Spear & Jackson BoilerMag XT Series User guide

Installation and
servicing instructions
www.boilermag.com

Thank you for choosing BoilermagXT, please follow the instructions carefully to ensure that
this BoilermagXT magnetic filtration system is fitted and maintained correctly.
By completing and returning the guarantee card in the pack you qualify for a 10 year
warranty against manufacturing defects. Failure to follow these instructions will invalidate
the warranty.
BoilermagXT is a magnetic filtration system for heating systems in larger
premises such as industrial, commercial and municipal buildings. For other
applications always consult the manufacturer before installing.
This product contains strong magnets. Care and attention should be taken at all
times during installation and servicing. Do not place the magnetic cores on any
ferrous surfaces or near ferrous objects.
Suitable personal protective equipment should be used during all installation and
servicing.
BoilermagXT must be installed by a qualified person in accordance with all
relevant current regulations.
PPE
BoilermagXT Heating & Cooling System Filter
www.boilermag.com

3
BoilermagXT is typically installed on the return circuit as close to the boiler as possible.
On larger systems, such as the one shown, smaller BoilermagXT units may be installed
elsewhere to give extra protection for radiators and pipework.
Please also ensure that the BoilermagXT is located in a position which gives adequate
access above to lift out the magnets during servicing and maintenance. Also access is
required to the underneath of the unit to connect a hose or hold a bucket during draining.
Venting Options
The BoilermagXT unit is fitted with a manual vent, however, an additional Automatic Air Vent
has been packaged along with unit separately. The auto-vent will automatically release the
trapped air maintaining heating efficiency.
Please note: If using the Automatic Air Vent, operating pressure is reduced to 10 bar and
maximum temperature to 110˚C respectively.
Please find enclosed the installation instructions for the Automatic Air Vent.
Ensure the heating system is isolated prior to carrying out
installation or maintenance work.
Where to Install
Guide to Installation
Larger unit Smaller unit
BOILER
HEADER TANK
www.boilermag.com

1. Identify a suitable location (see ‘Where to
Install’ p3).
2. Ensure enough clearance to carry out
cleaning as the rods must be lifted out of the
unit to clean. See dimensions in column B in
the table below.
3. Mark and then cut out the correct length of
pipe section to be removed to accommodate
the BoilermagXT unit and isolation valves.
Ensure the cut is level and burr free.
(Isolation valves are not included in the
BoilermagXT pack.)
4. Install appropriate isolation valves to the
pipework and fit the valves to the two PN16
flanges (see below for flange dimensions).
5. Position the BoilermagXT in place then align
and secure the fittings to connect the unit
to the valves.
6. Open the isolation valves and turn on the
heating system
7. Complete the BoilermagXT warranty card and
return to Spear & Jackson.
8. Run the heating system at normal operating
temperature and check installation integrity.
Flange details
Part No. Inlet / outlet ∅ABFlange spacing C
BMXT150/2/AAV 2" 305 260
BMXT200/3/AAV 3" 390 360
BMXT200/4/AAV 4" 390 360
BMXT300/6/AAV 6" 360 470
BMXT300/8/AAV 8" 400 525
BMXT400/10/AAV 10" 770 760
BMXT400/12/AAV 12" 820 760
B
A
C
2" PN16 4" PN16 6" PN163" PN16
8" PN16
10" PN16
Ø165
Ø125
Ø18
Ø220
Ø180
Ø18
Ø285
Ø240
Ø22
Ø340
Ø22
Ø295
Ø405
Ø355
Ø26
Ø200
Ø160
Ø18
12" PN16
Ø460
Ø410
Ø26
all dimensions in mm unless stated
Installing BoilermagXT
Installation details
www.boilermag.com

5
Cleaning and servicing must only be carried out by a qualified person in accordance with
all relevant current regulations.
To maintain optimum efficiency we recommend cleaning annually. However when a
BoilermagXT is fitted to an existing heating system we recommend more regular checks as it
is likely there will be a large build-up of ferrous oxide (black sludge) to clear out.
To service and maintain BoilermagXT follow the instructions below:
Lift out the magnetic cores using the handle on top
of the unit. *Warning see below*. Be careful not to
place the cores on or near ferrous items.
For 8",10" and 12" BMXT units, the weight may exceed safe single person lifting limits.
Please check and if required do as 2 persons or alternatively as a mechanical lift.
Either place a bucket underneath or connect a
hose to the 1¼" drain valve on the underside of
the BoilermagXT. Remove the drain plug and open
the drain valve. Partially open the inlet isolation
valve and allow the contents to drain through
the drain valve.
Isolate the heating system and close the isolation
valves on either side of the BoilermagXT unit.
Remove the black tricone positioned on the lid.
Servicing & Maintenance Instructions
21
4
3
www.boilermag.com

*Automatic Air Vent option also available
Servicing & Maintenance Instructions
If required open the vent shown on the top of the
unit to release any trapped air*.
When the draining water runs clear turn off the inlet
isolation valve and allow the remaining contents to
drain. Close the drain valve and replace the plug.
65
7
Replace the magnetic core and hand tighten
the black tricone to retain. Re-open both
isolation valves.
www.boilermag.com

7
Performance
Magnetic performance 9,000 gauss high strength
Performance reading on tube surface
Magnetic material Rare earth neodymium iron boron (NdFeB)
Magnet grade N42SH – inspected and confirmed by hysterograph prior to use
Temperature 5º to 150ºC (If using Automatic Air Vent option, the maximum
temperature is 110ºC)
Operating pressure 12 bar (If using Automatic Air Vent option, the operating
pressure is 10 bar)
Drain Valve 1 1/4”
Materials
Housing 304 grade stainless steel
Magnet tube assembly 316 grade stainless steel – aerospace quality
Surface finish Internal - bead blast
External - powder coated, black
Sealing Viton o-ring, brown
Options High temperature samarium cobalt magnetic material +250º C
Warranty 10 years
D
C
∅B
∅A
Part No. Inlet / Outlet
Dia. A
Filter
Dia. B
Flange
spacing
C
Height
D
No.
magnetic
rods
Flow rate
cubic
metres/
hour
Flange
type
BMXT150/2/AVV 2”/DN50 170mm 260mm 280mm 520 PN16
BMXT200/3/AVV 3”/DN80 220mm 360mm 335mm 755 PN16
BMXT200/4/AVV 4”/DN100 220mm 360mm 335mm 785 PN16
BMXT300/6/AVV 6”/DN150 325mm 470mm 420mm 9110 PN16
BMXT300/8/AVV 8”/DN200 325mm 525mm 460mm 9140 PN16
BMXT400/10/AVV 10”/DN250 406mm 760mm 600mm 16 220 PN16
BMXT400/12/AVV 12”/DN300 406mm 760mm 675mm 16 310 PN16
Product data
www.boilermag.com

While every effort has been made to ensure the accuracy of the information in this
publication please note that specifications may change without notice.
1½"connectionsBoilermag
Domestic Filter
(22mm/28mm)
Inhibitor &
Cleaner
To optimise your heating system performance
try our range of treatment products
Testing Kits and
Dosage Indicator Strips
Electrolytic
Scale Reducers
Don't forget to register for your
Boilermag 10 year warranty...
Visit www.boilermag.com
T: +44 (0)114 225 0624
F: +44 (0)114 225 0610
service@boilermag.com
This manual suits for next models
7
Table of contents
Popular Industrial Equipment manuals by other brands

erowa
erowa PowerChuck P manual

Veeco
Veeco K465i GaN Operation and maintenance

Mayr
Mayr EAS-HT 405 Series Installation and operational instructions

Mark 7
Mark 7 Power Trim Xpress instruction manual

Mayr
Mayr EAS-NC Lastic-Backlash-free Installation and operational instructions

Emerson
Emerson PACSystems RX3i Important product information