SUTO S320 Manual

English
Instruction and operation manual
S 320
2-channel display

Dear Customer,
thank you for choosing our product.
The operating instructions must be read in full and carefully observed
before starting up the device. The manufacturer cannot be held liable
for any damage which occurs as a result of non-observance or non-
compliance with this manual.
Should the device be tampered with in any manner other than a
procedure which is described and specified in the manual, the warranty
is cancelled and the manufacturer is e empt from liability.
The device is destined e clusively for the described application.
SUTO offers no guarantee for the suitability for any other purpose.
SUTO is also not liable for consequential damage resulting from the
delivery, capability or use of this device.
2 S 320

Table of contents
1. Safety instructions.......................................................................4
2. Application.................................................................................6
3. Features.....................................................................................6
4. Technical Data............................................................................7
4.1 General.................................................................................7
4.2 Electrical Data........................................................................7
4.3 Input-Signals.........................................................................7
4.4 Output-Signals.......................................................................7
5. Dimensional drawing....................................................................8
6. Installation ................................................................................9
6.1 Installation Requirements........................................................9
6.2 Electrical connection ..............................................................9
6.2.1 AC Power supply and alarm connection (A1640)..................10
6.2.2 DC Power supply and alarm connection (A1641).................10
6.2.3 Signals at back terminals.................................................11
6.2.4 Connection of the following sensors...................................12
6.2.5 Looping the 4... 20 mA of S 215 to a PLC...........................12
7. Configuration ...........................................................................13
8. Operation ................................................................................14
8.1 Description of display icons....................................................14
8.2 Sensor setting......................................................................15
8.3 Alarm setting.......................................................................15
8.4 System status and settings ...................................................15
8.5 Service setting ....................................................................15
9. Signal input .............................................................................15
9.1 Digital input ........................................................................15
9.2 Analog input ........................................................................15
10. Signal outputs.........................................................................16
10.1 Alarm output .....................................................................16
10.2 Interface ...........................................................................16
11. Optional e tra accessories.........................................................16
12. Maintenance............................................................................16
13. Disposal or waste.....................................................................16
14. Warranty................................................................................17
S 320 3

1. Safety instructions
1. Safety instructions
Please check if this instruction manual accords to the
product type.
Please observe all notes and instructions indicated in this
manual. It contains essential information which have to be
observed before and during installation, operation and
maintenance. Therefore this instruction manual has to be read carefully
by the technician as well as by the responsible user / qualified
personnel.
This instruction manual has to be available at the operation site of the
display at any time. In case of any obscurities or questions, regarding
this manual or the product, please contact the manufacturer.
W RNING!
Compressed air!
ny contact with quickly escaping air or bursting
parts of the compressed air system can lead to
serious injuries or even death!
•Only use pressure tight installation material.
•Avoid that persons get hit escaping air or bursting parts of the
instrument.
•The system must be pressureless during maintenance work.
W RNING!
Voltage used for supply!
ny contact with energized parts of the product, may
lead to a electrical shock which can lead to serious
injuries or even death!
•Consider all regulations for electrical installations.
•The system must be disconnected from any power supply during
maintenance work.
•Any electrical work on the system is only allowed by authorized
qualified personal.
4 S 320

1. Safety instructions
W RNING!
Permitted operating parameters!
Observe the permitted operating parameters, any
operation exceeding this parameters can lead to
malfunctions and may lead to damage on the
instrument or the system.
•Do not e ceed the permitted operating parameters.
•Make sure the product is operated in its permitted limitations.
•Do not e ceed or undercut the permitted storage and operation
temperature and pressure.
•The product should be maintained and calibrated frequently, at
least annually.
General safety instructions
•It is not allowed to use the product in e plosive areas.
•Please observe the national regulations before/during installation
and operation.
Remarks
•It is not allowed to disassemble the product.
TTENTION!
Measurement values can be affected by malfunction!
The product must be installed properly and
frequently maintained, otherwise it may lead to
wrong measurement values, which can lead to
wrong results.
Storage and transportation
•Make sure that the transportation temperature of the display is
between -20°C... 60°C.
•For transportation it is recommended to use the packaging which
comes with the display.
•Please make sure that the storage temperature of the display is
between -10°C... 50°C.
S 320 5

1. Safety instructions
•Avoid direct UV and solar radiation during storage.
•For the storage the humidity has to be <90%, no condensation.
2. pplication
The S 320 display can display all relevant parameters (flow, dew point,
pressure, temperature, power consumption, compressor status etc.) in
a compressed air system.
The S 320 display and data logger is not developed to be used in
e plosive areas. For the use in e plosive areas please contact the
manufacturer.
The S 320 display and data logger is mainly used in compressed air
systems in industrial environment.
3. Features
•Graphic display for easy user interface.
•Fle ible power supply: 100 V... 240 VAC / 50... 60 Hz or 18... 30
VDC.
•1 input for flow / dew point sensor.
•1 input for analog sensors: 0... 20 mA, 4... 20 mA, 0... 10 V.
•2 relay outputs for alarm.
•USB interface for configuration with S4C software.
•Wall or panel mountable casing.
•Optional alarm on display.
6 S 320

4. Technical Data
4. Technical Data
4.1 General
Operating temperature 0°C... 50°C
Housing material ABS
Protection class IP65
Dimensions See dimensional drawing on the ne t page
Display Graphic display, 220 140 pi els with back
light
Interface USB to PC
Keyboard 4 keys
Weight 0.52 kg
4.2 Electrical Data
Power supply 100... 240 VAC, 15 VA (option A1640)
18... 30 VDC, 15 VA (option A1641)
Sensor supply 24 V, 10 W
4.3 Input-Signals
Digital input 1 SDI for dew point and flow sensors
Analog input 1 0... 20 mA or 1 4... 20 mA or
1 0... 10 V
4.4 Output-Signals
Alarm output 2 relays, 230 VAC, 3 A
S 320 7

5. Dimensional drawing
5. Dimensional drawing
8 S 320

6. Installation
6. Installation
Please make sure that all components listed below are included in your
package.
Qty Description Item No.
1 S 320 Panel with ordered options
and if ordered with casing
D500 0320
1 Instruction manual No P/N
6.1 Installation Requirements
The instrument can either be mounted into a panel or if ordered with
the optional wall casing on a wall. Please observe the drawings in
chapter 5 for details. The housing of the S 320 must be fi ed on the
wall using suitable dowels and screws.
6.2 Electrical connection
Terminal block layout at back side
The following diagram is the terminal block layout at S 320 back side.
S 320 9

6. Installation
6.2.1 C Power supply and alarm connection ( 1640)
AC power connection: AC alarm connection:
6.2.2 DC Power supply and alarm connection ( 1641)
DC power connection: DC alarm connection:
10 S 320

6. Installation
6.2.3 Signals at back terminals
Terminal Pin Signal Description
G 8 +VbPositive sensor supply
7 -VbNegative sensor supply
6 SDI Digital communication signal from sensors
5 Iin 4... 20 mA signal from sensor
4 +P Active pulse signal from flow sensor
3 -VbNegative signal connection to PLC
2 Iout 4... 20 mA signal to PLC
1 -VbNegative signal connection to PLC
H 6 -VbNegative signal connection to PLC
2 -VbNegative signal connection to PLC
4 -VbNegative signal connection to PLC
3 -VbNegative signal connection to PLC
2 Piso Isolated pulse output pin 2, NO
1 Piso Isolated pulse output pin 1, NO
I 5 +VbPositive analog sensor supply
4 -VbNegative analog sensor supply
3 +20 mA Positive current input
2 SGND Signal ground (internally connected to -Vb of
terminal I)
1 +10 V Positive voltage input
Remarks
•In order to use the isolated pulse output at terminal H its required
to have the active pulse output of the flow sensor connected to
terminal G, pin 4.
•4... 20 mA signals from flow sensor or dew point sensors can be
looped through the G terminal pin 5 + 2. The e ternal device (PLC
or mA-meter) negative signal is connected to pin 1.
•Analog sensors are connectable to terminal I.
S 320 11

6. Installation
6.2.4 Connection of the following sensors
S 320 S 400 /
420 /
S 450 /
452
S 201 S 220 /
212
S 215 Colour
Terminal Pin Signal Pin Pin Pin Pin Pin
G 8 +VbA.3 2 A.3 3 3 blue
7 -VbA.2 3 A.2 2 2 white
6 SDI A.1 4 A.1 1 1 brown
5 Iin A.4 A.4 4 black
4 +P A.5 grey
3 -Vb
2 Iout
1 -Vb
Remark
In case the 4... 20 mA signal of S 215 is to be looped to a PLC the
connection in the ne t table should be used. The listed colour codes in
the table above are for the sensor cables.
6.2.5 Looping the 4... 20 m to a PLC
2-wire connect the sensor
S 320 S 215
Terminal Pin Signal Pin
G 8 +Vb+I of PLC
7 -Vb2 of S 215
6 SDI 1 of S 215
5 Iin -I of PLC
4 +P
3 -Vb
2 lout 3 of S 215
1 -Vb
12 S 320

6. Installation
3-wire connect the sensor
S 320 S 212
Terminal Pin Signal Pin Colour
G 8 +Vb3 +I of PLC blue
7 -Vb2 2 of S 217 white
6 SDI 1 1 of S 217 brown
5 Iin 4 -I of PLC black
4 N/A
3 -Vb
2 lout
1 -Vb
. Process voltage
input 0... 1 V or 0... 10
V
B. Process current
input 0... 20 mA or 4...
20 mA
C. loop powered 4... 20
mA sensor with supply
from S 320
7. Configuration
The S 320 is delivered with specific customer settings according to the
order.
In order to simplify the user interface not all settings but most of it are
accessible via the user interface, instead a PC software can be used.
This software is called S4C which can be downloaded from the company
web page.
S 320 13

7. Configuration
To change certain or all settings by the user, S 320 can be connected to
the PC via the USB interface. After starting S4C all device settings are
accessible.
All settings are stored permanently inside of the S 320 and do not need
to be entered again, unless the user wants some changes. Some setting
for the dew point and flow sensor can also be done at the user
interfacer of S 320.
8. Operation
8.1 Description of display icons
The display can illustrate different measurement values like shown in
the graphic. Please use the buttons for changing settings.
•Use this key to e it the current menu level.
•Use it to leave all setting state without saving the
change.
•Use this keys to browse and select different items in
menu and scroll through different pages of
measurement value display.
14 S 320

8. peration
•Use this key to alter or adjust the setting option or
numbering.
•Use this key to enter to submenu or ne t menu level
of the current selected menu item.
•To confirm the setting change or enable an option in all
setting state.
After pressing the enter button, different submenus can be selected. The
particular submenus will be e plained in the ne t chapters.
8.2 Sensor setting
After selecting “Sensors” the ne t screen will show which kind of
sensors are programmed at which terminal. Changes can be done
individually for each sensor, by selecting the terminal where the sensor
is connected to.
8.3 larm setting
The S 320 has two alarm relay outputs. It is possible to set the value
and the direction of the value for “Alarm 1” and “Alarm 2”.
8.4 System status and settings
Please press the “System” button for the following submenus:
Device Info It will show different system information like device type,
device serial number, firmware version, hardware version
etc.
LCD
Contrast
Contrast of the display can be changed.
Reset In case sensors have been changed its recommended to
use this function in order to update system settings.
Language Please choose the desired language.
8.5 Service setting
Contact information of service company ban be set in this submenu.
S 320 15

9. Signal input
9. Signal input
9.1 Digital input
The display has one sensor input for SUTO flow / dew point sensor.
9.2 nalog input
The display has one analog input for SUTO pressure / temperature
sensor or further sensors (0... 20 mA / 4... 20 mA / 0... 10 V).
10. Signal outputs
10.1 larm output
The display has two alarm relay outputs (230 VAC, 3 A).
10.2 Interface
The data can be transmitted via USB port to a data collection system or
software.
11. Optional extra accessories
The following e tra accessories are optional:
•Sensor cable 5 m with M12 connector, open wire.
•Sensor cable 10 m with M12 connector, open wire.
•Power cable with mains plug, 1.8 m.
12. Maintenance
To clean the sensor and its accessories it is recommended to use moist
cloth only.
TTENTION!
Do not use isopropyl alcohol to clean the display!
13. Disposal or waste
Electronic devices are recyclable material and do not belong in the
household waste.
The sensor, the accessories and its packings must be disposed according
16 S 320

13. Disposal or waste
to your local statutory requirements. The dispose can also be carried by
the manufacturer of the product, for this please contact the
manufacturer.
14. Warranty
SUTO provides a warranty for this product of 24 months covering the
material and workmanship under the stated operating conditions from
the date of delivery. Please report any findings immediately and within
the warranty time. If faults occurring during the warranty time SUTO
will repair or replace the defective unit, without charge for labour and
material costs but there is a charge for other service such as transport
and packing costs.
E cluded from this warranty is:
•Damage caused by:
◦Improper use and non-adherence to the instruction manual.
◦Use of unsuitable accessories.
◦E ternal influences (e.g. damage caused by vibration, damage
during transportation, e cess heat or moisture).
The warranty is cancelled:
•If the user opens the measurement instrument without a direct
request written in this instruction manual.
•If repairs or modifications are undertaken by third parties or
unauthorised persons.
•If the serial number has been changed, damaged or removed.
Other claims, especially those for damage occurring outside the
instrument are not included unless responsibility is legally binding.
Warranty repairs do not e tend the period of warranty.
TTENTION!
Batteries have a reduced warranty time of 12
month.
S 320 17
Other manuals for S320
1
Table of contents
Other SUTO Data Logger manuals
Popular Data Logger manuals by other brands

Onset
Onset HOBO Micro Station quick start

Axiometrix Solutions
Axiometrix Solutions imc C Series manual

MadgeTech
MadgeTech HiTemp140X2 Series Product user guide

HyQuest Solutions
HyQuest Solutions iRIS 350FX user guide

AquaFlex
AquaFlex Cellular Hub user manual

DeltaTRAK
DeltaTRAK FlashLink 40527 quick start guide