Pr ssur Controls, Op ration and T sting
Not :
All boilers are provided with one high limit
pressure ontrol and at least one operating pressure
ontrol.
1.
The high limit pressure ontrol is equipped with a manual
reset feature. There is no subtra tive differential s ale
with this type of ontrol
2.
All pressure ontrols are equipped with an adjusting
s rew, allowing for setting of desired operational and
high limit pressures. To redu e pressure setting, turn
adjusting s rew in dire tion that allows indi ator to point
to a lower pressure setting on the s ale. To in rease pres-
sure setting turn adjusting s rew in dire tion that allows
indi ator to point to a higher pressure on the s ale
Not :
It is re ommended that the high limit ontrol be set
10psig above the desired normal operating pressure.
3.
Operating pressure ontrols, have a separate differential
s ale. Differential indi ates pressure below the main
operating maximum pressure, the pressure ontrol will
re-set. The differential set point is adjusted in the same
manner by turning the adjusting s rew in the desired
dire tion to in rease or de rease the differential pressure
value.
Installation, Operation & Maintenance Manual
8
Pr -Op ration Ch ck (All Boil rs)
LWCO/PUMP CONTROL OPERATION AND TESTING
1.
All valves for in oming water supply are to be fully opened.
Main dis onne t swit h is to be in the "on" position. Boiler main
swit h is to be in the "on" position. Sin e boiler will be empty
the pump or solenoid will be energized allowing the boiler to
fill with water. Control will automati ally fill boiler to proper
operating water level and the pump/solenoid will be de-ener-
gized. Conta tors will then energize, applying voltage to the
heating elements.
2.
Pump swit h operation – at this point water should be visible
approximately half way up the sight glass. Slowly open the
drain valve lo ated at the bottom of the boiler. Water level in
the sight glass will begin to drop, allowing the low water ut
off/pump ontrol to energize the feed water system. Close valve
for proper operation.
3.
Low water utout swit h performan e – open the drain valve
ompletely. Maintain this ondition until water level falls within
the gauge glass enough to ause the low water utout swit h to
de-energize the heating elements. All of the onta tors will be
in a de-energized or open state at this time. Close the drain
valve, water feed system will automati ally refill the boiler and
the onta tors will re-energize.
Boilers equipped with an auxiliary low water ut-off
ontrol with a manual re-set button (required as
mandatory equipment is some states): on e the orre t
operating water level has been rea hed, it will be ne -
essary to depress the reset button in order for the on-
ta tors to re-energize.
Not :
For boilers equipped with an automati
blowdown system:
• For test 1 - the blowdown time lo k must be in the
“run” mode before the boiler will automati ally fill.
• For test 2 and 3 - in order for the drain valve to open
the blowdown lo k must be in the “off” mode.
(See blowdown time lo k insert) The automati
blowdown indi ator light will be on when the valve
is open. This light will remain on for the duration
of the blowdown y le (a few se onds). It may be
ne essary to y le the time lo k from the “run” to
“off” mode several times.
4.
Operating pressure ontrol he k: Close steam outlet
valve [supplied by ustomer] and adjust operating pres-
sure ontrol to 20psig and the differential to 10psig.
Set the high limit pressure ontrol to 30psig. Swit h
boiler on to allow steam pressure to build-up. Pressure
gauge reading will in rease and the operating pressure
ontrol will de-energize the onta tor(s) when the pres-
sure gauge indi ates 20psig. Open steam outlet valve
to bleed off pressure. When the pressure gauge read-
ing de reases below 10psig (differential) the operating
pressure ontrol will re-energize the onta tor(s).
5.
High limit pressure ontrol he k: FOR TEST PURPOSES
ONLY! Set the high limit pressure ontrol 10psig lower
than the operating pressure ontrol. Close the steam
outlet valve and swit h the boiler on to allow boiler to
build pressure. When the pressure gauge indi ates the
pressure at whi h the high limit pressure ontrol is set,
the high limit pressure ontrol re-set button will pop-
up and the ontrol will de-energize the onta tor(s).
Open the steam outlet valve to bleed off pressure. The
onta tor(s) should not re-energize on pressure drop.
The onta tor(s) should only re-energize when the pres-
sure has dropped and the high limit pressure ontrol
reset button is depressed.