Sulzer EC 531 User manual

www.sulzer.com
Equipment controller EC 531
EN User guide
81307150B (08/2018)
Ethernet RS 485
Digital outputs (V+)
27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 47 49 50 51 52
V- DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 AO1 AO2 V+ AI1 AI2 AI3 AI4 V- AI5 AI6 RJ45 + - Shld
out (4-20 mA) in Pt100/PTC
Bias +
Term.
Bias -
EC 531
AUTO
0
AUTO
0
1 2
Esc.
RS 232
USB
232SR-medoM)CDV43-9(stupnilatigiDrewoP
V+ V- DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 DI11 DI12 DI13 DI14 AI7 V- AI8 V- V- RXD TXD RTS CTS
12345678910 11 12 13 14 15 16 17 18 19 20 22 23 24 25 26
Pt100/Leak

2
Copyright © 2018 Sulzer. All rights reserved.
This manual, as well as the software described in it, is furnished under license and may be used or copied only in
accordance with the terms of such license. The content of this manual is furnished for informational use only, is
subject to change without notice, and should not be construed as a commitment by Sulzer. Sulzer assumes no
responsibility or liability for any errors or inaccuracies that may appear in this book.
Except as permitted by such license, no part of this publication may be reproduced, stored in a retrieval system,
or transmitted, in any form or by any means, electronic, mechanical, recording, or otherwise, without the prior
written permission of Sulzer.
Sulzer reserves the right to alter specications due to technical developments.
EN
81307150B

3
Contents
About this guide, audience and concepts 5
1 Overview of the display symbols 7
1.1 EC 531 panel......................................................................................................................7
1.2 Symbols on the graphic display .........................................................................................8
1.2.1 Time and date ....................................................................................................................8
1.2.2 Level and the dynamic eld ................................................................................................8
1.2.3 Outlet value on the display .................................................................................................8
1.2.4 Pump information window..................................................................................................9
1.3 Floats and overow sensor on the display..........................................................................9
1.4 Pump, mixer, pipe and start / stop symbols.....................................................................10
1.5 Power and alarm indicator ..............................................................................................10
1.6 Menus and submenus, passcodes and personal alarm...................................................10
1.6.1 Status view....................................................................................................................... 11
1.7 Entering the main menu and set the language ................................................................. 12
1.7.1 Manual control ................................................................................................................. 12
1.8 Quick status ..................................................................................................................... 13
2 Setup the EC 531 15
2.1 Set general conguration, system, ID and communication settings ................................. 15
2.2 Setup the digital inputs, digital outputs, analog inputs and analog outputs ..................... 17
2.3 Setup the pump pit parameters .......................................................................................18
2.4 Set pump 1 and pump 2 settings and their alarms ..........................................................18
2.5 Common P1–P2...............................................................................................................20
2.6 Set log settings and events ..............................................................................................20
2.7 Set up communications to surrounding units VFD, soft starters and energy meter .........21
2.8 Set up cleaner, mixer or drain pump (if used) ...................................................................21
3 Detailed description of the functions 23
3.1 Pump capacity calculation...............................................................................................23
3.2 Overow ow calculation..................................................................................................34
3.3 Pump alternation..............................................................................................................35
3.4 Pump reversing ................................................................................................................37
3.5 Speed controlled pumps (VFD) ........................................................................................38
3.6 Best efciency point pump control ..................................................................................40
3.7 Crash log.......................................................................................................................... 41
3.8 Communication................................................................................................................ 41
3.9 Cross reference table .......................................................................................................43
4 Further explanations of some functions of analog- and digital in- and output signals 45
4.1 Digital in: personnel alarm and local mode.......................................................................45
4.2 Digital in: block operation.................................................................................................45
4.3 Digital out: data register set point.....................................................................................45
4.4 Digital out: logic IO ...........................................................................................................46
4.5 Digital out: external reset alert..........................................................................................47
4.6 Analog in: outlet pressure.................................................................................................47
4.7 Analog out: data register and data register 2’s complement............................................ 47
EN
81307150B

4
5 APpendix: tables of guide line to the menus in EC 531 49
5.1 Quick status: system menu ..............................................................................................50
5.2 Quick status: pump pit.....................................................................................................50
5.3 Quick status: pump 1 and pump 2................................................................................... 51
5.4 Quick status: digital in and digital out...............................................................................53
5.5 Quick status: analog in and analog out ............................................................................53
5.6 Detailed status: system ....................................................................................................54
5.7 Detailed status: pump pit .................................................................................................55
5.8 Detailed status: pump 1 and pump 2 ...............................................................................57
5.9 Detailed status: PID regulator...........................................................................................58
5.10 Detailed status: analog inputs ..........................................................................................59
5.11 Detailed status: analog outputs........................................................................................60
5.12 Detailed status: digital inputs ...........................................................................................60
5.13 Detailed status: digital outputs .........................................................................................61
5.14 Detailed status: communication .......................................................................................61
5.15 Detailed status: eld bus modules (RS 485).....................................................................63
5.16 Settings: alarm legend .....................................................................................................64
5.17 Settings: system...............................................................................................................65
5.18 Settings: pump pit............................................................................................................65
5.19 Settings: pump 1 and pump 2 .........................................................................................67
5.20 Settings: common P1 – P2 ..............................................................................................70
5.21 Settings: PID regulator .....................................................................................................72
5.22 Settings: pulse channels ..................................................................................................72
5.23 Settings: analog logging...................................................................................................73
5.24 Settings: analog inputs..................................................................................................... 74
5.25 Settings: analog outputs ..................................................................................................77
5.26 Settings: digital inputs......................................................................................................78
5.27 Settings: digital outputs....................................................................................................79
5.28 Settings: communication .................................................................................................80
5.29 Settings: eld bus modules (RS 485) ...............................................................................82
5.30 Settings: select language.................................................................................................83
EN
81307150B

5
ABOUT THIS GUIDE, AUDIENCE AND CONCEPTS
This guide describes the equipment controller EC 531. The equipment controller can either be used
stand-alone or communicate values and conditions to a central SCADA system or a web based alarm
and monitoring solution like AquaWeb from Sulzer.
Installation guide There is a separate document Installation guide that describes how to physically install the pump
controller (printed document in the installation package, and also a PDF on www.sulzer.com).
Audience This guide is intended for system administrators and operators of EC 531 equipment controller.
Prerequisites This guide assumes that you already are acquainted with those pumps you are set to control and
have the sensors connected to EC 531.
The system administrator must also know and decide on the following:
1. The pump controller can either use an analog level-sensor, which measures the water level in the pit,
for precise control over start and stop levels, or it can use simple oat switches placed at start and
stop levels.
• Float switches can be used in addition to an analog level-sensor, as a backup, and as an
additional alarm input.
• An analog level-sensor has several advantages over oat switches: it is more robust
(cannot get stuck or be mechanically jammed); it is more accurate; it is more exible (the
start and stop levels can easily changed); you can get readings of the water level in the
pit, the inow, overow and the pump capacity; you can optimize the pump performance
in various ways, including exercising, alternative stop levels, tariff control etc.
• It is also possible to employ an alternative stop level, usually a lower level than normal,
that is effective once after a number of pump starts. This can be useful if it is desirable to
“completely” empty the pit once in a while.
2. You need to know if the pump(s) should be exercised in case of long idle periods. If the installation
has one or two pumps, you need to decide if the pumps should alternate.
3. If the electricity has daily varying tariffs, you must know the times of high / low tariffs.
4. You must know how overow will be measured: if it will be measured using both an overow detector
(to detect the start of the overow) and a level sensor (to measure the actual ow), you must know the
parameters (exponents and constants) to be entered as settings so that the overow can be accu-
rately calculated by the EC 531.
5. You need to know which alarm class, A-alarm or B-alarm (see Glossary and conventions), to assign
each alarm.
Reading guide For installation, see the separate document Installation guide, which covers EC 531. Before you
make any settings, or use the control panel, read chapter 1 Oiverview of the display symbols —it
describes the general functionality and the meaning and usage of the controls on the panel.
The system administrator must ensure that all settings according to chapter 2 Setup the EC 531 are
suitable for your application.
NOTE! The default settings are listed in the Installation guide
EN
81307150B

6
Text appearing and declaration in this guide
Text in italic is a description of text on the display or a description how you nd your way through
the menus by key strokes. Text in bold, is how you have to do a change of the settings in the EC 531
menu.
Most settings in chapter 2 only apply to the system administrator, but the following also apply to those
who operate the controller: language selection, date and time settings, units, backlight time-out,
buzzer, operator passcode, start / stop levels.
Glossary and conventions
To designate a menu item in a hierarchy, an angle bracket is used to separate the levels. Ex-
ample: Settings > System means the menu item you reach by rst choosing the menu item
Settings, which has a number of submenus, where you choose the menu item System.
Text in blue indicates a hypertext link. If you read this document on a computer, you can click on
the item, which will take you to the link destination.
Pump exercising: Long idle periods in a corrosive contaminated environment are not good
for pumps. As a countermeasure, they can be “exercised” at regular intervals, which will reduce
corrosion and other detrimental effects.
Alarm class: The alarm class can be either A-alarm or B-alarm. A-alarms are those that require
immediate action, so operational staff in the eld should be alerted regardless of the time of day.
B-alarms are less important, but should be taken care of during normal work hours.
Digital in: A signal that is either ON or OFF (high or low), where high is anything between 5 and
35 volts DC, and low is anything below 2 volts.
Digital output: A signal that is either ON or OFF. At ON condition output current is sourced
from the power supply and the output is high (~V+). At OFF condition the output is low but it
cannot serve as a drain function (no output current). Are typically connections to relays.
Analog output: Signal in the range 4-20 mA. Sourced from power supply.
Analog input: Eight analog inputs used for connecting sensors. Ain:1 to Ain:4 are 4-20mA in-
puts. Ain:5-Ain:6 are congurable for Pt100 and PTC. Ain:7-Ain:8 are congurable for or Pt100
and Leakage.
Pump reversing: The controller can reverse the pump if the necessary external equipment is
installed in the station. The controller can reverse the pumps on number of occasions, e.g. low
capacity, pump fail, fallen motor protector, over currents and after number of starts
RS 485 modules: Refer to surrounding units connected to the RS 485 bus, e.g. soft starters,
VFDs, and an energy meter.
EN
81307150B

7
1 OVERVIEW OF THE DISPLAY SYMBOLS
EC 531 is designed to control 1-2 pumps. It can operate a pump station stand alone and / or within
a surveillance system together with some communication equipment. For conguration and opera-
tor interaction, use the menus which can be selected using the arrow, Enter and Esc keys. With the
AquaProg software, conguration and back up of settings can be stored on a PC.
Add the 3G modem CA523 to create a full remote alarm and monitoring solution, together with an
AquaWeb rental contact or by any SCADA system.
This section will guide you through all the symbols on the display of EC 531.
1.1 EC 531 panel
1.2 Symbols on the graphic display
1.2.1 Time and date
1.2.2 Level and the dynamic eld
1.2.3 Outlet value on the display
1.2.4 Pump information window
1.3 Floats and overow sensor on the display
1.4 Pump, mixer pipe and start / stop symbols
1.5 Power and alarm indicator
1.6 Menus and submenus, passcodes and personal alarm
1.6.1 Status view
1.7 Entering the main menu and set the language
1.7.1 Manual control
1.8 Quick status
1.1 EC 531 panel
The default screen (top-level view) of the display on the EC 531 dynamically shows the operating sta-
tus of the pumps and conditions in the pit, displaying just about everything you need to know about
the current situation. Figure 1-1 shows symbols and explains their meanings. The unit will always re-
vert to this view after 10 minutes of inactivity in any other view (such as showing menus or submenus).
In the submenus you can always return to the default screen by pressing ESC.
Figure 1-1 EC 531 panel
Pumps in auto (green) or
Manual (yellow) mode
Alarm indicator, ashing when
unacknowledged alarms
Start / Stop the pumps
in manual mode
Service ports, RS 232 and USB
Keypad to enter the menus
and alter settings
Power indicator
EN
81307150B

8
1.2 Symbols on the graphic display
There are several symbols in the EC 531 display which are described below.
Figure 1-2 Symbols on the display
The top screen appears differently depending if there is a level sensor in the system or not. There is
no level value presented if the pit is without a level sensor. If no analog (Ain1-4, preferred Ain1) input is
dedicated for Level sensor, the controller assumes there are Start / Stop oats. The start / stop oats
are animated and must have a dedicated input if they are to appear on the display.
1.2.1 Time and date
When an alarm occurs, this eld turns red for A-alarm or yellow for B-alarms and the alarm text is also
shown here. The time and date is no longer visible.
Graphic display with level sensor Graphic display with start / stop oats
Figure 1-3 Examples of the rst line
Alarm line
When no active or unacknowledged alarm, System time and date will be shown instead.
(This is the clock used for time stamped events such as logging)
(())
Unacknowledged alarm (red line = A-alarm, yellow line = B-alarm)
Symbol and alarm text will be shown.
Acknowledged active alarm
Symbol and alarm text will be shown.
1.2.2 Level and the dynamic eld
If level sensor is installed on one of the analog inputs, the height of the level in the pit is present-
ed, shown with two decimal places, and by means of a visual water level indicator on the graphics
display. Level can be referenced from sea level (if set). If there is a high-level alarm setup and it gets
activated, the dynamic eld turn into red. If the system runs on oats, no level or visual water level
indicator will be shown on the display.
1.2.3 Outlet value on the display
Outow: After the controller has calculated the pump capacity, a value appears on the display when
the pump or pumps run. See the se c t i o n 3.1 Pump capacity calculation for information on how the
calculation is done and which parameters are necessary to set.
Outlet pressure: If there is an outlet pressure sensor installed, the value appears on the display. See
the section 3.1 Pump capacity calculation for information on how the calculation is done and which
parameters are necessary to set.
First line in normal mode First line when A-alarm
Pit water level
Overow sensor
Start / Stop levels
Inlet info
First line
Clock / Alarm
Mixer
Outlet info
Pump info. windows
High level oat
Visual water level
indicator
Low level oat
High level oat
Low level oat
Pump Pump
EN
81307150B

9
1.2.4 Pump information window
The pump information window contains several symbols and not all of them are visible if there isn’t
an alarm. Without any alarms or fault conditions, only Current and grey shaded Temperature and
Leakage symbols are shown.
Figure 1-4 Pump information window without alarms or fault conditions
Summary of the symbols in pump information window:
High temperature, combination of set up sensors.
Orange when pending. Turns red when there is an active alarm associ-
ated. Grey when inactive.
Leakage, combination of set up sensors.
Orange when pending. Turns red when there is an active alarm associ-
ated. Grey when inactive.
Vibration fault, only shown when active.
Orange when pending alarm and red when active alarm.
Electric fault, only shown when active. Combination of electric faults
(Fallen motor protector, High / low motor current, Phase missing). Or-
ange when pending alarm and red when active alarm.
Current indicator bar, top turns red when reaching high current limit.
Motor
Current
Will be shown:
• with one decimal in range 0 to 9.9, otherwise without decimals
• will show kilo ampere as integers if above 999 A
Active alarms are prioritized, if more than two alarms are active they are prioritized as follows
1) Temperature, 2) Leakage, 3) Vibration, 4) Electric faults
1.3 Floats and overow sensor on the display
High- and low level oats are green in normal mode. They switch position (animated) and are ashing
red when activated.
Start / stop oats are gray in non-active mode, and blue when activated.
Overow sensor is green in normal mode, turn to ashing red when activated.
Motor current
Temperature Leakage
EN
81307150B

10
1.4 Pump, mixer, pipe and start / stop symbols
The symbols are as follows:
Pipe with pump reference
• Animated ow when pump running in forward direction
Pump symbol, will rotate when pump running
Triangle can be:
• Green – Non blocked
• Yellow – Externally blocked or in reverse
• Red – Blocked by pump fault
• When blocked, symbol will be crossed
• If manual reset is needed a ashing ’!’ will appear.
Mixer symbol
• Same colour coding as pump symbol
Start and stop symbols are just relative to each other and no value is shown on the top screen.
1.5 Power and alarm indicator
The two leftmost symbols on the panel are for power and alarm indication:
• A green light indicates that the unit is powered.
• The red alarm indicator ashes whenever there is an unacknowledged alarm, and the dis-
play tells the type of the alarm. When the alarm is acknowledged, the light turns steady
red, and remains so until the active alarm is remedied.
1.6 Menus and submenus, passcodes and personal alarm
The arrow keys on the key pad have different functions depending where in the menus you are. From
the top screen, the functions are following:
Key pad shortcuts
Left arrow Will open ”Quick status” menu for pump 1
Right arrow Will open ”Quick status” menu for pump 2
Enter Will acknowledge present alarm in alarm list
Up / down arrows Will open the menus
Key pad
Press either the up or down arrow button to switch to the menu view. When entering the menus and
submenus, you can navigate through them all by using the arrow buttons and Enter. If there are visible
triangles on the last line on the screen, these symbolize which choices could be made. Step through
the lines by pressing up / down arrow and press Enter to enter a submenu or change value. Esc
button will cancel the current operation and goes back to top screen (or default screen). A right arrow
indicates that a submenu is available.
EN
81307150B

11
Escape to cancel and
return to top screen
Symbolize the choices
which can be made with
the arrow keys
Use the left / right buttons to choose the insertion point. Use the up / down buttons to increase / de-
crease a value or letter. Press Enter to enable editing of a value. Values and strings can also be altered
through the alphanumeric keyboard. Finish the editing by pressing enter.
You conrm an operation with the Enter button, or acknowledge an alarm. Pressing the Escape will
cancel operation and leave setting unchanged or return animated top screen.
Passcodes There are three security levels:
1. Daily operations, such as acknowledging an alarm or stopping a pump, do not require any pass-
code or authorization.
2. Operational settings, such as setting the start or stop levels for the pump, require a passcode at
the level of Operator; default 1.
3. Conguration settings that affect the basic functionality or access, such as the type of level sensor,
require a passcode at the level of System; default 2.
After entering a passcode a timer is started, all settings are unlocked until timer resets. The factory
default passcodes are 1 and 2 respectively, but the codes can be changed under the menu item
Settings > System. Whenever a passcode for Operator is requested, you may supply either the pass-
code for Operator or System.
Personal alarm When the pump station is manned, a personal alarm can be issued if the maintenance person hasn’t
shown activity within a certain period of time. For details about settings related to this, see section
4.1 Digital in: Personnel alarm and local mode (assigning Alarm type, Alarm delay and Max time to
reset), how to set up the digital input and digital output for staff in station.
After the specied Alarm delay, the assigned output is activated so a visual or audio signal can alert
the maintenance person that the alarm timer must be reset. If the alarm timer is not reset within Max
time to reset, a personal alarm is sent out.
NOTE! To reset the timer, just push any button on the control panel.
1.6.1 Status view
Status view is easy to access by pressing [left arrow] for pump 1 or [right arrow] for pump 2 on the key
pad. Status view shows Pump running time, Number of starts, Start / Stop level, Pump capacity,
Motor current, Motor power, Last pump capacity calculated value, Starts since last reverse, if the
pump is Blocked or not and Detailed status.
Pump running time, Number of starts and Blocked have submenus which are accessible by press-
ing Enter at current line.
EN
81307150B

12
1.7 Entering the main menu and set the language
Press up- or down arrow and following screen appears:
Step down to Select language and press Enter.
Press Enter again and use the down arrow to step between the languages, press Enter when your
language of choice is highlighted. After the language is selected, press left arrow to return to main
menu or Esc to return to default screen.
1.7.1 Manual control
Enter the menu by pressing up- or down arrow from main screen. Press Enter at Manual control,
then the menu and sub menus are as follows:
EN
81307150B

13
Submenu Parameter Value Type/Passcode
Pump 1
Manual start NO; YES Setting, Operator password
Pump reversing NO, YES Setting, Operator password
Fallen motor protect NO, YES Status value
Reset motor prot. NO, YES Setting, Operator password
Reset temp. prot. -OK-/[YES], -Tripped- Setting, Operator password
State of M-0-A switch MANUAL, Pump not in auto, AUTO Status value
VFD frequency 0.01 Hz Status value
Set manual frequency 0.1 H z Setting, Operator password
Pump 2
Manual start NO; YES Setting, Operator password
Pump reversing NO, YES Setting, Operator password
Fallen motor protect NO, YES Status value
Reset motor prot. NO, YES Setting, Operator password
Reset temp. prot. -OK-/[YES], -Tripped- Setting, Operator password
State of M-0-A switch MANUAL, Pump not in auto, AUTO Status value
VFD frequency 0.01 Hz Status value
Set manual frequency 0.1 H z Setting, Operator password
Mixer control
Start/Stop STOP, START Setting, Operator password
Run indication NO, YES Status value
Reset motor prot. NO, YES Setting, Operator password
Cleaning control Start/Stop STOP, START Setting, Operator password
Drain pump control
Start/Stop STOP, START Setting, Operator password
Run indication NO, YES Status value
Reset motor prot. NO, YES Setting, Operator password
1.8 Quick status
To get an overview status of signals and condition of the station or installation.
Pressing Enter on Quick status opens the sub-menus as shown below.
To get an overview of these menus, see Appendix
EN
81307150B

14
This page is intentionally left blank.
EN
81307150B

15
2 SETUP THE EC 531
Overview of settings
Every station will have its own unique conguration but the procedure to setup the station is similar.
This chapter will guide you through the basic settings in the EC 531. Make note that this does not
cover everything, you must take into account your prerequisites.
The menu item Settings has 14 submenus with a large number of settings that need to be entered by
the system administrator, although they all have default values. The notes below are a recommended
procedure to setup the EC 531.
2.1 Set general conguration, system, ID and communication settings
2.2 Set designated IO functions at DI, DO, AI and AO according to the electrical wiring drawing
2.3 Pump pit parameters and alarms
2.4 Set pump 1 and pump 2 settings and their alarms
2.5 Common P1-P2
2.6 Set log settings
2.7 Set up communications to surrounding units (VFD, soft starters (if used)
2.8 Set up cleaner, mixer or drain (if used)
Each of the 14 submenus under settings are described in separate tables in appendix.
To enter the settings area:
Press down arrow once and you are in the menus, continue to press down arrow to Settings, press
Enter.
All settings require a passcode for System except some settings under the submenu System and the
start / stop levels under submenus Pump 1 and Pump 2 which only require a passcode for Operator.
All the settings can be congured locally from the menus or by AquaProg. The advantage of Aqua-
Prog is you can save the conguration at your PC and easily restore the controller if needed.
2 .1 Set general conguration, system, ID and communication settings
Setup the language, System ID, units (metric or US units) by the menus:
• The topmost menu item System will be selected. Press Enter again.
• The topmost menu under System is Language. Press Enter and give passcode (de-
fault2) by using Up / Down arrows. Scroll to the language of your choice by using the Up
/ Down buttons.
• Select Station ID, Press Enter. Type in your station ID by using Up / Down arrows, re-
quired for AquaWeb or any other surveillance system.
• Select Date format, press Enter. Choose your date format.
• Set Date, Time, Units (Metric or US) and all other setting under this parameter.
• Set System alarms according to your preferences.
• Press Left arrow to return to Main menu; Settings. Scroll down to Communication.
• Set the Protocol of USB (Modbus RTU or TCP), cross reference (if used).
• Set the Protocol of Service port (DB9 in front).
• Modem port (screw terminals 22-26) and the communication parameters.
• Set the baud rate at the RS 485 bus and protocol ID to VFD and Energy meters (if used).
• Set the Ethernet parameters according to your network preferences.
EN
81307150B

16
In AquaProg:
Figure 2-1 System settings Figure 2-2 Communication
EN
81307150B

17
2.2 Setup the digital inputs, digital outputs, analog inputs and
analog outputs
Set designated IO-functions according to the electrical wiring drawing. See your drawings of the
station.
Under Settings, Digital inputs; choose appropriate input according to list
Table 2-1: Table 2-2:
Digital inputs
OFF
Run indication
Manual start
Set manual
Set auto
Start oat
Pump failure
Motor protector
High motor temp. pump
Leakage pump
Stop oat
Low level oat
Overow sensor
High level oat
Start oat drain pump
Local mode
Alarm reset
Power fail
DI pulse channel 1-4
Block PID controller
Alarm input
Block operation
Leakage mixer-drain pump
High temp. mixer or drain pump
Digital outputs
OFF
Pump control
Reset motor protector
Pump fail
Not enough pumps avail
One pump fail
Mixer control
Drain pump control
Cleaner control
Modem control
Remote control
Personnel alarm
High level
Alarm alert
Not ackn. alarm
Active alarm
Pump reversing
Logic IO
Data register set point
Extern reset alert
Table 2-3:
Analog input 1-4
OF F,
Pit level
Motor current
Outlet pressure
Vibrations
Xylem MiniCas Sim
Outow meter
Motor temperature
Free choice
Note
Analog 1 is recommended to be used
for the level sensor due to its higher
resolution
Table 2-4:
Analog outputs
OFF
Pit level
Pit inow
Pit outow
Pit overow
Pulse channel 1
Pulse channel 2
Pulse channel 3
Pulse channel 4
PID ctrl output
Data register
Data register 2 compl.
Set freq. P1
Set freq. P2
EN
81307150B

18
Table 2-5:
Analog input 5-6
OFF
Motor temperature
Free choice
Table 2-6:
Analog input 7-8
OFF
Motor temperature
Leakage
Free choice
In AquaProg:
2.3 Setup the pump pit parameters
Table 2-7:
Pit settings
Station ow*
Overow
Pit alarms
Cleaning control
Mixer control
Drain pump control
Motor protector auto-reset
Level sensor check
Tariff control
Level above sea
* MUST for accurate pump capacity calculation
It is recommended to setup the Pit area under Station ow as this will give the best possible pump
calculations accuracy. These are also tied to Energy calculation, Pump capacity and Outlet calcula-
tions.
There are several alarms which can be set under Pit alarms. Each alarm is congurable to be A- or
B-alarms. Consult your drawings and verify which are important for your installation. Every alarm can
trigger the crash log, see section 3.7 for further information about crash log.
2.4 Set pump 1 and pump 2 settings and their alarms
Important parameters to congure for each pump:
Type of pump control
Running indication
Start / stop level
Pump alarms
Optional parameters: Pump curve
EN
81307150B

19
Pump 1 and pump 2:
Type of pump control:
• Pump disable
If using only one pump in the system; recommended to have pump 2 as disable
• ON / OFF control
A digital output starts the pump without any RS-485 communication to VFD or soft
starter
• VFD manuel speed
Start a VFD which has predened frequency
• VFD PID control
Start / stop pump with digital output and VFD controlled by 4-20mA analog output
from the controller
• VFD best efciency point
Require RS 485 communications to VFD
Select run indication:
• Any discrete source
Output signal or digital input
• Output signal
No return signal from the pump, just activated output signal from the relay contact
• Motor current
Current transformers connected to an analog input
• Fieldbus RS 485
RS 485 communication to / from VFD or soft starter
Start / Stop levels for each pump
Recommended to have different start levels if there are two pumps. Same stop level for two pumps is
ne.
Pump alarms
There are several pump alarms to setup. Each alarm is congurable to be A- or B-alarms. The rst
part, table 2-8 below, is to setup the types of alarm (A- or B), alarm delay and if the alarm shall trigger
the crash log.
Table 2-8:
Pump alarms
No run indication
Fallen motor protector
Motor protector reset error
Pump not in auto
Pump error
Max continuous runtime
Alarm blocked
Max reverse attempts
Low pump capacity
Vibration
Leakage
High temperature
High motor current
Low motor current
Every alarm can trigger the crash log, see section 3.7 for further information about crash log.
EN
81307150B

20
Block pump on alarm
These alarms must be acknowledged on site or remotely to allow the pump to start again.
Hold pump on alarm
All the alarms here will block the pump when the alarm is active. When the criteria for the alarm have
returned to normal state, the pump starts again automatically.
2.5 Common P1–P2
To avoid possible station problems this option has many useful functions like, Pump exercising,
Pump reversing, Max number pumps running, Min relay intervals, Alternations and Pump block-
ing.
Figure 2-3 AquaProg view of common P1-P2
2.6 Set log settings and events
There are 16 congurable analog log channels on the EC 531. It is recommended to the use the log
channels in sequential order from channel 1, as having log channels disabled between active chan-
nels will cause unnecessary data trafc to the surveillance system.
The logs are kept in the controller for 15 days and the oldest will be deleted when the memory is full.
EN
81307150B
Other manuals for EC 531
1
Table of contents
Other Sulzer Controllers manuals