Installation Operation & Maintenance Manual
Pressure Controls, Operation an Testing
NOTE:
All boilers are provided with one high limit pres-
sure control and at least one operating pressure control.
1. The high limit pressure control is equipped with a manual
reset feature. There is no subtractive differential scale with
this type of control
2. All pressure controls are equipped with an adjusting screw,
allowing for setting of desired operational and high limit
pressures. To reduce pressure setting, turn adjusting screw
in direction that allows indicator to point to a lower
pressure setting on the scale. To increase pressure setting
turn adjusting screw in direction that allows indicator to
point to a higher pressure on the scale
NOTE:
It is recommended that the high limit control be set
10% above the desired normal operating pressure (15 psig
boilers should be set to 13 psig)
3. Operating pressure controls, except low pressure (15 psig)
types have a separate differential scale. Differential
indicates pressure below the main operating maximum
pressure, the pressure control will re-set. The differential set
point is adjusted in the same manner by turning the
adjusting screw in the desired direction to increase or
decrease the differential pressure value.
4. Operating pressure control check: Close steam outlet valve
supplied by customer] and adjust operating pressure
Pre-Operation Check (All Boilers)
LWCO/PUMP CONTROL OPERATION AND TESTING
1. All valves for incoming water supply are to be fully opened.
Main disconnect switch is to be in the "on" position. Boiler main
switch is to be in the "on" position. Since boiler will be empty
the pump or solenoid will be energized allowing the boiler to
fill with water. Control will automatically fill boiler to proper
operating water level and the pump/solenoid will be de-
energized. Contactors will then energize, applying voltage to
the heating elements.
2. Pump switch operation – at this point water should be visible
approximately half way up the sight glass. Slowly open the drain
valve located at the bottom of the boiler. Water level in the
sight glass will begin to drop, allowing the low water cut
off/pump control to energize the feed water system. Close valve
for proper operation.
3. Low water cutout switch performance – open the drain valve
completely. Maintain this condition until water level falls within
the gauge glass enough to cause the low water cutout switch to
de-energize the heating elements. All of the contactors will be
in a de-energized or open state at this time. Close the drain
valve, water feed system will automatically refill the boiler and
the contactors will re-energize.
Boilers equipped with an auxiliary low water cut-off
control with a manual re-set button (required as
mandatory equipment is some states): once the correct
operating water level has been reached, it will be
necessary to depress the reset button in order for the
contactors to re-energize.
NOTE:
For boilers equipped with an automatic blow-
down system:
• For test 1 - the blowdown time clock must be in the
“run” mode before the boiler will automatically fill.
• For test 2 and 3 - in order for the drain valve to open
the blowdown clock must be in the “off” mode.
(See blowdown time clock insert) The automatic
blowdown indicator light will be on when the valve
is open. This light will remain on for the duration of
the blowdown cycle (a few seconds). It may be nec-
essary to cycle the time clock from the “run” to
“off” mode several times.
control to 20 psig (10 psig for low pressure boilers) and
the differential to 10 psig (Note: Low pressure boilers do
not have a differential setting). Set the high limit
pressure control to 30 psig (13 psig for low pressure
boilers). Switch boiler on to allow steam pressure to
build-up. Pressure gauge reading will increase and the
operating pressure control will de-energize the
contactor(s) when the pressure gauge indicates 20 psig
(10 psig for low pressure boilers). Open steam outlet
valve to bleed off pressure. When the pressure gauge
reading decreases below 10 psig (differential) (3 psig for
low pressure boilers) the operating pressure control will
re-energize the contactor(s).
5. High limit pressure control check: FOR TEST PURPOSES
ONLY! Set the high limit pressure control 10 psig (5 psig
for low pressure boilers) lower than the operating
pressure control. Close the steam outlet valve and switch
the boiler on to allow boiler to build pressure. When the
pressure gauge indicates the pressure at which the high
limit pressure control is set, the high limit pressure
control re-set button will pop-up and the control will de-
energize the contactor(s). Open the steam outlet valve to
bleed off pressure. The contactor(s) should not re-
energize on pressure drop. The contactor(s) should only
re-energize when the pressure has dropped and the high
limit pressure control reset button is depressed.