SPX MARLEY CP User manual

CP cooling tower
OPERATION - MAINTENANCE
uk_Z1045767_A ISSUED 8/2018 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT.
user manual

2
contents
These instructions assist in obtaining efficient, long life from Marley
counterflow cooling towers. Direct questions concerning cooling
tower operation and maintenance to your Marley sales representative.
Always include your tower serial number when requesting informa-
tion or ordering parts. Look for this number on the sidewall casing.
Note
The following defined terms are used throughout this manual to
bring attention to the presence of hazards of various risk levels, or
to important information concerning the life of the product.
Indicates presence of a hazard which can cause severe personal
injury, death or substantial property damage if ignored.
Indicates presence of a hazard which will or can cause personal
injury or property damage if ignored.
Indicates special instructions on installation, operation or mainte-
nance which are important but not related to personal injury hazards.
Caution
Note
Tower Startup........................................................................................................................................................ 3
Operation.................................................................................................................................................................. 4
Maintenance .......................................................................................................................................................... 7
Water Quality and Blowdown................................................................................................................... 8
Spare Parts..........................................................................................................................................................10
Seasonal Shutdown Instructions .......................................................................................................11
Tower Inspection and Maintenance.................................................................................................12
Inspection and Maintenance Schedule ........................................................................................13
Troubleshooting................................................................................................................................................14
Safety........................................................................................................................................................................15
Inspection Checklist .....................................................................................................................................16
Warning

3
operation
Tower Startup
Microorganisms including Legionella bacteria can exist in premise
plumbing including cooling towers. The development of an effective
water management plan (WMP) and implementation of maintenance
procedures are essential to prevent the presence, dissemination and
amplification of Legionella bacteria and other waterborne contami-
nants throughout premise plumbing. Before operating the cooling
tower, the water management plan and maintenance procedures
must be in place and regularly practiced.
WATER SYSTEM–Consult a knowledgeable water treatment professional to
clean and treat your new cooling tower prior to startup. Cooling towers must
be cleaned and disinfected regularly in accordance with local public health
services and recommendations. Do NOT attempt any service unless the fan
motor is locked out.
Remove any dirt and trash which has accumulated in the cold water basin.
Remove any sediment from the cold water collection basin, sump, and screens.
Use a water hose to flush cold water collection basins.
Fill the cold water collection basin and circulating water system until the op-
erating water level is reached.
OPERATE WATER SYSTEM–Prime and start the circulating water pumps.
Increase the flow of circulating water gradually to design water flow rate to
avoid water hammer which could damage the distribution piping system.
Increase the flow of circulating water gradually to match design water flow
rate. Circulate water over the cooling tower continuously for several days
before starting the mechanical equipment and placing the cooling tower into
continuous operation.
When starting in freezing weather, follow procedures outlined in
Freezing Weather Operation.
INSPECTION–It is imperative that all operating assemblies be inspected
before they are placed in operation. The following is a list of components to
be checked before starting the tower:
1–Check tightness of bolts in fan hood joints.
2–Check bolted joints in the fan and gear motor drive assemblies.
3—Check the piping connection hardware
Warning
Note
➠

4
4—Visually inspect the fill, drift eliminators, air inlet louvers and the distribution
piping and spray nozzles.
5–Check gear motor oil for sludge or water by draining off and testing a sample
as outlined in the manufacturer’s Gear Motor IOM Manual. Check gear
motor oil level. Add oil as required. Refer to the Gear Motor IOM Manual
for oil filling procedure and list of recommended lubricants.
6–Rotate fan by hand to be sure of free rotation and ample tip clearance.
7–Test run each fan separately for a short time. Check for excessive vibration
or unusual noise. If either is present, see Troubleshooting Guide on pages
14 and 15 of this manual. Fan must rotate clockwise when viewed from
above. Recheck gear motor oil level.
8–Check functioning of make-up water supply. Make sure the blowdown will
carry the proper amount of water.
Clean the sump screens several times during the first weeks of
operation. After this, clean sump screens weekly.
STARTING FAN–Operate the fan for 30 minutes to permit the gear motor oil
to come up to operating temperature and check the motor load with a watt
meter, or take operating volt and ampere readings and calculate motor hp. Pitch
fans if required to pull correct contract horsepower when circulating design
water rate at design hot water temperature. Refer to the manufacturer’s Fan
IOM Manual for instructions. Check tightness of fan blade fasteners after a
brief period of operation.
Entering water temperature in excess of 80°C may result in fill de-
formation.
TOWER PERFORMANCE–Keep the cooling tower clean and water distribu-
tion uniform to obtain continued maximum cooling capacity.
The capacity of a cooling tower to cool water to a given cold water temperature
varies with the wet-bulb temperature and the heat load applied to the cooling
tower. As the wet-bulb temperature drops, the cold water temperature also
drops. However, the cold water temperature does not drop linearly with the
wet-bulb temperature.
A cooling tower will not control heat load. The flow rate of water circulated
through the cooling tower will determine the temperature range of cooling in
conjunction with a given heat load. The hot water and cold water temperatures
will increase with higher heat loads.
Note
Caution
operation

5
HOT WATER DISTRIBUTION SYSTEM–Maintain uniform water distribution
at the nozzles (uniform spray cone). The amount of water circulated should
approximate the contract requirements and the nozzle pressure should be kept
constant. Lower pressures may indicate excessive losses in the piping system
and/or insufficient pump capacity; greater pressures might indicate clogged
nozzles and/or overpumping. If a greatly reduced water flow rate is desired, it
may be advisable to change nozzle sizes to obtain the desired pressure and
maintain proper water distribution. An SPX Cooling Technologies engineer
can advise minimum and maximum flow rates for even distribution.
COLD WATER COLLECTION BASIN–A suitable depth must be maintained
to keep the pumps from pulling air into the line. The amount of “make-up”
water required to keep the water in the collection basin at the required depth
depends upon the “evaporation loss” and “blowdown” .
FREEZING WEATHER OPERATION–During periods of low temperature
operation, 2°C to 5°C or below, ice will form on the relatively dry parts of the
cooling tower that are in contact with the incoming air. Primarily, this includes
the air inlet and adjacent structural framing. Your understanding of cold weather
operation will be enhanced if you read “Cooling Towers and Freezing
Weather” Technical Report H-003 available at spxcooling.com.
Ice forming characteristics on any given cooling tower will vary, depending on
velocity and direction of wind, circulating water rate, and heat load. Excessive
ice formation may be controlled by regulating air and water flow through the
tower by one or more of the following procedures:
1–Shut the fan down. This reduces the cooling air rate to a minimum and in-
creases the quantity of warm water at the air inlet to a maximum. However,
normal “fan off” operation causes reverse air flow by aspiration and may
cause water blowout and therefore must be done with caution and moni-
toring. For automatic operation, a timer switch can be provided to shut the
fan down for a few minutes each hour.
2–If the cooling tower has VFD, operate the fans at half speed forward. This
reduces the cooling air rate (heat transfer) and increases the quantity of
warm water at the air inlet.
3–With no heat load on the circulating water, icing cannot be controlled. Towers
must not be operated with reduced water rate and/or no heat load during
freezing weather. If a bypass directly into the cold water basin is used, all
water must be bypassed.
operation

6
Reverse operation of fans is not recommended.
INTERMITTENT OPERATION–When the unit is operated intermittently dur-
ing freezing weather, it is necessary that the water be drained from the tower
piping to insure protection against freezing and possible rupture.
Always shut off electrical power to the tower fan motor prior to
performing any inspections that may involve physical contact with
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
Well-maintained equipment gives the best operating results and the least
maintenance cost. SPX recommends setting up a regular inspection schedule
to insure effective, safe operation of the cooling tower. Use the schedule on
page 19 to obtain continuously good performance with the least tower main-
tenance. See Cooling Tower Inspection Check List in this manual. Keep a
continuous lubrication and maintenance record for each cooling tower.
HOT WATER DISTRIBUTION SYSTEM–Keep the circulating water and
distribution system (piping and nozzles) clean and free of dirt, algae, and scale.
Algae and scale may clog nozzles, eliminators, fill, and piping, and may collect
on the equipment served thus reducing its performance.
The interior of the cooling tower can be accessed through an inspection door
located on the side casing. This will provide access to the water distribution
system, eliminators and fill.
Caution
Warning
operation

7
DRIFT ELIMINATORS–Eliminators should be kept clean.
Do not walk or step on the eliminators.
COLD WATER COLLECTION BASIN–Inspect collection basin occasionally
for leaks and repair if necessary. Keep cold water outlets clean and free of
debris. Makeup and circulating water controls must operate freely and maintain
the desired water quantity in the system.
Do not walk or step on the fan hood.
The gear motor is located on top of the fan hood. A ladder and platform is
provided for access. The fan guard can be removed in sections for fan main-
tenance.
GEAR MOTOR–Make weekly and monthly oil checks. Inspect internal part
during seasonal oil change. Lubricate and maintain each gear motor in ac-
cordance with the manufacturer’s instructions. If repair work is necessary,
contact the nearest representative of the gear motor manufacturer.
FAN–Inspect fan blade surfaces every six months. For detailed maintenance
information, refer to the manufacturer's Fan IOM Manual.
PAINTING–Periodically clean and, if necessary, recoat all metal parts subject
to corrosion.
COLD WATER COLLECTION BASIN—A section of the air inlet louvers can
be removed to access the cold water collection basin. Remove both star
screws and the top fastening strip. The louver segment can be removed as
a block in one piece.
Warning
Warning
maintenance

8
Water Quality and Blowdown
BLOWDOWN–Blowdown, or bleed-off, is the continuous removal of a portion
of the water from the circulating system. Blowdown is used to prevent the
dissolved solids from concentrating to the point where they will form scale.
The amount of blowdown required depends upon the cooling range (the dif-
ference between the hot and cold water temperatures) and the composition
of the make-up water (water added to the system to compensate for losses
by blowdown, evaporation and drift). The following table shows the amount
of blowdown required to maintain different concentrations with various cool-
ing ranges:
BLOWDOWN–% OF CIRCULATING RATE
EXAMPLE: 159 m3/hr circulating rate, 10°C cooling range. To maintain
4 concentrations, the required blowdown is 0.458% or .00458 times
159 m3/hr, which is .73 m3/hr.
If tower is operated at 4 concentrations, circulating water will contain four
times as much dissolved solid as the make-up water, providing none of the
solids form scale or are otherwise removed from the system.
CHEMICAL TREATMENT–In some cases chemical treatment of the cir-
culating water is not required if adequate blowdown is maintained. In most
cases, however, chemical treatment is required to prevent scale formation and
corrosion. Sulfuric acid or one of the polyphosphates is most generally used
to control calcium carbonate scale. Various proprietary materials containing
chromates, phosphates or other compounds are available for corrosion control.
When water treatment chemicals are required, the services of reliable water
treating companies should be obtained.
maintenance
Cooling Range Number of Concentrations
1.5X 2.0X 2.5X 3.0X 4.0X 5.0X 6.0X
3ºC .78 .38 .25 .18 .11 .08 .06
6ºC 1.58 .78 .51 .38 .25 .18 .14
8ºC 2.38 1.18 .78 .58 .38 .28 .22
11ºC 3.18 1.58 1.05 .78 .51 .38 .30
14ºC 3.98 1.98 1.32 .98 .64 .48 .38
Multipliers are based on drift of 0.02% of the circulating water rate.

9
Biofilm, a gelatinous organic growth, and algae, a green moss, may grow
in the cooling tower or heat exchangers. Their presence can interfere with
cooling efficiencies. Proprietary compounds are available from water treating
companies for the control of slime and/or algae; however, compounds which
contain copper are not recommended. Chlorine and chlorine containing
compounds are effective algaecides and slimicides. If used, chlorine should
be added as intermittent (or shock) treatment only as frequently as needed
to control the slime and algae. Chlorine and chlorine containing compounds
should be added carefully since very high levels of chlorine may occur at or
near the point of entry into the circulating water system.
FOAMING–Heavy foaming sometimes occurs when a new tower is put into
operation. This type of foaming generally subsides after a relatively short pe-
riod of operation. Persistent foaming can be caused by the concentrations of
certain combinations of dissolved solids or by contamination of the circulating
water with foam-causing compounds. This type of foaming can sometimes be
minimized by increasing the blowdown, but in some cases foam depressant
chemicals must be added to the system. Foam depressants are available from
a number of chemical companies.
Maintenance of Fill Performance
Water must be kept clean by treatment, screening, or filtering to
avoid the possibility of fill clogging and loss of thermal performance.
Potential Causes of Fill Clogging:
• Debris and suspended materials.
• Scale—Can be sulfates, silicates, carbonates, or oxides. Scaling effects can
be accentuated by suspended solids.
• Algae and/or Biofilm—Can control with chlorine or non-oxidizing biocides.
Possible Sources of Scale:
• Calcium Sulfate—From make-up and sulfates produced by sulfuric acid for
pH adjustment. Calcium sulfate should be kept below 1000 ppm expressed
as CaCO3.
• Calcium Carbonate—Generally will not form scale in the cooling tower if
carbonate scaling does not occur in the condenser.
• Exceptions: If make-up water contains surplus free carbon dioxide, scaling
may be inhibited in the condenser, but may occur in the tower fill because
of CO2stripping.
Warning
maintenance
➠

10
• Silicates and Oxides—Silica scale is virtually impossible to remove. Silica
scale is unlikely if SiO2is held below 150 ppm. Oxides, such as iron oxide,
can coat all parts of the system if soluble iron is present in concentrations
above 0.5 ppm. Iron oxides do not usually develop into thick scales but can
accentuate the development of other scales.
Do not walk directly on the fill. Place appropriate walking surface
on fill to avoid crushing. Recommended walking surface would be a
minimum of 15mm thick plywood measuring at least 30cm x 60cm.
Spare Parts
SPX Cooling Technologies manufactures and inventories cooling tower re-
placement parts. Typical lead time is 10 working days. Contact your Marley
representative for emergency service.
Owners should consider maintaining inventory of critical mechanical compo-
nents, such as a fan assembly and gear motor to avoid emergency shutdown
of cooling tower operations.
Be sure to furnish the tower serial number when ordering parts.
Caution
maintenance

11
Seasonal Shutdown Instructions
Tower–Drain all tower piping.
During shutdown, follow recommendations in the Cooling Tower Inspection
and Maintenance section of this manual before attempting repairs. Apply
protective coating as required to all metal parts. Particular attention should be
given to mechanical equipment supports, drive shaft and drive shaft guards.
Mechanical Equipment:
Gear motor – Downtime for 3 months or less.
1. Follow the manufacturer's instruction for shutdown instructions.
2. Check the oil level and if necessary remove any condensation water.
3. Consider the gear motor space heater option
Gear motor – Downtime for 3 months or more.
1. Follow the manufacturer's instruction for shutdown instructions.
2. If the motors do not have space heaters, operate mechanical equipment
one hour each week.
3. Do not start the motor without determining that there will be no interference
with free rotation of the fan drive.
4. At startup, operate mechanical equipment one hour or until oil is warm, then
shut the equipment down. Drain the oil and refill with new oil.
5. Refer to manufacturer’s Gear Motor IOM manual for instruction on changing
oil.
Refer to the Downtime Instruction User Manual for downtime exceeding six
months. If shutdown period is longer than seasonal, contact your Marley sales
representative for additional information.
maintenance

12
Cooling Tower Inspection and Maintenance
Microorganisms including Legionella bacteria can exist in premise
plumbing including cooling towers. The development of an effective
water management plan (WMP) and implementation of maintenance
procedures are essential to prevent the presence, dissemination and
amplification of Legionella bacteria and other waterborne contami-
nants throughout premise plumbing. Before operating the cooling
tower, the water management plan and maintenance procedures
must be in place and regularly practiced.
In addition, the following steps are recommended:
Do NOT attempt any service unless the fan motor is locked out.
• Consult a knowledgeable water treatment professional to clean and treat
your cooling tower. See Tower Startup section of this manual.
• Cooling towers must be cleaned and disinfected regularly in accordance
with local public health services and recommendations. •Workersperform-
ing decontamination procedures must wear personal protective equipment
(PPE) as directed by their facility safety officer.
• Cooling towers must be visually inspected regularly to assess signs of
bacterial growth, appearance of debris and scale on drift eliminators and
general operating conditions.
• Replace worn or damaged components.
To minimize the presence of waterborne microorganisms, including Legionella,
follow the water management plan for your facility, perform regularly scheduled
cooling tower inspections and maintenance, and enlist the services of water
treatment professionals.
For additional technical support, contact your Marley sales represen-
tative. For help identifying the sales representative in your area, visit
spxcooling.com/replocator.
Warning
maintenance

13
inspection and maintenance schedule
General Recommendations
—more frequent inspection and maintenance may be warranted
D–Daily W–Weekly M–Monthly Q–Quarterly S–Semiannually Y–Yearly R–as Required
Fan and Fan Guard
Gear Motor
Drift Eliminators
Fill
Cold Water Basin
Hot Water Distribution System
Air Inlet Louvers
Structural Members
FRP Casing
Fan Hood
Ladders, Platform and Doors
Inspect for clogging M M W W
Check for unusual noise or vibration D D
Inspect keys, keyways and set screws S S
Make sure vents are open S
Lubricate (grease) R
Check oil seals M
Check operating oil level D
Check static oil level M
Check oil for water and sludge M
Change oil S
Check fan blade tip clearance S
Check water level D
Check for leakage W S S S S
Inspect general condition SSYSYSSSYSS
Tighten loose bolts SS SSS
Clean RRRRSRR
Repaint R R
Rebalance R
Inspect/repair for safe use Y Y

14
troubleshooting
Trouble Cause Remedy
Motor will not start
Power not available at motor terminals
Check power at starter. Correct any bad connections between the control
apparatus and the motor.
Check starter contacts and control circuit. Reset overloads, close contacts,
reset tripped switches or replace failed control switches.
If power is not on all leads at starter, make sure overload and short circuit
devices are in proper condition
Wrong connections Check motor and control connections against wiring diagrams.
Low voltage Check nameplate voltage against power supply. Check voltage at motor
terminals.
Open circuit in motor winding Check stator windings for open circuits.
Motor or fan drive stuck Disconnect motor from load and check motor and fan drive for cause of
problem.
Rotor defective Look for broken bars or rings.
Unusual motor noise
Motor running single-phase Check motor and attempt to start it. Motor will not start if single-phased.
Check wiring, controls and motor.
Motor leads connected incorrectly Check motor connections against wiring diagram on motor.
Bad bearings Check lubrication. Replace bad bearings.
Electrical unbalance Check voltages and currents of all three lines. Correct if required.
Air gap not uniform Check and correct bracket fits or bearing.
Rotor unbalance Rebalance
Cooling fan hitting end belt guard Reinstall or replace fan.
Motor runs hot
Wrong voltage or unbalanced voltage Check voltage and current of all three lines against nameplate values.
Overload Check fan blade pitch. See “Fan User Manual.” Check for drag in fan
drivetrain and from damaged bearings.
Wrong motor RPM Check nameplate against power supply. Check RPM of motor and drive
ratio.
Bearing overgreased Remove bearing reliefs. Run motor up to speed to purge excessive
grease.
Wrong lubricant in bearings Change to proper lubricant. See motor manufacturer's instructions.
One phase open Stop motor and attempt to start it. Motor will not stat if single-phased.
Check wiring, controls and motor.
Poor ventilation Clean motor and check ventilation openings. Allow ample ventilation
around motor.
Winding fault Check with ohmmeter.
Bent motor shaft Straighten or replace shaft.
Insufficient grease Remove plugs and regrease bearings.
Too frequent starting or speed changes
Limit cumulative accelerations time to a total of 30 seconds/hour. Set on/
off or speed change set points farther apart. Consider installing a Marley
VFD drive for fine temperature control.
Deterioration of grease or foreign material in grease Flush bearings and relubricate.
Bearings damaged Replace bearings.
Motor does not come up
to speed
Voltage too low at motor terminals because of line
drop
Check transformer and setting of taps. Use higher voltage on transformer
terminals or reduce loads. Increase wire size or reduce inertia.
Broken rotor bars Look for cracks near the rings. A new rotor may be required. Have motor
service person check motor.
Wrong motor rotation Wrong sequence of phases Switch any two of the three motor leads.

15
troubleshooting
SAFETY FIRST–The CP cooling tower has been designed to provide a safe working environment while either
operating or shut down. The ultimate responsibility for safety rests with the operator and owner. When water
flow to the tower is shut off or when portions of the tower require maintenance, temporary safety barricades may
be required around openings and fall protection equipment should be utilized where appropriate for compliance
with OSHA and CE regulations, standards and good safety practices.
Trouble Cause Remedy
Unusual fan drive
vibration
Loose bolts and cap screws Tighten all bolts and cap screws on all mechanical equipment and
supports.
Fan
Make certain all blades are as far from center of fan as safety devices
permit. All blades must be pitched the same. See “Fan IOM Manual.” Clean
off deposit build-up on blades
Fan noise Blade rubbing inside of fan hood Adjust to provide blade tip clearance
Loose bolts in blade clamps Check and tighten if necessary.
Scale or foreign
substance in circulating
water system
Insufficient blowdown See "Water Treatment" section of this manual.
Water treatment deficiency Consult competent water treating specialist. See "Water Treatment"
section of this manual
Condensing temperature
too warm.
See “Cooling Tower
Operation.”
Entering wet bulb temperature is above design
Check to see if local heat sources are affecting evaporative condenser.
See if surrounding structures are causing recirculation of evaporative
condenser discharge air. Discuss remedy with Marley representative.
Design wet bulb temperature was too low. May have to increase evaporative condenser size. Discuss remedy with
Marley representative
Actual process load greater than design May have to increase evaporative condenser size. Discuss remedy with
Marley representative
Overpumping Reduce water flow rate over evaporative condenser to design conditions.
Evaporative condenser starved for air
Check motor current and voltage to be sure of correct contract
horsepower. Repitch fan blades if necessary. Clean eliminators. Check to
see if nearby structures or enclosing walls are obstructing normal airflow
to evaporative condenser. Discuss remedy with Marley representative.
Excessive drift exiting
evaporative condenser
Spray system malfunction Inspect spray system for proper operation. Correct as necessary.
Faulty drift elimination Check to see that the eliminators are clean, free of debris and installed
correctly. Clean if necessary. Replace damaged or worn out components.

16
inspection checklist
Date Inspected Inspected By
Owner Location
Owner's Tower Designation
Tower Manufacturer Model No. Serial No.
Process Served by Tower Operation: Continuous Intermittent Seasonal
Design Conditions m3/hr HW °C CW °C WB °C
Number of Fan Cells
Condition: 1—Good 2—Keep an eye on it 3—Needs immediate attention
1 2 3 Comments
Structure
Casing Material
Structural Material
Fan Deck Material
Stairway? Material
Ladder? Material
Handrails? Material
Interior Walkway? Material
Cold Water Basin Material
Water System
Distribution System
Header Material
Manifold Material
Branch Arms
Nozzles — Orifice Diameter
Heat Transfer System
Fill
Eliminators
Inlet Face of Fill
Use this space to list specific items needing attention:

17
inspection checklist
Condition: 1—Good 2—Keep an eye on it 3—Needs immediate attention
Mechanical Equipment 1 2 3 Comments
Gear Drive Units
Manufacturer
Model
Ratio
Oil Level:
Full Add Immediately
Low, check again soon
Oil Condition:
Good
Contains Water
Contains Metal
Contains Sludge
Oil Used — Type
Seals
Backlash
Fan Shaft Endplay
Any Unusual Noises?
No
Yes
Action Required:
Fans
Manufacturer
Fixed Pitch
Adjustable Pitch
Diameter
Number of Blades
Blade Material
Hub Material
Hub Cover Material
Blade Assembly Hardware
Tip Clearance
min. max.
Vibration Level
Fan Cylinder Height
Mech.Eqpt. Support Mat'l
Oil Fill and Drain Lines
Oil Level Sight Glass
Vibration Limit Switches
Makeup Valves
Other Components
Motor Manufacturer
Name Plate Data:
kW
RPM
Phase
Hz
Volts
F.L. Amps
Frame
SF
Special Info.
Last Lubrication — Date
Grease Used — Type
Any Unusual Noise?
No
Yes
Action Required
Any Unusual Vibration?
No
Yes
Action Required
Any Unusual Heat Build-up?
No
Yes
Action Required

uk_Z1045767_A | ISSUED 8/2018
© 2017-2018 SPX COOLING TECHNOLOGIES, INC | ALL RIGHTS RESERVED
In the interest of technological progress, all products are subject to design
and/or material change without notice.
SPX COOLING TECHNOLOGIES UK LTD
3 KNIGHTSBRIDGE PARK
WORCESTER WR4 9FA UK
44 1905 750 270 | ct.fap.emea@spx.com
spxcooling.com
CP cooling tower
USER MANUAL
Table of contents
Other SPX Accessories manuals
Popular Accessories manuals by other brands

Danfoss
Danfoss AKS 4100 instructions

INNOBIZ
INNOBIZ Pluglia Sonic V2 manual

Schroder
Schroder Model 1 instruction manual

ROSE DISPLAYS
ROSE DISPLAYS ANOGOTCHA SQUARE WITH MULTICLIPS manual

PCB Piezotronics
PCB Piezotronics 352B30 Installation and operating manual

WiNetworks
WiNetworks Win7225-2 installation guide