
Before Installing your new elements be sure the
McDonnell Miller low water cut-off an aux. low
water cutoff (if supplie ) is operating properly. The float chamber an
lower equalizer column of the MM control must be completely clear of
slu ge or other foreign matter. Failure to o this may cause the imme-
iate burn-out of the new elements. If the unit is probe equippe ,
check con ition of the probes an isolator.
All elements are thoroughly checke before shipment The manufactur-
er cannot be responsible for burn-outs cause by a faulty low water
cut-off.
The lower equalizer column can best be examine by breaking the
unions on either si e an then visually an manually examining the
piping with your finger or probes to see if it is clear an clean.
1.
Disconnect boiler from electric power supply at main safety switch or
fuse panel. Then turn boiler switch to “OFF" position.
2.
Close water supply valve on incoming water supply line.
Drain boiler completely of water.
3.
Open boiler oor to access heating element.
4.
Disconnect wire (electric) lea s connecting element to main power system of boiler.
Again, note wire connections to facilitate re-assembly. Procee to remove
an iscar (6) bolts from flange.
IMPORTANT:
Note the wire connections to facilitate re-assembly (see wiring schematic).
Remove an iscar six (5/16"-18) bolts from flange. Do not reuse these bolts.
5.
Thoroughly clean boiler flange of all foreign material. Be certain no part of ol gasket
remains on flange.
6.
Apply "Slic-Tite" Gasket Compoun (or equal) to both surfaces of new gasket supplie
with replacement element. Procee to install element flange assembly with gasket
between boiler flange an element flange. In oing this, be careful to align flange holes
so element wire connection terminals on element assembly are in line with previously
isconnecte wire lea s to facilitate easy connections.
NOTE:
Observe markings on element flange. Install element marking “TOP” on top.
7.
Use only new element flange bolts. Tighten all (6) element flange bolts to a torque value
of 22 lb-ft each (see illustration).
.
Connect all wires to the terminals. Tighten all element terminals to a torque value of
20 lb-in each (see illustration). Make sure all wires are clean an bright to assure goo
electrical contact.
9.
Check that the wires are correctly connecte to the contactor terminals an are tight-
ene to a torque value of 45 lb-in. (see illustration). Make sure all wires are clean an
bright to assure goo electrical contact.
10.
Open water valve to allow water supply to reach boiler fee mechanism.
11.
As boiler automatically refills, observe the new flange assembly for possible leaks.
If water is notice , the bolts must be re-tightene . Before oing this, turn the boiler
off at the main fuse safety switch.
12.
When boiler reaches working pressure, check flange assembly again for leaks.
Follow maintenance instructions provi e with the boiler.
ES 24A Electric Steam Generator Installation, Operation and Maintenance Manual
_____________________________________________________________________________
6
Element Replacement
Torque Values:
Element Flange Bolts: 22 lb-ft
Element Terminals: 20 lb-in
Contactor Terminals: see Torque chart
For Illustrative Purposes Only.
Power wiring shown in approximate
factory-installed location
TORQUE VALUES
________________________________________
Element Flange Bolts 22 lb-ft
________________________________________
Element Terminals 20 lb-in
________________________________________
Contactor Terminals 45 lb-in
Torque
Wrench
Torque
Wrench
Torque
Wrench
READ INSTRUCTIONS COMPLETELY BEFORE STARTING WORK
Boiler with
McDonnell Miller
11⁄2
1 Steam Equalizing Pipe
Pump and Low Water Control
Normal Boiler Water Line
Cut-Off Level is Arrow Mark
Blowdown Valve
1 Water Equalizing Pipe
!CAUTION
!CAUTION