Sulzer ABS PC 441 User manual

Esc
8
tuv
7
pqrs
9
wxyz
0
*#
5
jkl
4
ghi
6
mno
2
abc
1
,.
3
def
0 A
1.30 m
0.50 m
1.50 m
0.55 m
1.70 m
0.60 m
1.90 m
0.65 m
352.5 A 353.8 A 354.1 A
1.55 m 1827 l/s
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
2013.08.21 05:56:19 Low level
980.3 l/s
m
P3 P4
P1 P2
3
0
07:25:58 07:28:10 07:30:26
0.15 kWh/m3
CA 511
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 441
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 442
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 443 CA 781
CAN
CA 622
RX/TX
ON-OFF
485-term.
0V -485 +485
678
A B
V+ H Shld L V-
1235 4
CAN Bus
www.sulzer.com
Pump controller type ABS PC 441
EN User guide SW 1.70
81307063I (02/2019)

81307063I
II
Copyright © 2019 Sulzer. All rights reserved.
This manual, as well as the software described in it, is furnished under license and may be used or
copied only in accordance with the terms of such license. The content of this manual is furnished
for informational use only, is subject to change without notice, and should not be construed as a
commitment by Sulzer. Sulzer assumes no responsibility or liability for any errors or inaccuracies
that may appear in this book.
Except as permitted by such license, no part of this publication may be reproduced, stored in a
retrieval system, or transmitted, in any form or by any means, electronic, mechanical, recording, or
otherwise, without the prior written permission of Sulzer.
Sulzer reserves the right to alter specications due to technical developments.

81307063I
III
CONTENTS
ABOUT THIS GUIDE, AUDIENCE AND CONCEPTS 1
1 OVERVIEW OF FUNCTIONS AND USAGE 3
1.1 Field bus status indicator ................................................. 4
1.2 CA 511 operator panel ................................................... 4
1.2.1 Status view ............................................................ 6
1.2.2 How to access the status view ............................................. 6
1.2.3 Pump alarms under status view ............................................ 7
1.2.4 Trend curve ............................................................ 7
2 CONFIGURE THE PC 441 9
2.1 Setgeneralconguration,system,IDandcommunicationsettings . . . . . . . . . . . . . . . . . 9
2.2 Congurethedigitalinputs,digitaloutputs,analoginputsandanalogoutputs ....... 11
2.3 Conguretheeldbusunitmodules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4 Congurethepumppitparameters ........................................ 14
2.5 Settings for pump 1 to pump 4 and their alarms ............................... 16
2.6 Common P1 – P4 ...................................................... 18
2.7 Set log settings and events............................................... 19
2.8 IfusingCA622;setupcommunicationstosurroundingunitsVFD,softstartersand
energymeters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.9 Setupcleaner,mixerordrain(ifused) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3 DETAILED DESCRIPTION OF THE FUNCTIONS 21
3.1 Pump controller and/or monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.2 Pumpcapacityandin/outowofthepit ..................................... 22
3.2.1 Pit shape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.2.2 Pump curve........................................................... 32
3.2.3 Systemcurve ......................................................... 33
3.2.4 Energyeciency:kWh/volumeunit ........................................ 34
3.3 Overowowcalculation ................................................ 35
3.3.1 Howtocalculateoverowsbyusingconstantsandexponents ................... 36
3.4 Pump alternation....................................................... 36
3.4.1 Maxnumberofpumpsrunning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.5 Pump reversing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.5.1 Othersettingsregardingpumpreversing:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.6 Speedcontrolledpumps(VFD). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.6.1 CongurePC441forVFDpump(s) ........................................ 40
3.6.2 PIDsettings........................................................... 41
3.6.3 Variablefrequencydriveautoreset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4 FURTHER EXPLANATIONS ABOUT SOME DIGITAL/ANALOG OUTPUT/INPUT
TYPES 43
4.1 Logic IO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.2 Digitaloutputtype:datareg.setpoint ...................................... 44
4.3 Analogoutputtype:dataregister .......................................... 45
4.4 Mixerprestart ......................................................... 45
4.5 Mixeranddrainpumpblocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.6 Digitalout:externalresetalert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.7 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.7.1 Com port (screw terminals 48 – 52) ........................................ 46
4.7.2 Serviceport(9-polsD-Subinthefront) ..................................... 46
4.7.3 USBport(USBtypeBinthefront) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.7.4 Modem .............................................................. 46
4.7.5 Com Echo PC 441 ..................................................... 47

81307063I
IV
4.7.6 Alarms............................................................... 48
4.8 AquaProg ............................................................ 48
4.8.1 How to set up AquaProg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.9 Cross reference table ................................................... 49
5 SETTINGS 51
5.1 Select language ....................................................... 51
5.2 Overview of settings .................................................... 51
5.3 Systemsettings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.4 Pump pit settings ...................................................... 54
5.5 Pump 1 to 4 settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.6 Commonsettingsforpump1,2,3and4.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.7 SettingsforPIDcontroller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.8 Settingsformixer ...................................................... 65
5.9 Drainpump ........................................................... 65
5.10 Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.11 Analog logging ........................................................ 66
5.12 Settings for digital inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.13 Settings for digital outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.14 Settings for analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.15 Settings for analog outputs ............................................... 69
5.16 Settings for pulse channels............................................... 71
5.17 Settings for trend curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.18 Communication settings ................................................. 72
5.19 Settingsforeldbusmodules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.20 Common settings ...................................................... 77

81307063I
EN
1
ABOUTTHISGUIDE,AUDIENCEANDCONCEPTS
This guide describes the pump controller PC 441 and the operator panel CA 511. The pump controllers can ei-
therbeusedstand-aloneorcommunicateallvaluesandconditionstoacentralScadasystemorawebbased
alarmandmonitoringsolutionlikeAquaWebfromSulzer.
Installation guide There is a separate document Installation guidethatdescribeshowtophysicallyinstallthepumpcontroller
(printeddocumentintheinstallationpackage,andalsoaPDFonSulzerweb).
Audience ThisguideisintendedforsystemadministratorsandoperatorsofPC441pumpcontrollerwithoperatorpanel
CA 511 or PC program AquaProg.
Prerequisites Thisguideassumesthatyoualreadyareacquaintedwiththosepumpsyouaresettocontrolandhavethesen-
sors and operator panel CA 511 connected to PC 441.
Thesystemadministratormustalsoknowanddecideonthefollowing:
1. Thepumpcontrollercaneitheruseananaloglevel-sensor,whichmeasuresthewaterlevelinthepit,for
precisecontroloverstartandstoplevels,oritcanusesimpleoatswitchesplacedatstartandstoplevels.
• Floatswitchescanbeusedinadditiontoananaloglevel-sensor,asabackup,andasanad-
ditional alarm input.
• Ananaloglevel-sensorhasseveraladvantagesoveroatswitches:itismorerobust(cannotget
stuckorbemechanicallyjammed);itismoreaccurate;itismoreexible(youcaneasilychange
thestartandstoplevels);youcangetreadingsofthewaterlevelinthepit,theinow,overow
andthepumpcapacity;youcanoptimisethepumpperformanceinvariousways,includingexer-
cising,alternativestoplevels,taricontroletc.
• Itisalsopossibletoemployanalternativestoplevel,usuallyalowerlevelthannormal,thatis
eectiveonceafteranumberofpumpstarts.Thiscanbeusefulifitisdesirableto“completely”
emptythepitonceinawhile.
2. Youneedtoknowifthepump(s)shouldbeexercisedincaseoflongidleperiods.Iftheinstallationhastwo
pumpsormore,youneedtodecideifthepumpsshouldalternate.
3. Iftheelectricityhasdailyvaryingtaris,youmustknowthetimesofhigh/lowtaris.
4. Youmustknowhowoverowwillbemeasured:ifitwillbemeasuredusingbothanoverowdetector(tode-
tectthestartoftheoverow)andalevelsensor(tomeasuretheactualow),youmustknowtheparameters
(exponentsandconstants)tobeenteredassettingssothattheoverowcanbeaccuratelymeasuredbya
calculation in PC 441.
5. Youneedtoknowwhichalarmclass,A-alarmorB-alarm(seeGlossaryandconventions),toassigneach
alarm.
Reading guide Forinstallation,seetheseparatedocumentsInstallation guidesforrespectiveproduct,PC441,CA511,
CA44x,CA622andCA781,whichcanbefoundonSulzerhomepage.Beforeyoumakeanysettings,oruse
thecontrolpanel,readchapter 1 Overview of functions and usage—itdescribesthegeneralfunctionalityand
the meaning and usage of the controls on the panel.
Thesystemadministratormustensurethatallsettingsaccordingtochapter 5 Settingsaresuitableforyour
application.
NOTE! The default settings are listed in the Installation guide.

81307063I
EN
2
Text appearing and declaration in this guide
TextinitalicisadescriptionoftextinthedisplayofCA511oradescriptionhowyoundyourwaythroughthe
menusbykeystrokes.Textsinbold,ishowyouhavetodoachangeofthesettingsintheCA511menu.
Most settings in chapter 5onlyapplytothesystemadministrator,butthefollowingalsoapplytothosewhoonly
operatethecontroller:languageselection,dateandtimesettings,units,backlighttime-out,buzzer,operator
passcode,start/stoplevels.
Glossary and conventions
Todesignateamenuiteminahierarchy,ananglebracketisusedtoseparatethelevels.Example:Settings
>SystemmeansthemenuitemyoureachbyrstchoosingthemenuitemSettings,whichhasanumberof
submenus,whereyouchoosethemenuitemSystem.
Textinblueindicatesahypertextlink.Ifyoureadthisdocumentonacomputer,youcanclickontheitem,
whichwilltakeyoutothelinkdestination.
Pump exercising: Long idle periods in a corrosive contaminated environment are not good for pumps. As a
countermeasure,theycanbe“exercised”atregularintervals,whichwillreducecorrosionandotherdetrimental
eects.
Cos j:Cosine of the phase angle jbetween the motor current and the voltage.
Alarm class: The alarm class can be either A-alarm or B-alarm. A-alarms are those that require immediate ac-
tion,sooperationalstaintheeldshouldbealertedregardlessofthetimeofday.B-alarmsarelessimpor-
tant,butshouldbetakencareofduringnormalworkhours.
Digital in means a signal that is either on or o (high or low),wherehighisanythingbetween5and24volts
DC,andlowisanythingbelow2volts.
Digital output An output signal that is either on or o.
At onconditionoutputcurrentissourcedfromthepowersupplyandtheoutputishigh(~V+).Ato condition
the output is low (no output current).
Aretypicallyconnectedtorelays.
Analog outputs An output signal in the range 4-20 mA or 0-20 mA.
Sourcedfrompowersupply.
Analog inputsareforsensors,andtheseinputssensecurrentintherange4-20mAor0-20mA.

81307063I
EN
3
1 OVERVIEWOFFUNCTIONSANDUSAGE
PC 441 is designed to control 1-4 pumps. It can operate a pump station stand alone and/ or as a pump monitor.
ForcongurationandoperatorinteractionthegraphicoperatorpanelCA511maybeused.WiththeAquaProg
software(evaluationversionavailable)aPCcanbeusedforcongurationandbackupofsettings.Byadding
amodem,afullremotealarmandmonitoringsolutioncanbeachievedwithjustanAquaWebrentalcontract
orbymostSCADAsystems.Optionalmonitoringmodulesforleakage,temperatureandelectricalparameters
givesahighlyscalablesolutionforoptimalcostandperformance.
ThePC441canworkstandaloneortogetherwithextensionmodules,buttheextensionmodulescannotwork
without the PC 441.
.
As a pump monitoring devicethePC441oersthemarketacombinedstandardsolutionforsubmersible
pump and pump station surveillance. Can be set up for full-scale monitoring of one or up to four submersible
pumps plus ancillaries.
As a pump controllerthePC441controlsthestart/stopofthepumps,oeringastandardizedsolutionfor
sewagepumpstationswithuptofourpumps.Avarietyofsolutionsfromstandardon/ocontroluptoad-
vancedVFDsupportincludingpumpcapacitycalculation.
As a combined control and monitoring devicethePC441canbeoeredasasolutionsupportingboththe
areas above in a single unit.
Modules:
1. CA 511 - Graphical operator interface
Max 1 of this unit per system
2. CA 622 - RS 485 Communication interface module
Max 1 of this unit per system
3. PC 441 - Pump monitoring and/or controller
4.CA781-Analoganddigitaloutexpansionmodule
Max 1 of this unit per system
5. CA 441 - Moisture monitoring module
Max 4 of this unit per system
6. CA 442 - Temperature monitoring module
Max 6 of this unit per system
7.CA443-Motorandsupplypowermonitoringmodule
Max 5 of this unit per system
PC 441 is the heart
ofthesystem!Other
modules are optional.
1.
2. 3. 4.
5. 6. 7.

81307063I
EN
4
8.Sulzerwirelessmodem
Max 1 unit per system
Thebaseunit,PC441,communicateswiththeextensionmodulesviaCANcommunication.
Seetheinstallationguidehowtoconnecttheextensionmodules.Afullyextendedsystemcanlooklikethis:
8.
Modem
Figure 1-1
RS-232 port for a computer
(service port or com echo see 3.8.5)
Power indicator
Field bus indicator
Alarm indicator
USB (service port)
Agreenlampattheveryleftindicatesthattheunitispowered(eitherbatteryormains).
Theredalarmindicatorwillblinkwheneverthereisanunacknowledgedalarm.
1.1 Field bus status indicator
Pumpcontroller,operatorpanelandmonitoringmodulescommunicatesviaaCANbus.
Fixedgreenlight=connectedOK
Flashinggreenlight=searchingformodules
Flashingredlight=InvalidIDsetonmodule
1.2 CA 511 operator panel
Younavigatethemenusbythearrowbuttons.PresseithertheUp or Down arrow button to switch to the menu
view.YouconrmanoperationwiththeEnterbutton,oracknowledgeanalarm.PressingtheEscape button
will cancel the current operation.
Figure 1-2
0 A
1.30 m
0.50 m
1.50 m
0.55 m
1.70 m
0.60 m
1.90 m
0.65 m
352.5 A 353.8 A 354.1 A
1.55 m
1827 l/s
3.8 bar
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
2019.01.23 05:56:19 Low level
980.3 l/s
m
P3 P4
P1 P2
3
0
07:25:58 07:28:10 07:30:26
0.15 kWh/m3
Height of water in pit
Overflow detector
Inward flow to pit
Trend curve
Shows operation
(animated)
Height of water
(animated)
High-level float sensor
Low-level float sensor
Outward flow from pit
Back-pressure
Current consumption for pump
Total pump efficiency
Start / Stop levels
Thedisplayanditsinformationeldsinthedefaulttop-levelview.
Upto4pumpsvia16Din,16Dout,5Ain,4Aout
3 moisture and 5 temperature inputs per pump
Temp L2 & L3
-> CA 511
Station P1 P2 P3 P4 P1 P3
P2 P4

81307063I
EN
5
Thedefault(top-level)viewofthedisplaydynamicallyshowstheoperatingstatusofthepumpsandconditions
in the pit. Figure 1-2showsthesymbolsandexplainstheirmeanings.Theunitwillalwaysreverttothisview
after10minutesofinactivityinanyotherview(suchasshowingmenus).
WhenPC441issettouselessthan4pumps,theviewadaptstoshowactualnumberofpumps.
Power and alarm ThetwoleftmostsymbolsontheCA511panelareforpowerandalarmindication:
indicator
• Buttons at bottom gives direct access to the most common
menus.
• Bottomrightmost“Ackn.”.Buttonwillacknowledgethemostcur-
rentalarmdisplayedonstatusrowattopofdisplay.
• Right buttons will start or stop the pump. (Toggle actual state.)
Bykeepingbuttonpressed,forcedpumprunbelowstoplevelis
possible.
Right-hand buttons Thebuttonstothelowerrightofthedisplayhavethefollowingfunctions:
• To leave the overview image of the pump pit and go into the
menus,presseithertheUp or Down arrow button.
• Yougo“into”amenuitembypressingeithertheRight/Forward
button or the Enter button.
• Youconrm(orperform/execute)anoperationwiththeEnter
button ( ).
• Toexitthecurrentoperation,orleavethemenusandgobackto
overviewimageofthepumppit,presstheEscape button.
Main menu Figure1-3showstheMainmenu,whichyoureachfromtheoverviewimagebypressingeithertheUp or Down
arroworshortcutkeyMainbelowdisplay:
Main Menu Manual Control
Manual Control Pump 1
Alarm List Pump 2
Show Status Pump 3
Settings Pump 4
Select Language Mixer
Drain Pump
Cleaner
Remote Blocking
Esc
Figure 1-3 Thetop-levelmenuofthePC441graphicaldisplay.
Howtoselectlanguageandmakeallsettings(menuitemsSelect language and Settings) are described in
chapter 5 Settings.
How to enter values Press Enter to enable editing of a value.
and strings
0 A
1.30 m
0.50 m
1.50 m
0.55 m
1.70 m
0.60 m
1.90 m
0.65 m
352.5 A 353.8 A 354.1 A
1.55 m 1827 l/s
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
2013.08.21 05:56:19 Low level
980.3 l/s
m
P3 P4
P1 P2
3
0
07:25:58 07:28:10 07:30:26
0.15 kWh/m3
Esc
8
tuv
7
pqrs
9
wxyz
0
*#
5
jkl
4
ghi
6
mno
2
abc
1
,.
3
def
Use the Left/Right buttons to choose the insertion point.
Use the Up/Down buttons to increase/decrease a value or letter.
Values and strings can also be altered through the alphanumeric
keyboard.
Anasterisk(*)gives=adot(.).
Finishtheeditingbypressingenter.
Esc
8
tuv
7
pqrs
9
wxyz
0
*#
5
jkl
4
ghi
6
mno
2
abc
1
,.
3
def
• GreenlightisthepowerLED.
• Theredalarmindicatorasheswheneverthereisanunacknowledgedalarm,andthedisplaytells
youthetypeofthealarm.Whenthealarmisacknowledged,thelightturnssteadyred,andremains
lituntiltherearenoactivealarms,thisfunctionsthesameasthePC441alarmindicatorLED.
Direct functions, Thebuttonsatthebottomandtotherightofthedisplayhavethefollowingfunctions:
bottom and right
displays

81307063I
EN
6
Passcodes Therearethreesecuritylevels:
1. Dailyoperations,suchasacknowledginganalarmorstoppingapump,donotrequireanypasscodeor
authorization.
2. Operationalsettings,suchassettingthestartorstoplevelsforthepump,requireapasscodeatthelevelof
Operator;
3. Congurationsettingsthataectthebasicfunctionalityoraccess,suchasthetypeoflevelsensor,require
a passcode at the level of System.
Thefactorydefaultpasscodesare1and2respectively,butthecodescanbechangedunderthemenuitem
Settings > System.WheneverapasscodeforOperatorisrequested,youmaysupplyeitherthepasscodefor
OperatororSystem.
Personal alarm,
and how to reset it Whenthepumpstationismanned,apersonalalarmcanbeissuedifthemaintenancepersonhasn’tshown
activitywithinacertainperiodoftime.Fordetailsaboutsettingsrelatedtothis,seesection5.3Systemset-
tings (assigning Alarm type, Alarm delay and Max time to reset),section 5.12 Settings for digital inputs (as-
signing Sta in stationtoaDigitalin),andsection 5.13 Settings for digital outputs (assigning Personal alarm
alert to a digital output).
AfterthespeciedMax time to reset,theassignedoutputisactivatedsoavisualoraudiosignalcanalert
the maintenance person that the alarm timer must be reset. If the alarm timer is not reset within Alarm delay,a
personal alarm is sent out.
Toresetthetimer,justpushanybuttononthecontrolpanel.
1.2 .1 Status view
One of the useful functions in PC 441 is Status view. In the status view shows Pump running time, Number of
starts, Capacity and Energy consumption.InthosecasesthereCA441,CA442andCA443areinthesystem,
youwillbeabletoseeTemperaturesinthedierentbearings,monitoringtheVibrations,Power absorbed and
Motor current.YouwillalsoseethepowersupplyvoltageL1 – L3iftheisaCA443inthesystem.Allthepump
alarms will show up here in the graphic.
Pump Running Time
Number of Pump Starts
Pump Capacity
Energy Consumption
Temp. Upper Bearing
Temp. Stator
Temp. Lower Bearing
Vibrations
Power absorbed
Motor Current
L1-2 406 V L2-3 406 V
588 h
2940
609 l/s
115248 kWh
68 ˚C
79 ˚C
70 ˚C
2.7 mm/s
196 kW
353.2 A
L3-1 401 V
Total
P1
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
2011.06.23 05:56:19 NO UNACK ALARMS
Figure 1-4 Status view
1.2.2 How to access the status view
Statusviewiseasytobeaccessedbypushingthe“Status”belowthedisplay,andthen“Pump 1”–“Pump 4”
ontherightsideofthedisplay.Seepicturebelow.
Pump Running Time
Number of Pump Starts
Pump Capacity
Energy Consumption
Temp. Upper Bearing
Temp. Stator
Temp. Lower Bearing
Vibrations
Power absorbed
Motor Current
L1-2 406 V L2-3 406 V
588 h
2940
609 l/s
115248 kWh
68 ˚C
79 ˚C
70 ˚C
2.7 mm/s
196 kW
353.2 A
L3-1 401 V
Total
P1
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
2011.06.23 05:56:19 NO UNACK ALARMS
2
1
Figure 1-5 How to access Status view

81307063I
EN
7
It’spossibletousetheleftandrightarrowkeysatthenumeralkey
board to step to the other pumps.
Use up and down arrowstostepbetweendays.
Upto7daysbackcanbedisplayed.
LeavetheStatusviewbyESC.
1.2.3 Pump alarms under status view
If the Field bus modules CA 441 and CA 442areattachedtothePC441andpumpalarmsappears,when
under Status viewyouwillbeabletoseeanindicationwherethefaultisphysicallylocatedinthepump.
Motor protector Pump
or other general Pump
failures from PC 441
DI 2 Electric Area
DI 3 Motor Housing
T3 Hi Temp Lo. Bearing
T1 Hi Temp Stator /
T4 Hi Temp Stator
(T1 & T4 share the same
alarm numbers)
Stator temperature L2 - L3 with
additional CA 442
T2 Hi Temp Up. Bearing
DI 1 Oil Chamber /
or Leakage Pump
from PC 441
Figure 1-6 Pump sensor indications in Status view
Esc
8
tuv
7
pqrs
9
wxyz
0
*#
5
jkl
4
ghi
6
mno
2
abc
1
,.
3
def
How to access Trend curve
1.2.4 Trend curve
Another useful function in PC 441 is Trend curve.Hereyoucangetanoverviewofpitlevel,inowandoutow
oranyotherparameteryouchooseovertime.Fourdierenttrendcurvescanbedisplayedatthesametime.
Thereisalsoapossibilitytoadjusttheintervalsamplingforthecurves.Defaultsettingis1samplepersecond.
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
P3 P4
P1 P2
m
l/s
l/s
2
300
400
10
0
0
0
0
12:42:24 12:44:24 12:46:24
Figure 1-7 Trend curve

81307063I
EN
8
To get a presentation of the curve titles in the menu Trend curve,thenpushEnterthenyouhavetheTrend
curvepictureonthedisplay,thepicturewillappearwiththedescriptionasbelow:
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
P3 P4
P1 P2
m
l/s
l/s
2
300
400
10
0
0
0
0
12:42:24 12:44:24 12:46:24
[Pit Level]
[Pit Inflow]
[Outflow]
[Closed]
Figure 1-8 DescriptionofthecurvesinTrend curve
The presentation will disappear after a few seconds.
One screen of Trend cur ves covers 300 samplings and that corresponds to 5 minutes in default settings of 1
second.

81307063I
EN
9
2 CONFIGURETHEPC441
Overview of settings
Eachstationhasanuniquecongurationsetup,buttheprocedureissimilartosetupthese.Thischapterwill
guideyouthroughthebasicsettingsinPC441.Note:Thisdoesnotcoverallcongurations,youmustconsider
yourprerequisites.
The menu item Settingshas21submenuswithmanysettingsthatneedtobeenteredbythesystemadmin-
istrator(althoughtheyallhavesensibledefaultvalues).Thefollowing9notesbelowarearecommended
procedure to setup PC 441.
2.1. Setgeneralconguration,system-andcommunicationsettings
2.2. ConguredesignatedIOfunctionsatDI,DO,AIandAOaccordingtotheelectricalwiringdrawing
2.3. CongureI/Omodules,CA441,CA442,CA443,CA622,CA511andCA781
2.4. Pump pit parameters and alarms
2.5. Set pump 1 - 4 settings and their alarms
2.6. Common P1-P4
2.7. Set log settings and events
2.8. Setupcommunicationstosurroundingunits(VFD,softstartersand/orenergymeters(ifused)
2.9. Setupcleaner,mixerordrain(ifused)
Each of the 21 submenus under settings are described in separate tables in section 5.
To enter the settings area:
Press down arrowonceandyouareinthemenus,continuetopressdownarrowtoSettings,pressEnter.
ThemajorityofsettingsrequireapasscodeforSystemexceptsomesettingsunderthesub-menuSystem and
the start/stop levels under submenus Pump 1-4whichonlyrequireapasscodeforOperator.
AllthesettingscanbedonelocallyformthemenusorbyAquaProg.TheadvantageofAquaProgisyoucan
savethecongurationatyourPCandeasilyrestorethecontrollerifneeded.
2.1 Setgeneralconguration,system,IDandcommunicationsettings
SetupthebasicsystemparametersandcommunicationparametersbyusingthemenusinCA511:
Basic system parameters
• Fromthebasescreen,pressthekeyforSettingunderthedisplay,pressEntertwiceandgivethe
password (default 2).Scrollontheleftpartofthescreentoyourlanguagebyusingtheup/down
arrowkeys,pressEnteratyourchoice.
• UsethedownarrowkeytoStation application and press Enter. Select Pump controller or Pump
monitor byusingtheup/down arrow in the left part of the screen, pressEnteratyourchoice.Use
thedownarrowkeytoMain graphics and choose the base screen (Pump pit statusoranypump)
• UsethedownarrowkeytoSelect units,metricorUSunits,pressEnteratyourchoice.
• UsethedownarrowkeytoDate format,pressEnter.Chooseyourdateformat.
• UsethedownarrowkeytoSet date,Set time,andallothersettingsunderthisparameter.
• Set System alarmsaccordingtoyourpreferences.

81307063I
EN
10
Communication parameters
• Fromthebasescreen,pressthekeyforSettingunderthedisplay,scrolldownbyusingthedownar-
rowkeytoCommunication and press Enter. Press enter again and select Protocol (Modbus/Comli/
ModbusTCP)andpressEnteratyourchoice.Pressleftarrowkeytogobacktotheleftpartofthe
screen. Use the down arrow to Com port and press Enter. Select Station ID,PressEnter.Typein
yourStation IDbyusingnumeralkeysorup/downarrowkeys,requiredforAquaWeboranyother
surveillancesystem.SelectBaudrate,Parity and Handshake.Usetheleftarrowkeytogobackto
the left part of the screen and select Service port,pressEnter.SelectBaudrate for the service port.
• Selectmodemtype
Nowit’spossibletoconnecttoAquaProgthroughserviceportorUSB.
In AquaProg:
Figure 2-2 Communication
Figure 2-1 Systemsettings

81307063I
EN
11
2.2 Congurethedigitalinputs,digitaloutputs,analoginputsandanalog
outputs
SetdesignatedIO-functionsaccordingtotheelectricalwiringdrawing.Seeyourdrawingsofthestation.
Under Settings, Digital inputs; choose for each input according to table 2-1 and Digital outputs to table 2-2.
Digital outputs
OFF
Pump control
Reset motor protector
Pump fail
Too many pumps blocked
One pump fail
Master reset motor protector
Mixer control
Reset motor protector Mixer
Drain pump control
Reset motor protector Drain
Cleaner control
Modem control
Remote control
Personnel alarm
High level
Alarm alert
Not ackn. A-alarm
Not ackn. A/B-alarm
Active A-alarm
Active A/B-alarm
Pump reversing
Active B-alarm
Logic IO
Data register set point
Extern reset alert
Under Settings, Analog inputs,chooseforeachinputaccordingtotable2-3.Analoginput1isxedtoleveland
cannot be changed.
Table 2-3: Table 2-4:
Analog input 2-5
OFF
Motor current P1-P4
Back-pressure
Vibrations
Free choice
Vibrations P1-P4
Xylem MiniCas Sim P1-P4
Outow meter
Note
Analog1ispredenedtolevelsensor
and cannot be changed.
Analog outputs
OFF
Pit level
Pit inow
Pit outow
Pit overow
Pulse channel 1
Pulse channel 2
Pulse channel 3
Pulse channel 4
PID controller
Data register
Table 2-1: Table 2-2:
Digital inputs
OFF
Pump run indication
Manual pump start
Pump not in auto
Start oat
Pump failure
Motor protector
High temperature
Leakage
Stop oat P1-P4
Low level oat
Overow sensor
High level oat
Drain pump oat
Run indicator Drain pump
Motor protector Drain pump
Run indicator Mixer
Motor protector Mixer
Staff in station
Alarm reset
Power fail
DI pulse channel 1-4
Block PID controller
Alarm input
Mixer block + Alarm input
Drain pump block + Alarm input
Block remote data

81307063I
EN
12
In AquaProg:
Figure 2-3 Analog and digital inputs / outputs
2.3 Conguretheeldbusunitmodules
AlltheextensionmodulestoPC441areoptional.ThecommunicationisdonebytheCAN-bus.SeeInstal-
lation guide CA 441, CA 442, CA 443(P/N:81307058)onSulzerhomepageformoredetailinformationto
setup Leakage, Temperature and Power monitors.InstallationguidestoCA511(P/N81307061),CA622
(P/N81307133)andCA781(P/N81307132)canalsobefoundatSulzerhomepage.
CA 441 Leakage module
AsystemwithPC441cancontainuptofourCA441modules.
OneCA441modulecanmonitorleakageinoneorfourpumps
dependingonthesettingoftheaddressknobonthefrontof
themodule,seeInstallation guide CA 441, CA 442, CA 443
(P/N:81307058)formoreinformation.Ifusingonemoduletofour
pumps,thereisoneinputforeachpump.IfusingoneCA441
moduleforeachpump,therearefourinputstoeachpump.
Inthesettings,youmustspecifythatthemodule(s)areconnected
andwhichtypeofsensortypeyourpumpshave.DefaultisABS
standard and can be changed to Xylem (ITT Flygt).
CA 442 Temperature module
PC441supportsuptosixunitsofCA442.OneCA442module
can monitor temperatures in one or four pumps depending on the
settingoftheaddressknobonthefrontofthemodule,seeInstal-
lation guide CA 441, CA 442, CA 443(P/N:81307058)formore
information.Ifusingonemoduletofourpumps,thereisoneinput
foreachpump.IfusingoneCA442moduleforeachpump,there
arefourinputstoeachpump.Inthesettings,youmustspecify
sensortypes(Klixon/Pt100/PTC).
EachmodulefromCA442-1(“-1”referstotheaddressonthe
knob)toCA442-4hasa4-20mAVibrationinput,oneforeach
pump. The vibration inputs are disabled in units CA 442-5 and
CA 442-6.
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 441
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 442
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 443
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 441
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 442
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 443

81307063I
EN
13
CA 443 Power monitor module
PC441supportsuptoveCA443modules,onemoduleforeach
pumpandoneforwholesystem.CA443modulescannotbe
usedtogetherwithVFD.TheCA443modulesmustbeconnected
before pump contactor so the inputs L1-L3 never get powerless.
Iftheinputsgetpowerless,thephasealarmgoon,andthepump
willnotstart,seeInstallation guide CA 441, CA 442, CA 443
(P/N:81307058)formoreinformation.
CA 511 Graphical operator interface panel
PC 441 supports one CA 511. It is not possible to use one CA 511
toseveralPC441s.CA511isconnectedtoPC441viaCAN-bus
andhasaCAN-busterminationontheback.Thermwarever-
sioninCA511mustconformtotheversioninPC441.Alwaysuse
thelatestrmwaretoensurefullfunctionality.
CA 781 Output expansion module
CA781isamodulewhichgivesyoueightextradigitaloutputs
andtwoextraanalogoutputs.CA781modulemustbepowered
from the same source as PC 441 and cannot be powered from
theCAN-busbecauseofitshigherpowerconsumption.PC441
supports one CA 781 module. See Installation and user guide
(P/N81307123)onSulzerhomepageformoreinformation.
CA 622 RS 485 communication module
PC441cancommunicatedirectlytoVFDs,energymetersand
softstartersviaCA622module.CA622actsasModbusmaster,
communicating with attached Modbus slave devices. See the In-
stallation and user guide(P/N81307133)onSulzerhomepagefor
moreinformationandwhichVFD,energymetersandsoftstarters
PC441andCA622support.Ifmissingyourmodel-contactCon-
trol&MonitoringatSulzerandwemightbeabletoaddthenew
model.PC441supportoneCA622inthesystem.
WhenusingCA622inthesystem,thevaluesfrommany
parameterscanbereadoutbytheRS485busdirectfromVFD/
softstartersorenergymetersandstoredinthecontroller.These
values can also be logged. PC 441 together with CA 622 can also
controltheon/o,speedandreversingofthepumps.Consult
theInstallationanduserguideCA622(P/N81307133)onSulzer
homepageformoreinformationaboutwhichVFD/softstarters/
energymetersPC441andCA622supports.
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 441
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 442
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CA 443
Esc
8
tuv
7
pqrs
9
wxyz
0
*#
5
jkl
4
ghi
6
mno
2
abc
1
,.
3
def
0 A
1.30 m
0.50 m
1.50 m
0.55 m
1.70 m
0.60 m
1.90 m
0.65 m
352.5 A 353.8 A 354.1 A
1.55 m 1827 l/s
MAIN STATUS SETTING TREND ALARM ACKN.
PUMP 4
PUMP 3
PUMP 2
PUMP 1
2013.08.21 05:56:19 Low level
980.3 l/s
m
P3 P4
P1 P2
3
0
07:25:58 07:28:10 07:30:26
0.15 kWh/m3
CA 511
CA 781
CAN
CA 622
RX/TX
ON-OFF
485-term.
0V -485 +485
678
A B
V+ H Shld L V-
1235 4
CAN Bus

81307063I
EN
14
2.4 Congurethepumppitparameters
Table 2-5:
Pit settings
Level sensor type
Max number of pump running
Min time between relay change
Alternation
Alternative stop level
Start/stop on fast change
Station ow*
Calculation of pump capacity*
Overow
Backup running
Pit alarms
Pump blocking
Level sensor check
Tariff control
Level above sea
* MUST for accurate pump capacity calculation
Level sensor type (required parameter, default level sensor)
Analogsensororstart/stopoats.Analogsensorisrecommendedifyouwanttotrackthecapacityofthe
pumps and pumping volume.
Max number of pumps running (optional parameter)
Ifyourpipesystemcannothandletoohighows/pressureoryourpowergridhaslimitations,reducenumberof
pumps running at the same time. See section 3.4.1
Alternation (optional parameter)
Normalorasymmetrical
Normal:Thepumpsstartinsequencefrom1-4.Thereisalwaysonepumpstartattherst(lowest)startlevel.
Asymmetrical:Thepumpsaredividedintwogroupsthereonegroupisworkingmorefrequentlythantheother
group. See also section 3.4
Alternative stop level (optional parameter)
Thisfunctionistoaidreductionofsedimentsinthepitandavoidingoatingcrust
Start/stop on fast change (optional parameter)
Forexample:Ifthepumpstationispumpingclearwaterandaheavyrainllsthepitveryfast,thepumpcan
start before the level reach the start level.
Station ow (recommended parameters)
Under Meas. parameters set the Inow calculation=ONandyourpitshape,alsothefunctionEmptying or
Filling the pit must be set. System curve at duty pointisusedifthereisn’tanyOutlet pressure sensor.
Recommended is to setup the Pit area under Station ow.That’sbecausethepumpcalculationsshallpreform
as accurate as possible. This are bound to Energy calculation,Pump capacity and Outlet calculations. Best
accuracyofpumpcapacitycalculationsandpumpedvolumeiswhenanOutlet pressure sensor is used.
See section 3.2 for more information.
Calculation of pump capacity (recommended parameter)
Recommended to set Calculation=ON.Thelevelmustbeinthespanofminimumandmaximumduringthe
calculations.Makesurethatthealltimestogetherinstart delay/calculation time/stop delay in total must be in
one and the same pump sequence. See section 3.2 and forward.

81307063I
EN
15
Overow (optional parameter)
Overowcanbedetectedbyanoverowdetector(MD137)orbythecertainlevel.Seemoreinformationabout
overowin section 3.3.
Backup running (optional parameter)
BackuprunningstartwhenaHigh-level oatgetsactivated.Youcanspecifywhichpumpsshallparticipatein
backuprun,andhowlongthepumpshallrun.
Pit alarms (some parameters are recommended)
There are several alarms which can be set under Pit alarms.EachalarmiscongurabletobeA-orB-alarms.
Consultyourdrawingsandverifywhichareimportantforyourinstallation.
Pump blocking (optional parameter)
Thepumpcanbeblockedonremote.Thereisatimeoutwhichreleasestheblockingafteracertaintime.
BlockingonLow level oat and/or High pressure can be set here.
Level sensor check (optional parameter)
Level sensor checkItispossibletocheckthelevelsensorreadingcomparedtotheinstalledoats.Seethe
settings under Level sensorchecksetthisup.
Tari control (optional parameter)
Thisfunctionistoreduceenergyconsumptioninhoursofhighcostofenergy.Youcansetthisupforseparate
daysintheweek.
Level above sea (optional parameter)
Ifyoutypeinavaluehere,thisvaluewillbeaddedinthepitlevelbutnotaectthestart/stoplevels.
In AquaProg:
Figure 2-4 Pump pit settings

81307063I
EN
16
2.5 Settings for pump 1 to pump 4 and their alarms
Hereyoucangivethepumpatagname(max20characters).InstalledpumpsmusthaveRelay control
pump=YES,otherwisethepumpwillnotshowupinCA511graphics.Alternately;ifpump3andpump4are
not installed; Relay control pump=NO that pump disappears from the graphics.
Importantparametertosetupforeachpump:
Typeofpump(xedorVFD)
Runningindication(digitalinput,motorcurrentoreldbusmoduleCA622)
Start/stop level
Pump alarms
Pump curve
Optionalparameters:
Time settings
Pumpblocking
Pumpblockingonalarms
Dryrundetection
Type of pump:
• Fixedpumps
A digital output starts the pump
• Speedcontrolledpump(PID/VFD)
Start a VFD which has predened frequency
Pump parameters:
• Set the nominal current for the pump
• Set the power factor for the pump
Usefulparameterstodetectdryrunandheavyload
Select run indication:
• Digitalinput
• Motor current
Require current transformers connected to an analog input
• Modbus CA 622
RS 485 communication to/from VFD or soft starter
Start/stop levels for each pump
Recommendedtohavedierentstartlevelsforallthepumps.Samestoplevelforallthepumpsisne.
Time settings (optimal parameter)
Setthemaximumruntimeforthepumps
QH curve (pump curve)
Togetaccuratevaluesforpumpcapacityandpumpedvolume,thisparameterisimportant.Seechapter5for
more information about pump curve.
Other manuals for ABS PC 441
1
This manual suits for next models
1
Table of contents
Other Sulzer Controllers manuals