetron STC-1000Pro user manual

Emos T105 manual

Emos

Emos T105 manual

Ropex RESISTRON RES-401 operating instructions

Ropex

Ropex RESISTRON RES-401 operating instructions

Motorola HMTS1050 Specifications

Motorola

Motorola HMTS1050 Specifications

Steamist S170-1 Instructions for installation and use

Steamist

Steamist S170-1 Instructions for installation and use

Carlin EZ-Temp instruction manual

Carlin

Carlin EZ-Temp instruction manual

Ravanson KR-1011 user manual

Ravanson

Ravanson KR-1011 user manual

Full Gauge Controls MT-519Ri manual

Full Gauge Controls

Full Gauge Controls MT-519Ri manual

Mold-Masters TempMaster MT Series user manual

Mold-Masters

Mold-Masters TempMaster MT Series user manual

BriskHeat HL101 Series instruction manual

BriskHeat

BriskHeat HL101 Series instruction manual

VDH ALFANET 79 PI user manual

VDH

VDH ALFANET 79 PI user manual

American Standard ZZSENSAL0400AA Installer's guide

American Standard

American Standard ZZSENSAL0400AA Installer's guide

RADSON Purmo Tempco CP W user guide

RADSON

RADSON Purmo Tempco CP W user guide

Yudian AI-208 Operation manual

Yudian

Yudian AI-208 Operation manual

Stulz CyberLab Original instructions

Stulz

Stulz CyberLab Original instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.