210-0388 - Edition October2012
2.12 STARTING THE APPLIANCE
Before starting the water-heater ensure that:
The gas supplied is the one for which the appliance is
set
Current standards and provisions concerning the
installation of these appliances (particularly with regard
to correct connection of the flue system and the gas
supply line) have been observed
Earthing has been carried out in accordance with
current regulations
The gas isolating cocks (on the meter and near the
heater) are open
The water heater is full of water
2.13 FAULT FINDING
The control device locks out without ignition
the flame detection circuit is faulty and the control box
self-check prevents the continuation of the cycle
the flame detection electrode has a loose earth
connection
At the end of the pre-purge cycle the ignition electrode
does not spark and the control goes to lock-out
the ignition transformer inside the control box is faulty
the ignition electrode connection at the terminals of the
appliance is broken
At the end of the pre-purge cycle the ignition electrode
provides a spark, but the flame does not form and the
control box goes to lock-out
gas supply is off or there is air inside the line
the gas valve does not open because the solenoids are
faulty or their electrical connections are broken
At the end of the pre-purge cycle the ignition electrode
provides a spark, the flame forms but the control box
goes to lock-out
the flame is not establishing correctly owing to lack of
gas pressure
the detection electrode is not correctly positioned and
is not in contact with the flame
the electrical connection of the detection electrode is
broken
The appliance goes into lock-out during normal
functioning.
the gas supply has been interrupted, even temporarily:
the control box has not detected the presence of flame
and it has gone to lock-out
one of the cases in preceding points has occurred
during an intermittent functioning cycle
The heater functions for brief intermittent periods,
even though the thermostat is functioning correctly
and is in the heat requirement position.
the adjustable control thermostat is defective and is not
detecting the correct temperature
the pressure switch stops the burner because the flow
from the fan is not correct owing to an obstruction in
the flue system or excessive length
The control box is not in lock-out but the cycle remains
in pre-purge.
the pressure switch does not allow for continuation of
the cycle because the flue system is obstructed
the pressure switch does not allow for continuation of
the cycle because the fan is not functioning correctly or
does not exert sufficient pressure
the pressure switch does not allow functioning because
it is faulty or its electrical connections are broken
the pressure switch does not allow functioning because
the pressure line is obstructed or the silicon tube is
detached or broken
The control box is not in lock-out but the cycle doesn’t
start.
during the initial check of the control the pressure
switch contacts have been found in closed position
(because they are stuck or owing to incorrect setting of
the pressure switch) and accordingly do not enable the
continuation of the cycle
Check if the printed circuit fuse has blown up
IMPORTANT