Sulzer ABS PC 441 User manual

www.sulzer.com
Pump Controller Type ABS PC 441
EN Installation Guide
81307060J (03/2022)

81307060J
EN
Pump controller type ABS PC 441, Installation guide
2
Copyright © 2017 Sulzer. All rights reserved.
This manual, as well as the software described in it, is furnished under license and may
be used or copied only in accordance with the terms of such license. The content of this
manual is furnished for informational use only, is subject to change without notice, and
should not be construed as a commitment by Sulzer. Sulzer assumes no responsibility or
liability for any errors or inaccuracies that may appear in this book.
Except as permitted by such license, no part of this publication may be reproduced, stored
in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical,
recording, or otherwise, without the prior written permission of Sulzer.
Sulzer reserves the right to alter specications due to technical developments.

81307060J
EN
3
Pump controller type ABS PC 441, Installation guide
1 INSTALLATION
1.1 Mount the controller
Mount the controller on a 35 mm DIN rail. The physical dimensions of the con-
troller is: 86 x 160 x 60 mm (3.39 x 6.30 x 2.36 inch) (H x W x D). If it doesn’t
easily snap onto the rail, you can pull the small tab at the bottom side of the unit,
using a small screwdriver.
1.2 Make all connections
There are a total of 48 terminals that may be connected to power, sensors,
switches, relays and a modem; these terminals are numbered from 1 to 52 ac-
cording to the following gure:
WARNING Ensure that all power is off, and that all output devices to be connected to the
controller also are turned off before you connect anything!
Table 1 shows all connections to terminals 1-26 at the bottom side of the control-
ler. The usage of the congurable Digital In and Analogue In shown in the table
is the default conguration.
“Digital In” means a signal that is either on or o — high or low, where high is
between 5 and 34 volts DC. Digital In may be connected to either passive de-
vices, such as switches, or active devices that are powered and deliver signals.
Figure 1 shows how to connect such devices to the Digital In terminals.
Table 2 shows all connections to terminals 27–52 at the top side of the control-
ler. The usage of the congurable DO 1 to DO 8 and AO 1 to AO 2 shown in the
table is the default conguration. “DO” stands for “Digital Outputs”, which are
voltage outputs.
The power must be DC between 9 and 34 volts. Figure 2 shows how to connect
a power-fail switch to Digital In 3 (terminal 5) and how to connect a battery pack
for uninterrupted operation.
The modem should be connected according to Figure 8.
For CAN bus (Field bus) see section 1.3 Can bus.
RS-232 port for
a computer
Terminals at the top side of the controller, numbered 27 to 52
Terminals at the bottom side of the controller, numbered 1 to 26

81307060J
EN
Pump controller type ABS PC 441, Installation guide
4
Table 1. Terminals at the bottom side of the pump controller
Factory Settings Namei#
Voltage supply, 10–32 V DC ⇒
V+ 1
V - 2
Overow level Digital In 1 →3
HIgh level oat Digital In 2 →4
Power failure Digital In 3 →5
Personal in station (local mode) Digital In 4 →6
Motor protector pump 1 Digital In 5 →7
Pump 1 not in auto Digital In 6 →8
Spare pump 1 Digital In 7 →9
Motor protector pump 2 Digital In 8 →10
Pump 2 not in auto Digital In 9 →11
Spare pump 2 Digital In 10 →12
Motor protector pump 3 Digital In 11 →13
Pump 3 not in auto Digital In 12 →14
Spare pump 3 Digital In 13 →15
Motor protector pump 4 Digital In 14 →16
Pump 4 not in auto Digital In 15 →17
Low level oat Digital In 16 →18
19
V+ ←20
Level sensor Analogue Inii 1 →21
P1 Motor current Analogue Inii 2 →22
P2 Motor current Analogue Inii 3 →23
P3 Motor current Analogue Inii 4 →24
P4 Motor current Analogue Inii 5 →25
V- 26
i. “Digital In” means a signal that is either on or o (high or low), where high is anything
between 5 and 32 volts DC and low is anything below 2 volts. All digital inputs are
congurable in the menu Settings > Digital Inputs, but the conguration shown here is
the default one.
ii. “Analogue In” means Analogue Input. They are all sensing the current in the range
4–20 mA or 0–20 mA. This is congured in the menu Settings > Analogue Inputs.
Figure 1. The Digital In terminals may be connected
to either passive devices, such as switches, or active
devices that are powered and deliver signals. Con-
nect devices according to the gure. Voltage
Supply
Signal
Output
Signal
ground
Voltage
Supply
PC 441
Digital
inputs
X
Y
V+
Push -button/switch
Signalling device

81307060J
EN
5
Pump controller type ABS PC 441, Installation guide
Table 2. Terminals at the top side of the pump controller
#NameiFactory Settings
27 V - 0V
28 →DOi1. Alarm alert
29 →DOi2. Pump 1
30 →DOi3. Pump 2
31 →DOi4. Pump 3
32 →DOi5. Pump 4
33 →DOi6. Personal alarm alert
34 →DOi7. Relay Mixer
35 →DOi8. High level
36
37 →+ AOii 1. Pit level
38 ←- AOii 1.
39 →+ AOii 2.
O
40 ←- AOii 2.
41
42 V
+↔
CAN_V+
43
CAN_H
44
↔
CAN_SHLD
45
CAN_L
46 V - 0V
47
48 ←CTS
49 →RTS
50 →TX
51 ←RX
52 0V
i. DO means Digital Output. It is a voltage output. See the menu Settings > Digital Out-
puts for conguration of these outputs.
ii. AO means Analogue Output. See Settings > Analogue Outputs for conguration of
these outputs.
Figure 2. The power must be DC between 9 and 34 volts, but if
it also charges batteries, it should be 27.2 V.
Connect a power-fail switch to Digital In 3 (terminal 5) according
to the gure.
For uninterrupted operation in case of power failure, connect a
battery pack according to the gure.
Voltage
Supply
PC 441
Digital input:
"Powerfail"
Relay
Backup battery pack
+
+
Fuse
AC
DC
Battery
charger
27.2 V
V+

81307060J
EN
Pump controller type ABS PC 441, Installation guide
6
Figure 3. Analogue input connection (level sensor)
Figure 4. Digital output connection (external relay)
Figure 5. Analogue output connection
V+
PC 441
PINS
Analogue
In I
Level sensor +
-
4-20 mA
V+
V-
PC 441
PINS
0V
DOI
Relay
Loads are connected series
AO1+
AO1-
PC 441
PINS
With analogue connected
to V-
PLC
V-
A A
+-+-
+
-
V-
V+
0/4 - 20 mA

81307060J
EN
7
Pump controller type ABS PC 441, Installation guide
1.3 CAN bus (Field bus)
A CAN network is of multidrop type witch means that all units are connected in
parallel on the same cable. PC 441 is the master on the bus to which display
devices like CA 511 and any monitoring devices are connected (type CA 441 /
442 / 443).
The CAN cable uses 5 wires. Two wires are used for communication CAN_L and
CAN_H. One wired is shield CAN_SHLD and two wires are used as bus power
V+ and 0V. Bus power allow devices to get power directly from the bus.
Figure 6. CAN connection
1.3.1 Using bus power
Max bus power output from PC 441 is 350 mA (V+). CA 511 can be bus powered
directly from PC 441. Other modules must use an external power supply.
A few rules:
□If CA 511 is the only device connected on the bus. Bus power CA 511 directly
from PC 441.
□If other devices (like CA 441 ..) also are connected. Don’t use bus power from
PC 441 for these devices. Connect an external power supply (V+ and 0V) to
the rst device in the chain.
□If some modules are placed far away from the main unit, it’s a good idea to
use a separate power supply for these units.
1.3.2 CAN termination
The CAN bus shall be terminated at both cable ends.
PC 441 is bus master and has a built-in termination that are always active and
should therefore always be placed in one of the endpoints of the cable.
For other devices you can activate the selectable termination with a switch
marked CAN TERM
Active termination for the device placed on the other endpoint of the cable.
All other devices between should have their termination switch in O position.
Figure 7. CAN network with connection
CA 511 CA 441 / 442 / 443
0V CAN_L SHLD CAN_H V+
0V CAN_L SHLD CAN_H V+
12345
1 2345
PC 441
V+ 42
43
44
45
46
CA 44x
CAN_H
SHLD
CAN_L
0V
~
-
+
Power supply
CAN TERM
ON
CAN TERM
OFF
CAN TERM
OFF
CAN TERM
OFF
CA 511 CA 44xCA 44x CA 44x PC 441
Always
ON

81307060J
EN
Pump controller type ABS PC 441, Installation guide
8
1.3.3 CAN ID
In a CAN network every unit must have a unique address or ID-number.
PC 441 and CA 511 use a xed ID on the bus and no ID settings are needed for
these devices.
On the CA 44x one part of the address is set default depending on device, the
other part of the address is set by a hexadecimal switch, marked “ID”. Choose
address by pump number as in table below or instructions in system manual. If
the device has a unique address and contact with the network master, the CAN
LED is still green. For error codes of the CAN LED see system manual.
When used with PC 441 use the following addresses to achieve correct func-
tions.
Table 3. CA 441 Leakage Monitor
CAN SUB ID Monitoring function
0 Not used with PC 441
1 Pump 1 or pumps 1-4
2 Pump 2
3 Pump 3
4 Pump 4
5 - > F Not used with PC 441
Table 4. CA 442 Temperature Monitor
CAN SUB ID Monitoring function
0 Not used with PC 441
1 Pump 1 or pumps 1-4
2 Pump 2
3 Pump 3
4 Pump 4
5 - > F Not used with PC 441
Table 5. CA 443 Power Monitor
CAN SUB ID Monitoring function
0Main power monitor
1 Pump 1
2 Pump 2
3 Pump 3
4 Pump 4
5 - > F Not used with PC 441
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I

81307060J
EN
9
Pump controller type ABS PC 441, Installation guide
Figure 8. Depending on the type of modem, connect according to the gure. Modem cable 43320588.
2 CONNECTION OF XYLEM PUMPS TO ABS PC 441
It is possible to connect Xylem pumps in parallel with ABS pumps.
For connection of sensors there are three cases depending on sensor congu-
ration in the pump.
Case A: CLS sensor or combination of sensors in series
In this case you have to use the analog inputs on the PC441. For advanced mo-
tor current monitoring or if out of analog inputs on the PC 441 use the CA 443
module for current monitoring. See the CA 44x Installation Guide.
If the sensors are not connected in series, connect the sensors to temperature
and leakage monitors respectively, see case B and C below. However the CLS
is always connected to an analog input of the PC 441.
ATTENTION ! In this case feeding power must not exceed 13.7 volts DC at any time.
Overvoltage can cause permanent damage to the pump controller. Ideal power
is between 11.5 and 13.7 Volts DC
Pay special attention to the polarity of the CLS. Faulty connection will cause
none or malfunction.
Select input type “ITT MiniCas Sim” on the PC 441 for this functionally.
OV
FLS/
FLS10
CLS
Thermo
switch
Analoge
input 2 - 5
V+
Ai(n)
Power input
12V DC
Xylem pump
ABS PC 441
CLS or
any combination of sensors like:
•CLS and FLS or
•CLS and Thermo switch or
•Thermo switch and FLS
•CLS and Thermo switch and FLS

81307060J
EN
Pump controller type ABS PC 441, Installation guide
10
Case B: Only temp sensors
Chose “Klixon” Thermo switch/PTC or “Pt100” mode in the settings menus for
CA 442
Case C: Only leakage sensors from the FLS series
Chose “Xylem” mode in the settings menus for CA 441.
Klixons/
Pt100
CAN T(n)+
T(n)-
Power input
DC
Xylem pump
ABS PC 441
ABS CA 442
CAN
FLS/
FLS10
CAN Di(n)+
Di(n)-
Power input
DC
Xylem pump
ABS PC 441
ABS CA 441
CAN

81307060J
EN
11
Pump controller type ABS PC 441, Installation guide
3 TECHNICAL DATA
3.1 Technical data PC 441
Ambient operation temperature -20 to +50 °C (-4 to +122 °F)
Ambient storage temperature -30 to +80 °C (-22 to +176 °F)
Degree of protection IP 20, NEMA: Type 1
Housing material PPO and PC
Flame rated V0 (E45329)
Pollution degree 2
Mounting DIN Rail 35 mm
Dimension HxWxD: 86 x 160 x 60 mm (3.39 x 6.30 x 2.36
inch)
Humidity 0-95 % RH non condensing
Power supply 9-34 VDC SELV or Class 2
Power consumption < 5.0 W (without digital output load)
Installation category CAT II
Digital outputs
Max load
8 DO. Positive logic. Sourcing from power
supply.
1A/output. Max total current for all 8 outputs
together is 4 A.
Digital inputs
Input resistance
Input voltage
16 DI. Positive logic
10 kohm
5-34 V . Trig level ~ 4 V
Max pulse rate digital in 13-16 500 Hz (pulse channels)
Analogue outputs
Max load
Resolution
Current limit
2 AO. 0/4-20 mA Sourcing from power supply
500 ohm@12 V, 1100 ohm@24 V
15 bits 0.5 uA
~22 mA
Analogue inputs
Input resistance
Resolution
5 AI. 0/4-20 mA
136 ohm. PTC protected
AI1 :15 bits (level sensor). AI2-5 : 10 bits
Communication ports 1 RS232 Service port
1 RS232 port for telemetry interface (modem)
1 USB2 Service port
Field Bus (to CA 511/CA 441 ………) 1 CAN Port . Max current load 350 mA
Max altitude 2000 m
Approval
3.2 Cleaning
How to clean the unit
Power o the unit. Only outside/front shall be cleaned by using a dry, soft cloth. A
good choice would be the microber type of cloth. Gently wipe the PC 441 front
in order not to scratch the overlay. If the dry cloth did not completely remove the
dirt, do not press harder in an attempt to scrub it o. If necessary, moisten the
cloth by adding a small amount of water with thin solution of mild detergent and
try again. Never use detergent with polish or solvent which can have an impact of
the plastic surface.

Declaration of conformity
Declaration of Conformity
As defined by:
EMC Directive 2014/30/EU, RoHS II Directive 2011/65/EU
EN EC Declaration of Conformity SV EG-försäkran om överensstämmelse
DE EG-Konformitätserklärung NO EUs Samsvarserklæring
FR Déclaration de Conformité CE DA EC-Overensstemmelseserklæring
NL EC-Overeenkomstigheidsverklaring FI EU-Vaatimustenmukaisuusvakuutus
ES Declaración de conrmidad CE ET EÜ Vastavuse deklaratsioon
PT Declaracão de conformidade CE PL Deklaracja zgodnosci WE
IT Dichiarazione di conformità CE CS Prohlášení o shodšĕ ES
EL Δήλωση εναρμόνισης EK SK EC Vyhlásenie o zhode
TR AT Uygunluk Beyanı HU EK Megfelelőségi nyilatkozat
Sulzer Pumps Sweden AB, Rökerigatan 20, SE-121 62 Johanneshov, Sweden
EN: Name and address of the person authorised to compile the technical file to the authorities on request:
DE: Name und Adresse der Person, die berechtigt ist, das technische Datenblatt den Behörden auf Anfrage zusammenzustellen:
FR: Nom et adresse de la personne autorisée pour générer le fichier technique auprès des autorités sur demande :
NL: Naam en adres van de persoon die geautoriseerd is voor het op verzoek samenstellen van het technisch bestand:
ES: Nombre y dirección de la persona autorizada para compilar a pedido el archivo técnico destinado a las autoridades:
PT: Nome e endereço da pessoa autorizada a compilar o ficheiro técnico para as autoridades, caso solicitado:
IT: Il nome e l’indirizzo della persona autorizzata a compilare la documentazione tecnica per le autorità dietro richiesta::
EL: Όνομα και διεύθυνση του ατόμου που είναι εξουσιοδοτημένο για τη σύνταξη του τεχνικού φακέλου προς τις αρχές επί τη απαιτήσει:
TR: Yetkili makamlara istek üzerine teknik dosyayı hazırlamaya yetkili olan kişinin adı ve adresi:
SV: Namn och adress på den person som är auktoriserad att utarbeta den tekniska dokumentsamlingen till myndigheterna:
NO: Navn og adresse på den personen som har tillatelse til å sette sammen den tekniske filen til myndighetene ved forespørsel:
DA: Navn og adresse på den person, der har tilladelse til at samle den tekniske dokumentation til myndighederne ved anmodning om dette:
FI: Viranomaisten vaatiessa teknisten tietojen lomaketta lomakkeen valtuutetun laatijan nimi ja osoite:
ET: Isiku nimi ja aadress, kelle pädevuses on koostada nõudmise korral ametiasutustele tehnilist dokumentatsiooni:
PL: Nazwisko i adres osoby upoważnionej do przygotowania dokumentacji technicznej w przypadku, gdy jest ona wymagana przez władze:
CS: Jméno a adresa osoby oprávnĕné na vyžádání ze strany úřadů vytvořit soubor technické dokumentace:
SK: Meno a adresa osoby oprávnenej na zostavenie technického súboru pre úrady na požiadanie:
HU: Asmens, įgalioto valdžios institucijoms pareikalavus sudaryti techninę bylą, vardas, pavardė ir adresas:
Frank Ennenbach, Director Product Safety and Regulations, Sulzer Management AG , Neuwiesenstrasse 15, 8401 Winterthur, Switzerland
EN: Declare under our sole responsibility that the products: SV: Försäkrar under eget ansvar att produkterna:
DE: Erklärt eigenverantwortlich dass die Produkte: NO: Erklærer på eget ansvar, at følgende produkter
FR: Déclarons sous notre seule responsabilité que les produits: DA: Erklærer på eget ansvar, at følgende produkter:
NL: Verklaren geheel onder eigen verantwoordelijkheid dat de produkten: FI: Vakuutamme yksinomaan omalla vastuullamme, että seuraavat tuotteet
ES: Declaramos bajo nuestra exclusiva responsabilidad que los productos: ET: Deklareerime ainuvastutajana, et tooted:
PT: Declaramos sob nossa unicia responsabilidade que los produtos: PL: Deklaruje z pelna odpowiedzialnoscia, ze urzadzenia typu:
IT: Dichiariamo sotto la nostra esclusiva responsabilità che i prodotti: CS: Prohlašuje na vlastní odpovědnost, že výrobky:
EL: Δηλώνουμε με αποκλειστική μας ευθύνη ότι τα προϊόντα: SK: Vyhlasujeme na našu zodpovednost’, že výrobky:
TR: Sorumluluk tamamen bize ait olarak beyan ederiz ki aşağıdaki ürünler: HU: Felelösségünk teljes tudatában kijelentjük, hogy a termékek:
Pump controller type ABS PC 441
EN: to which this declaration relates are in conformity with the following standards or other normative documents:
DE: auf die sich diese Erklärung bezieht, den folgenden und/oder anderen normativen Dokumenten entsprechen:
FR: auxquels se réfère cette déclaration sont conformes aux normes ou à d’autres documents normatifs:
NL: waarop deze verklaring betrekking heeft, in overeenstemming zijn met de volgende normen of andere normatieve documenten:
ES: objeto de esta declaración, están conformes con las siguientes normas u otros documentos normativos:
PT: aque se refere esta declaracáo está em conformidade com as Normas our outros documentos normativos:
IT: ai quali questa dichiarazione si riferisce sono conformi alla seguente norma o ad altri documenti normativi:
EL: τα οποία αφορά η παρούσα δήλωση είναι σύμφωνα με τα ακόλουθα πρότυπα ή άλλα κανονιστικά έγγραφα:
TR: bu beyanın konusunu oluşturmakta olup aşağıdaki standart ve diğer norm belgelerine uygundur:
SV: som omfattas av denna försäkran är i överensstämmelse med följande standarder eller andra regelgivande dokument:
NO: som dekkes av denne erklæringen, er i samsvar med følgende standarder eller andre normative dokumenter:
DA: som er omfattet af denne erklæring, er i overensstemmelse med følgende standarder eller andre normative dokumenter:
FI: joihin tämä vakuutus liitty, ovat seuraavien standardien sekä muiden sääntöämääräävien asiakirjojen mukaisia:
ET: mida käespöev deklaratsioon puudutab, on vastavuses järgmiste standardite ja muude normatiivdokumentidega:
PL: do których odnosi sie niniejsza deklaracja sa zgodne z nastepujacymi normami lub innymi dokumentami normatywnymi:
CS: na které se toto prohlášeni vztahuje, jsou v souladu s následujícími normami nebo jinými normativními dokumenty:
SK: na ktoré sa vz ahuje toto vyhlásenie, zodpovedajú nasledujúcim štandardom a iným záväzným dokumentom:
HU: amelyekre ez a nyilatkozat vonatkozik, megfelelnek a következőszabványokban és egyéb szabályozó dokumentumokban leírtaknak:
EMC: EN 61326-1:2013
Stockholm 30-03-2022
Per Askenström
Sulzer Pumps Sweden AB

UKCA Declaration of Conformity
Manufacturer: Sulzer Pump Solutions Ireland Ltd.
Address: Clonard Road, Wexford, Ireland
Declare under our sole responsibility that the product:
Pump controller type ABS PC 441
To which this declaration relates is in conformity with the following standards or other normative documents as
dened by:
Electromagnetic Compatibility Regulations 2016, S.I. 2016 No 1091
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012,
S.I. 2012 No 3133
BS EN 61326-1:2013
Brendan Sinnott
General Manager,
Sulzer Pump Solutions Ireland Ltd.
Wexford
30.03.2022

Sulzer Pump Solutions Ireland Ltd, Clonard Road, Wexford, Ireland
Tel +353 53 91 63 200, www.sulzer.com
Other manuals for ABS PC 441
1
Table of contents
Other Sulzer Controllers manuals