Sundyne Sunflo P-3000 Series Installation instructions manual

02.10.02E, 6/2000 Visit our website at www.sundyne.com
Effective: 6/2000
Supersedes: 6/97
P-3000
with Journal Bearings
Instruction & Operation Manual
SUNFLO

02.10.02E, 6/2000 Visit our website at www.sundyne.com 1
COPYRIGHT
All rights reserved. No part of this publication may be reproduced, stored in a
retrieval system or transmitted in any form or by any means, electronic,
mechanical, photocopying, recording or otherwise without the prior permission
of Sundyne Corporation.
©2000 Sunyne Corporation
WARRANTY
Sundyne Corporation warrants to Buyer for a period of twelve (12) months from the
date of being placed in service (but not to exceed eighteen (18) months after the
date of shipment) that the equipment at the time of shipment will be free from
defects of design, material and workmanship. If any defects or malperformance
occur during the warranty period, Sundyne’s sole obligation shall be limited to
alteration, repair or replacement at Sundyne’s expense, F.O.B. Factory, of parts or
equipment, which upon return to Sundyne and upon Sundyne’s examination prove to
be defective. Equipment and accessories not manufactured by Sundyne are
warranted only to the extent of and by the original manufacturers’ warranty. Sundyne
shall not be liable for damage or wear to equipment caused by abnormal conditions,
vibration, failure to properly prime or to operate equipment without flow or caused by
corrosives, abrasives or foreign objects. THE FOREGOING WARRANTY IS
EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER
EXPRESSED OR IMPLIED INCLUDING ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. In no
event shall Sundyne be liable for consequential or incidental damages.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 2
Icons Used in this Manual
The following icons (symbols) are used to indicate specific types of information.
Good ideas to use. A reminder to do something.
Equipment use alert. Unless you follow these procedures correctly, the equipment may be
damaged.
Safety alert. Failure to follow these procedures can endanger the safety of you or others.
Electrical hazard. Failure to follow these procedures can endanger the safety of you or
others.
NOTES:
Sunflo P-3000 = High Speed Centrifugal Pumps

02.10.02E, 6/2000 Visit our website at www.sundyne.com 3
USING THIS MANUAL:
This manual presents installation, servicing, starting, pump control, troubleshooting, maintenance, and
spare parts information for the Sunflo P-3000 centrifugal pump.
Parenthetical numbers included in the text correspond to item numbers located on the illustrated figures.
Information that may be required and is not included herein may be obtained from your Sundyne
Corporation distributor, or directly from the factory.
i. Introduction to the Sunflo P-3000 Pump
ii. Safety Precautions
iii. Critical Startup Checklist
1. Receiving Your Unit
Inspection, Storage, Long-Term Storage
2. Installation
Mounting, Frame mount Drive Unit Installation, Final Alignment, Suction and Discharge Piping
3. Auxiliary Piping and Seal Environment
Single Seal Flush System, Double Seal Liquid Buffer System, Tandem Seal Liquid Buffer System,
Process Seal Drains, Seal Cavity Pressure Rise
4. Pre-startup
Gearbox Oil Fill
5. Startup
6. Pump Operation
Suction Conditions, Discharge Conditions, Minimum Flow Conditions, Maximum Flow Conditions,
Drivers, Entrained Gases
7. Pump Control
Parallel Operation
8. Troubleshooting
Gearbox and Pump, Pump Mechanical Seals
9. Maintenance
Servicing – Driver, Gearbox Oil Change, Seal Leakage, Radial Ball Bearings, Coupling
Torque Values

02.10.02E, 6/2000 Visit our website at www.sundyne.com 4
10. Pump Disassembly
Provides a detailed disassembly procedure for the gearbox and pump
11. Pump Assembly
Provides a detailed re-assembly procedure for the gearbox and pump
12. Tool Drawings
13. Parts List
General, Recommended Spares

02.10.02E, 6/2000 Visit our website at www.sundyne.com 5
i. Introduction to the Sunflo P-3000 Pump
The Sunflo P-3000 pump is a high pressure/high speed centrifugal pump which provides multi-stage
performance from a single-stage unit. The frame mounted configuration offers a greater degree of
performance diversity and added driver flexibility such as the use of standard electric motors, steam
turbines, and internal combustion. The close-coupled design incorporates the proven Sunflo design in an
integral pump and motor package. This configuration provides a compact lightweight unit that does not
utilize bedplates, couplings or belts. Installation is simplified and alignment of the pump and motor is not
necessary. Close-coupled pumps are ideal for OEM packages and other industrial applications where a
frame unit is not desired.
Common uses include pollution control, chemical, petrochemical, power system services, pulp and paper,
vehicle manufacturing, mining, food and beverage, and oil products.
ii. Safety Precautions
Safety Warning
Sundyne Corporation manufactures centrifugal pumps to exacting International Quality Management
System Standards (ISO 9001 - 1987) as certified and audited by Lloyd's Register Quality Assurance
Limited. Genuine parts and accessories have been specifically designed and tested for use with these
products to ensure continued product quality and performance. As Sundyne Corporation cannot test all
parts and accessories sourced from other vendors, incorrect design and/or fabrication of such parts and
accessories may adversely affect the performance and safety features of these products. Failure to
properly select, install or use authorized Sunflo pump parts and accessories is considered misuse and
damage or failure caused by misuse is not covered by Sundyne’s warranty. Additionally, modification of
Sunflo products or removal of original components may impair the safety of these products and their
effective operation.
Suggested Safety Instructions:
During installation, maintenance, or repair operations of a Sunflo pump, systems for safety shall be
applied before the commencement of work. Failure to take responsibility for safety may lead to injury of
operator or others.
Personal Protective Equipment (PPE): Safety glasses with side shields, as a minimum, shall be worn
by all personnel installing or performing maintenance or repair on the equipment. If equipment is over 15
pounds (7 kg) and is to be manually lifted, or if pallet jacks or forklifts are to be used, steel-toed safety
shoes shall be worn. When testing the equipment, hearing protection is highly recommended if noise
levels exceed 85 dB during an eight (8.0) hour period. Chemical resistant gloves shall be used if chemical
use is required (see Chemical Use below for additional information). If chemicals have warnings
regarding fumes and/or dust/mists, a dust mask respirator shall be worn as a minimum.
When selecting one piece of PPE to be used with another, consider the compatibility between them. For
example, safety glasses should not interfere with the seal from hearing protection. Be sure to clean the
PPE after each use.
Use of Forklifts: All forklift drivers must have a current recognized license. If using a forklift, first ensure
that the lift is in a safe operating condition.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 6
Electrical Safety: During installation, service, or repair ensure all electrical sources are off and it is safe
to operate the equipment. A recognized Lock-out/Tag-out program should be followed - Locks and/or
tags should be provided warning employees that the equipment is being installed, serviced, and/or
repaired. Once the work is complete, the person installing the lock and/or tag shall remove it following
your company’s procedure for Lock-out/Tag-out and inform others of start-up.
Testing Equipment: Persons in the immediate area shall be warned when a test is to be performed.
Tools: Tools shall be insulated from electrical shock. Ensure all tools are clean and free of oil and the
insulation is not damaged in any way.
Chemical Use: Any chemicals to be used shall be accompanied by a relevant material safety data sheet
(MSDS), in accordance with your government legislation. If applicable, chemical proof gloves shall be
used. An eye wash station (or equivalent) should be available in the event of injury. Should any
hazardous or flammable chemicals have passed through the equipment a complete decontamination of
the equipment is required.
Fall Protection: When working over six feet from the ground, fall protection is required.
Machine Guards: Guards shall remain in place on all equipment. Only during maintenance/repair can
the guards be removed, and prior to start-up, the guard must be replaced.
Lock-Out/Tag-Out Guidelines:
Follow Your Company’s Lock-Out / Tag-Out Procedure When Servicing Sunflo Pumps.
iii. Critical Startup Checklist
Know Your Machine
Before servicing and starting up the Sunflo P-3000 pump, carefully review the specification sheet, the
outline drawings, performance curves, and this instruction manual. It is important you become familiar
with the pump configuration before starting and operating the pump.
Driver Instructions
Carefully follow the installation and starting instructions provided by the manufacturer of the driver. This is
included in the final data package.
Auxiliaries
1. Check the utility connections.
2. Verify that the auxiliary piping conforms to Sundyne’s drawings.
3. Verify the connections of the switches, the instruments, and their settings.
4. Calibrate all measurement equipment (Flow meters, Current or Ampere meters, Pressure meters, etc.).
Environmental Control System
Install a system to control the environment of the seal, if required, and verify that Port 1 is properly
vented.
If required install overhead drain piping.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 7
Pressurized Fluid Loop:
Pressurize double seal buffer loop or external seal flush, if required, prior to admitting fluid into pump
casing.
Check Driver Rotation
Rotation must be in the same direction as the arrow stamped or cast on the pump casing.
Gearbox Servicing:
Where applicable, operate auxiliary lube pump to fill heat exchanger and filter. Add oil as necessary
through fill fitting until oil level stabilizes in sight glass. The gearbox alone requires approximately eight
U.S. quarts (7.5 liters).
Starting Pump
Start pump with suction valve completely open while throttling discharge valve, to bring pump to design
operating point.
Heat Exchanger
If a heat exchanger for the gearbox is installed, adjust the cooling flow to keep the temperature of the
gearbox sump at 120°-170°F (49°-77°C).
Check
Check total head, flow rate, and power consumption against pump specification sheet. Check that
specific gravity, viscosity and NPSH are in accordance with specification sheet. These conditions will
significantly alter performance of the pump.
Process Conditions
Do process conditions; suction pressure, suction temperature, discharge pressure, agree with
specification sheet information? Check with your Sunflo representative if you must test or run a different
fluid/specific gravity than shown on the specification sheet.
Auxiliary Lube Pump
If you have an auxiliary lubrication pump, unlock the electrical circuit and start it in the “hand” position.
Check for oil leaks and recheck the oil level.
Piping Connections
Are the following bolted/threaded connections tight:
a. Pump flange bolts?
b. Seal environment piping and port connections?
c. Cooling water connections to heat exchanger? (if applicable)
d. Gearbox oil drain plug?
e. Pump case drain plug?

02.10.02E, 6/2000 Visit our website at www.sundyne.com 8
1. Installation
This section contains the following:
Introduction: Provides a brief description of the pump and how it is used.
Inspection: Important items to inspect as soon as you receive your pump.
Short-term Storage: Procedure for units installed within 6 months.
Long-term Storage: Procedure for units installed after 6 months.
Mounting
Final Alignment
Suction and Discharge Piping: Procedures to set up the suction and discharge piping.
Auxiliary Piping and Seal Environment: Procedures to set up the seal environment controls,
even if you use the standard system supplied by the factory. Gas buffer system procedures are
included.
Baseplate Mounting and Grouting: Use this information for grouting the baseplate.
Driver and Coupling: Procedures to align the driver and pump. Do this after grouting, and before
connecting the piping for suction and discharge. Once the suction and discharge piping is
connected, confirm the final alignment.
Inspection
1. When you receive the Sunflo P-3000 Pump, check for any damage. If you find any, inform the carrier
and Sundyne Corporation promptly.
2. Use Outline drawings in the last section of final data package, and reference the Pump and Gearbox
bill of material to ensure that all auxiliary items are properly included.
3. Check the gear shaft carefully. Seal drag may cause it not to turn freely at first; this is normal. If the
gear shaft binds, it may be damaged, or may need adjusting.
Short-term Storage - 1 day to 6 months
1. If the pump is to be stored near strong chemicals or salt water, protect it immediately. To do this,
follow steps 5 through 10 from the long-term storage procedures below.
2. Protect the unit from moisture and dust.
3. Make sure that the factory’s shipping covers for the housing flanges and the seal ports are securely
in place.
4. Carefully follow the storage instructions provided by the manufacturer of the motor or turbine driver.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 9
Long-term Storage - 6 months or more
If you store the Sunflo P-3000 Pump for a long period of time, the following methods are very important.
If you require further instructions, please contact Sundyne Corporation at (303)-425-0800 USA and ask
for the Field Service Department.
1. Be sure the storage area is indoors and has: Humidity below 65%; and temperature range from 45°F
to 85°F (7°C to 29°C).
2. Do not allow contact of airborne chemicals with the internal components of the unit.
3. If the unit is being stored near strong chemicals or salt water, protect it immediately.
4. Protect the unit from moisture and dust.
5. Make sure that the factory’s shipping covers for housing flanges and seal ports are securely in place.
6. Prevent corrosion to the components of the gearbox and the fluid-end.
7. Use desiccant bags to absorb moisture.
8. Purge the internal components with an inert gas.
9. Flood component internals with oil.
10. After long-term storage, have an authorized Sundyne service engineer inspect all components and
supervise any necessary repair to be sure that they work properly. Any components not made by
Sundyne (except mechanical seals) must be inspected or replaced as determined by the
manufacturer’s authorized personnel, at the purchaser’s expense. Any Field Service work must be
clearly stated at the time of purchase to validate an Extended Warranty.
Because storage location and unknown factors at the site or storage are beyond our control,
Sundyne does not accept any liability for damage to the equipment during storage, nor do we
guarantee the quality of the equipment during and after the storage period. An Extended Warranty
will be null and void if the proper equipment preparation is not maintained.
Mounting
A. During pump installation, ensure that adequate surrounding space is available for inspection,
operation, and maintenance requirements.
B. The pump and driver for both the close-coupled and the frame mounted units should be bolted to a
concrete foundation or an adequately supported structure substantial enough to absorb any vibration
and to form a rigid support. If the pump and driver are mounted on a bedplate, the bedplate should
be mounted on a concrete foundation and grouted.
1. Choose a solid ground location and build the foundation form 3 inches larger overall than the
bedplate.
2. Use bedplate anchor bolts of the same size specified in the outline drawing. Provide pipe sleeves
with an I.D. 2.5 to 3.0 times the bolt diameter. Provide flat washers between the bolt head and pipe
sleeve to keep the bolt from slipping through the pipe sleeve.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 10
3. Bolts should be of sufficient length so that they will project at least one-fourth inch above the nuts
after allowing for bedplate, shim, and nut thickness. Locate the bolts accurately according to the
outline drawing.
4. Pour concrete and tamp or vibrate during the pouring process to ensure no hollow spot forms. This
is especially important around the anchor bolts. Do not allow any concrete to fall inside the pipe
sleeves.
5. Level off the concrete surface. Leave a rough finish to provide a good base for grout. Allow the
foundation to cure for one week before installing.
6. Hoist the bedplate above the foundation and lower into position over the anchor bolts. Anchor bolts
can be moved laterally in the hollow of pipe sleeve for ease of alignment with the holes in the
baseplate.
7. Using a precision level across the bedplate (front to rear and side to side), insert steel shims as
required next to each bolt until the bedplate is level in all directions. Secure the anchor bolt nuts
finger tight only.
8. Provide a wood dam around the base perimeter of the bedplate and thoroughly wet the top surface
of the foundation. The use of non-shrink grout is recommended. Grout should be of a consistency
to flow out under the bedplate against the wood dam. Grout should be puddled continuously as it is
poured to expel air and to completely fill the space under the bedplate. Fill to the level of the grout
hole.
9. Allow the grout to harden for at least 48 hours. Tighten the anchor bolts.
Figure 1
FRAMEMOUNT DRIVE UNIT INSTALLATION
A. Pumps supplied from the factory with a driver, base, and coupling are rough aligned prior to
shipment. However, stresses caused by lifting and shipment may cause minor distortion which will
alter the factory alignment. Check the coupling alignment after the baseplate has been leveled and
prior to grouting.
B. If the coupling alignment has been disturbed by improper leveling of the base-plate, correct prior to
grouting. After the base has been grouted and the piping connected, make a final pre-startup
alignment check. Additionally, a hot alignment check should be made once the pump has reached
normal operating temperature.
C. Coupling alignment should be verified only after the suction and discharge piping has been
connected.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 11
If a coupling is being used that was not supplied by Sundyne, it must be a flexible type,
vibration- damping coupling. Refer to the coupling manufacturer’s recommendations for
installation and alignment.
To prevent personnel injury, lock-out the starting switch on the driver.
D. Alignment of the pump and driver is vital to trouble-free mechanical operation. The following are
suggested steps to establish initial alignment of the unit using Sundyne stocked flexible couplings.
1. Clean all parts using a nonflammable solvent. Lightly coat the seal with grease and place on the
shafts before the mounting hubs.
2. Mount hubs on their respective shafts so the hub is flush with the end of its shaft. Tighten the set
screws when furnished.
3. Align the coupling. On the initial alignment, set the motor 0.003 to 0.004 inches (0.076 to
0.101 mm) higher than the pump to allow for thermal growth.
4. Tighten all hold down bolts on the pump and driver (and bedplate if used). Check the alignment
and realign if necessary.
FINAL ALIGNMENT
The motor shaft height should be equal to the pump input shaft height at operating temperature.
The final alignment should be re-checked after a week of operation
A. Final alignment can only be accomplished after the unit has been run under actual operating
conditions. The unit must be run for a sufficient period of time to bring the unit up to operating
temperature. After the warm up period has elapsed, stop the unit, disconnect the coupling, and check
the alignment. Repeat the alignment procedure and run the pump through another warm-up
procedure to verify the alignment.
B. Recheck the alignment after the pump has been running for about a week. This check must be made
immediately after the pump has been shut down and before it has a chance to cool.
Installing The Suction And Discharge Piping - Guidelines
A. Good installation practice dictates that there should be a minimum straight length of pipe on the
suction of the pump equal to ten (10) times the suction pipe diameter. This is to allow the liquid to
flow into the pump casing/impeller without turbulence. Furthermore, good installation practice
dictates the use of suction piping at least one or two sizes larger than the pump flange and reduction
of the pipe diameter at the pump flange. Use an eccentric reducer with the “Belly” side down. Do
NOT install with “Belly” side up. Never use suction piping of a smaller diameter than the pump suction
inlet.
B. Both the suction and discharge piping should have no unnecessary elbows, bends, and fittings as
they increase friction losses in the piping. The size of pipe and fittings should be selected carefully to
keep the friction losses as low as practical.
C. Suction and discharge block-and-bleed valve designs are recommended to isolate the pump during
shutdown and to drain the process piping when removal of the pump is necessary.
The rotation of the pump casing without a modification to the journal bearing
orientation will cause the pump to fail. Contact the factory or your authorized Sunflo
sales representative for assistance on how to modify the journal bearings.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 12
D. The pump casing can be rotating in increments of 90° to place the discharge connection in any of the
four positions: horizontal right or left and vertical up or down.
E. Do not rotate the seal housing. The seal ports must always be as shown in Figure 2.
Figure 2
F. Under no circumstances should the suction pipe be forced in order to align it to the pump suction
inlet. The flange bolts should slip into the aligned flange holes without straining the piping.
G. Gasket surfaces should be parallel and flange bolts should slip into the aligned flange holes without
straining the pipe to fit the pump.
H. Piping layouts should be designed to provide sufficient support and flexibility to minimize forces and
moments induced by the piping onto the pump.
I. All piping must be supported independently of the pump. Proper support for the suction and
discharge piping is essential in order to avoid pipe strain on the pipe casing.
J. The suction line should be clean and a temporary suction strainer of approximately 40 mesh should
be installed during initial startup to protect the impeller from damage by mill scale, welding slag, or
other foreign particles during initial startup.
K. Always provide a suction pressure gauge on all installations to monitor suction conditions. Install the
gauge as close as possible to the suction flange. When temporary suction strainers are used, ensure
that the gauges are installed on both sides of the strainer.
L. Always provide a discharge pressure gauge on all installations to monitor discharge conditions.
Install the gauge as close as possible to the discharge flange.
M. Check valves should be placed on all installations where back flow through the pump is possible. If a
check valve is installed in the discharge line, provisions should be made to vent the space between
the pump and the check valve or the pump may not prime.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 13
Auxiliary Piping and Seal Environment
A. Depending upon the pump seal arrangement and application, a seal environment control system may
be required. The pump seal environment must always be maintained as determined by the seal
arrangement. There are three different seal arrangements available for your Sunflo P-3000 pump:
The single seal, the double seal, and the tandem seal. It is important that the seal environment
control system piping be connected as shown in Figure 2 and that the seal drain port is always left
open.
B. For application data and available seal flush plans utilizing a process seal, please refer to Sunflo
Field Engineering Bulletin 40.2.58, “Sunflo Pump Seal Plans”. Contact your authorized Sunflo sales
representative if you do not have this bulletin.
If a seal flush system is not in use, then the seal flush port should be plugged to prevent
outside contamination of the seal cavity. The seal flush port is at the 12 o’clock position
as shown in Figure 2.
Regardless of what seal arrangement is being used, the process drain on the seal
housing must always remain open to atmosphere. Failure to leave the gearbox drain
port open will cause process fluid to accumulate in the seal housing and to eventually
leak past the gearbox seal into the gearbox oil sump.
Single Seal Flush System
C. A seal flush system utilizing the seal flush port is available for use with the single or tandem seal
arrangement. The seal flush must be cool, clean, and compatible with the process fluid and pump
materials of construction. When using an external seal flush, the seal must be flushed at 15 psi
(1.05 kg/cm2) above the seal cavity pressure and at a controlled rate of 2.0 gpm (0.4 m3/hr). Please
refer to Paragraph G of this section for details concerning seal cavity pressure rise. Seal cavity
pressure rise values are provided in Table 1.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 14
Double Seal Liquid Buffer System
The buffer system must be in operation prior to flooding the pump suction. Failure to do
so will cause reverse pressurization of the in-board seal and may result in contamination
of the buffer system with the process fluid.
D. A liquid buffer system must be used with a double liquid seal arrangement to prevent process liquid
leakage out of the pump. The buffer must be cool, clean, and compatible with the process fluid and
pump materials of construction. The buffer is introduced into the “buffer in” port of the seal housing at
a pressure of 15 psi (1.05 kg/cm2) above the design seal cavity pressure rise. Please refer to
Paragraph G of this section for details concerning seal cavity pressure rise. Seal cavity pressure rise
values are provided in Table 1. A small portion of the buffer fluid flows across the inboard seal into the
process fluid and a small portion flows across the outboard seal and is vented from the drain port. A
buffer flow of 0.5 to 3 gpm (0.10 to 0.70 m3/hr) must be maintained through the buffer cavity to
properly lubricate and cool the seals. This flow should be regulated by a valve or orifice on the “buffer
out” port of the seal housing.
TANDEM SEAL LIQUID BUFFER SYSTEM
E. A liquid buffer system is used with tandem seal arrangement to cool and lubricate the outboard seal
and to contain process fluid leakage from the inboard seal. The buffer fluid must be cool, clean, and
compatible with the process fluid and pump materials of construction. The buffer liquid is introduced
into the “buffer in” port of the seal housing at atmospheric pressure and must maintain a flow of 0.5 to
3.0 gpm (0.10 to 0.70 m3/hr) through the buffer cavity to properly lubricate and cool the outboard
(secondary) seal.
PROCESS SEAL DRAINS
F. Piping may connect to the seal port drain. However, the piping should be arranged to prevent any
back pressure. Failure to prevent back pressure will cause a failure of the gearbox seal resulting in
the leakage of process fluid into the gearbox.
SEAL CAVITY PRESSURE RISE
G. Whenever a single seal with external flush, double, or tandem seal arrangement is used, the seal
cavity pressure rise must be known to determine the seal flush or buffer pressure. The area behind
the impeller, near the seal, is referred to as the seal cavity. Suction pressure plus the seal cavity
pressure rise plus a safety margin of 15 psi (1.05 kg/cm2) equals the required double seal buffer
pressure or the single seal flush pressure.
The required seal flush/buffer pressure may be determined for your pump model by using the values in
Table 1 and the method provided below:
1. Find the pump model that is applicable to your pump.
2. Determine the seal cavity pressure rise (based on water with a specific gravity of 1.0).
3. Multiply this seal cavity pressure rise value by the specific gravity of the process fluid.
4. Specify the seal flush/buffer pressure to equal the sum of the suction pressure, the specific
gravity corrected seal cavity pressure rise determined in Step G-3, and 15 psi (1.05 kg/cm2).

02.10.02E, 6/2000 Visit our website at www.sundyne.com 15
EXAMPLE:
Model: Sunflo P3-AJG
Suction Pressure: 19 psig
Seal Cavity Pressure Rise: 20 psig
(From Table 1)
Process Specific Gravity: 0.95
Required Seal Flush/Buffer Pressure
(RSFBP) = Suction Pressure + Seal Cavity Pressure Rise + 15 psig
RSFBP = 19 psig + (20 psig)(0.95) + 15 psig
RSFBP = 53 psig

02.10.02E, 6/2000 Visit our website at www.sundyne.com 16
Table 1. Seal Cavity Pressure Rise (Based on Water: SG = 1.0 and 60 Hz)
*SCPR in psi (bar)
Model SCPR* Model SCPR* Model SCPR* Model SCPR* Model SCPR*
P3-AJG
PE-AKG
P3-ALG
P3-AMG
P3-ANG
P3-APG
20
(1.4) P3-AJH
P3-AKH
P3-ALH
P3-AMH
P3-ANH
P3-APH
20
(1.4) P3-AMJ
P3-ANJ
P3-APJ
20
(1.4) P3-AMK
P3-ANK
P3-APK
P3-AQK
P3-ARK
P3-ASK
P3-ATK
P3-AVK
P3-AWK
20
(1.4) P3-ARL
P3-ASL
P3-ATL
P3-AVL
20
(1.4)
P3-ARM
P3-ASM 25
(1.7) P3-BNE
P3-BPE
P3-BQE
P3-BRE
P3-BSE
P3-BTE
P3-BVE
P3-BWE
25
(1.7) P3-BLF
P3-BMF
P3-BNF
P3-BPF
P3-BQF
P3-BRF
P3-BSF
P3-BTF
P3-BVF
P3-BWF
25
(1.7) P3-BMG
P3-BNG
P3-BPG
P3-BQG
P3-BRG
P3-BSG
P3-BTG
P3-BVG
P3-BWG
25
(1.7) P3-BLH
P3-BMH
P3-BNH
P3-BPH
P3-BQH
P3-BRH
P3-BSH
P3-BTH
P3-BVH
P3-BWH
25
(1.7)
P3-BLJ
P3-BMJ
P3-BNJ
P3-BPJ
P3-BQJ
P3-BRJ
P3-BSJ
P3-BTJ
P3-BVJ
P3-BWJ
25
(1.7) P3-BMK
P3-MNK
P3-BTK
P3-BVK
P3-BWK
30
(2.1) P3-BRL
P3-BSL 30
(2.1) P3-CMD
P3-CND
P3-CPD
P3-CQD
P3-CRD
P3-CSD
P3-CTD
P3-CVD
P3-CWD
30
(2.1) P3-CJE
P3-CKE
P3-CLE
P3-CME
P3-CNE
P3-CPE
P3-CQE
P3-CRE
P3-CSE
P3-CTE
P3-CVE
P3-CWE
35
(2.4)
P3-CJF
P3-CKF
P3-CLF
P3-CMF
P3-CNF
P3-CPF
P3-CQF
P3-CRF
P3-CSF
P3-CTF
P3-CVF
P3-CWF
35
(2.4) P3-CHG
P3-CJG
P3-CKG
P3-CLG
P3-CMG
P3-CNG
P3-CPG
P3-CQC
P3-CRG
P3-CSG
40
(2.8) P3-CJH
P3-CKH
P3-CLH
P3-CMH
P3-CNH
P3-CPH
P3-CQH
P3-CRH
P3-CSH
40
(2.8) P3-CMJ
P3-CNJ
P3-CPJ
P3-CQJ
45
(3.1) P3-CMK
P3-CNK 45
(3.1)
P3-DGB
P3-DHB
P3-DJB
P3-DKB
P3-DLB
P3-DMB
P3-DNB
P3-DPB
50
(3.4) P3-DFC
P3-DGC
P3-DHC
P3-DJC
P3-DKC
P3-DLC
P3-DMC
P3-DNC
P3-DPC
50
(3.4) P3-DED
P3-DFD
P3-DGD
P3-DHD
P3-DJD
P3-DKD
P3-DLD
P3-DMD
P3-DND
P3-DPD
50
(3.4) P3-DDE
P3-DEE
P3-DFE
P3-DGE
P3-DHE
P3-DJE
P3-DKE
P3-DLE
P3-DME
50
(3.4) P3-DFF
P3-DGF
P3-DHF
P3-DJF
P3-DKF
P3-DLF
P3-DMF
50
(3.4)
P3-DGG
P3-DHG
P3-DJG
P3-DKG
60
(4.1) P3-DJH 60
(4.1) P3-EDB
P3-EEB
P3-EFB
P3-EGB
P3-EHB
P3-EJB
P3-EKB
P3-ELB
P3-EMB
P3-ENB
70
(4.8) P3-ECC
P3-EDC
P3-EEC
P3-EFC
P3-EGC
P3-EHC
P3-EJC
P3-EKC
P3-ELC
70
(4.8) P3-ECD
P3-EDD
P3-EED
P3-EFD
P3-EGD
P3-EHD
P3-EJD
P3-EKD
70
(4.8)
P3-EEE
P3-EFE
P3-EGE
P3-EHE
P3-EJE
70
(4.8) P3-EGF
P3-EHF 70
(4.8) P3-FCB
P3-FDB 75
(5.2) P3-FEB
P3-FFB
P3-FGB
P3-FHB
P3-FJB
80
(5.5) P3-FCC
P3-FDC
P3-FEC
P3-FFC
P3-FGC
P3-FHC
80
(5.5)
P3-FCD
P3-FDD
P3-FED
P3-FGD
80
(5.5) P3-FEE
P3-FFE 80
(5.5)

02.10.02E, 6/2000 Visit our website at www.sundyne.com 17
Table 1. Seal Cavity Pressure Rise (based on Water: SG = 1.0 and 50 Hz)
*SCPR in bar (psi)
Model SCPR* Model SCPR* Model SCPR* Model SCPR* Model SCPR*
P3-HJG
P3-HKG
P3-HLG
PE-HMG
P3-HNG
P3-HPG
1.2
(17) P3-HJH
P3-HKH
P3-HLH
P3-HMH
P3-HNH
P3-HPH
1.2
(17) P3-HMJ
P3-HNJ
P3-HPJ
1.2
(17) P3-HMK
P3-HNK
P3-HPK
P3-HQK
P3-HRK
P3-HSK
P3-HTK
P3-HVK
P3-HWK
1.4
(20) P3-HRL
P3-HSL
P3-HTL
P3-HVL
1.4
(20)
P3-HRM
P3-HSM 1.4
(20) P3-JNE
P3-JPE
P3-JQE
P3-JRE
P3-JSE
P3-JTE
P3-JVE
P3-JWE
1.7
(25) P3-JLF
P3-JMF
P3-JNF
P3-JPF
P3-JQF
P3-JRF
P3-JSF
P3-JTF
P3-JVF
P3-JWF
1.7
(25) P3-JMG
P3-JNG
P3-JPG
P3-JQG
P3-JRG
P3-JSG
P3-JTG
P3-JVG
P3-BWG
1.9
(27) P3-JMH
P3-JNH
P3-JPH
P3-JQH
P3-JRH
P3-JSH
P3-JTH
P3-JVH
P3-JWH
1.9
(27)
P3-JLJ
P3-JMJ
P3-JNJ
P3-JPJ
P3-JQJ
P3-JRJ
P3-JSJ
P3-JTJ
P3-JVJ
P3-JWJ
2.1
(30) P3-JLK
P3-JMK
P3-JTK
P3-JVK
P3-JWK
2.1
(30) P3-JRL
P3-JSL 2.1
(30) P3-KMD
P3-KND
P3-KPD
P3-KQD
P3-KRD
P3-KSD
P3-KTD
P3-KVD
P3-KWD
2.4
(35) P3-KJE
P3-KKE
P3-KLE
P3-KME
P3-KNE
P3-KPE
P3-KQE
P3-KRE
P3-KSE
P3-KTE
P3-KVE
P3-KWE
2.5
(36)
P3-KJF
P3-KKF
P3-KLF
P3-KMF
P3-KNF
P3-KPF
P3-KQF
P3-KRF
P3-KSF
P3-KTF
P3-KVF
2.5
(36) P3-KHG
P3-KJG
P3-KKG
P3-KLG
P3-KMG
P3-KNG
P3-KPG
P3-KQC
P3-KRG
P3-KSG
P3-KTG
2.8
(40) P3-KJH
P3-KKH
P3-KLH
P3-KMH
P3-KNH
P3-KPH
P3-KQH
P3-KRH
P3-KSH
2.8
(40) P3-KLJ
P3-KMJ
P3-KNJ
P3-KPJ
P3-KQJ
3.3
(48) P3-KMK
P3-KNK 3.3
(48)
P3-LGB
P3-LHB
P3-LJB
P3-LKB
P3-LLB
P3-LMB
P3-LNB
P3-LPB
3.5
(50) P3-LFC
P3-LGC
P3-LHC
P3-LJC
P3-LKC
P3-LLC
P3-LMC
P3-LNC
P3-LPC
3.5
(50) P3-LED
P3-LFD
P3-LGD
P3-LHD
P3-LJD
P3-LKD
P3-LLD
P3-LMD
P3-LND
P3-LPD
3.5
(50) P3-LDE
P3-LEE
P3-LFE
P3-LGE
P3-LHE
P3-LJE
P3-LKE
P3-LLE
P3-LME
P3-LNE
3.5
(50) P3-LFF
P3-LGF
P3-LHF
P3-LKF
P3-LLF
P3-LMF
3.5
(50)
P3-LGG
P3-LHG
P3-LJG
P3-LKG
4.9
(70) P3-LJH 4.9
(70) P3-MDB
P3-MEB
P3-MFB
P3-MGB
P3-LHB
P3-LJB
P3-LKB
P3-LLB
P3-LMB
P3-LNB
4.9
(70) P3-MCC
P3-MDC
P3-MEC
P3-MFC
P3-MGC
P3-MHC
P3-MJC
P3-MKC
P3-MLC
4.9
(70) P3-MCD
P3-MDD
P3-MED
P3-MFD
P3-MGD
P3-MHD
P3-MJD
P3-MKD
4.9
(70)
P3-MEE
P3-MFE
P3-MGE
P3-MHE
P3-MJE
4.9
(70) P3-MGF
P3-MHF 4.9
(70) P3-NCB
P3-NDB 5.3
(77)
P3-NEB
P3-NFB
P3-NGB
P3-NHB
P3-NJB
5.6
(81) P3-NCC
P3-NDC
P3-NEC
P3-NFC
P3-NGC
P3-NHC
5.6
(81)
P3-NCD
P3-NDD
P3-NED
P3-NFD
P3-NGD
5.6
(81) P3-NEE
P3-NFE 5.6
(81)

02.10.02E, 6/2000 Visit our website at www.sundyne.com 18
Pre-Startup
Gearbox Oil Fill
Refer to Table 2 for lube oil system specifications.
Refer to Table 3 for gearbox lubricant specifications.
Overfilling the gearbox will cause excess foaming, increased power consumption, and oil leakage.
Make up oil can be added through the fill plug (P3-8) during operation.
A. Prior to initial startup and after any disassembly, the following oil fill procedure must be followed to
ensure proper priming of the high speed shaft journal bearings. Please refer to Figure 3.
B. Remove the plug (Item P3-214) on the lube oil manifold for use as an air vent.
C. Ensure that the gearbox oil sump drain plug is installed.
D. Remove the fill plug (Item P3-8) and fill the gearbox until the fluid level reaches the designated level
on the sight glass. Approximately 8 quarts (7.5 liters) are required.
E. Replace the fill plug and air vent plug.
F. Remove the oil filter, fill with oil, and reinstall.
Figure 3.

02.10.02E, 6/2000 Visit our website at www.sundyne.com 19
Table 2. Lube Oil system Specifications
English Metric
Sump Capacity 8 quarts 7.5 liters
Oil Pressure 40 – 60 psig 2.8 – 4.2 kg/cm2
Oil Temperature (Sump) 120° – 160°F 50 – 70°C
Cooling Water Required 5 – 10 at 90°F max. 1.2 – 2.3 m3/hr at 32°C max.
Cooling Water Pressure 150 psi max. 11 kg/cm2max.
Table 3. Sunflo Gearbox Lubricants
Gravity, API 29.5 nominal
Viscosity, SUS
100°F (38°C) 200 maximum
210°F (100°C) 38 minimum
Viscosity Index, ASTM D2270 90 minimum
ISO Viscosity Grade 32, 46
Flash Point, °F, ASTM D92 360 minimum (182°C)
Pour Point, °F, ASTM D97 -20 maximum (-29°C)
Rust Test, ASTM D-665, Procedure B Pass
Oxidation Test, ASTM D-943, hours to 2.0 neutralization
number 2000
EP Additive Present
Foam Limits, ASTM 892, milliliters maximum, Sequence 1 25/0
2 50/0
3 25/0
Note: No additives are recommended.
In general, ISO VG 32 turbine oils or most synthetic oils will meet these specifications. The
properties of your oil should be verified by the oil manufacturer prior to use.
Dextron III type ATF is not recommended for use in Sunflo gearboxes. Problems with foaming may
occur and the additional additives compared to Dextron II could compromise the mechanical
integrity and reliability of your Sunflo pump.
Startup
Perform the following steps to start your Sunflo pump.
A. Review the pump specification sheet noting design parameters and possible seal system
requirements.
B. Check to ensure that the driver has been serviced per the instructions supplied by the driver
manufacturer.
C. Check to ensure that the screen has been installed in the temporary suction strainer.
D. If a buffer fluid or external seal flush is required, ensure that this system is pressurized prior to
flooding the suction. Failure to pressurize the buffer system will allow the process fluid to
contaminate the buffer fluid and may also allow contaminants in the process stream to damage the
seal face.
Table of contents
Other Sundyne Water Pump manuals
Popular Water Pump manuals by other brands

goodnature
goodnature C100 owner's manual

Crivit
Crivit 285656 instruction manual

Antares
Antares HOTMATIC 15-1.5 Installation and operating instructions

Groeneveld
Groeneveld Twin-3 User instruction

Wilden
Wilden P800 Engineering, operation & maintenance

GORMAN-RUPP PUMPS
GORMAN-RUPP PUMPS 81 1/2A2-B Installation, operation, and maintenance manual with parts list

Metabo
Metabo DP 18-5 SA Original instructions

Blichmann
Blichmann RipTide Assembly operation maintenance

Intex
Intex Quick-Fill AP619-III owner's manual

DIVERSITECH
DIVERSITECH ASURITY PROCP-22S installation instructions

Varian
Varian TV 1001 SEM instruction manual

BUSCH
BUSCH COBRA BC 0101 G instruction manual