System air DVCompact User manual

DVCompact
SupplyUnit
CommissioningRecord
Documentinoriginallanguage208384-EN_GB
2013-12-11A001

1CommissioningInstructions
General
Systemairassembliesaretestedandfunctiontestedatthefactorybeforedelivery.Theautomationis
factorypresetandaspecialdocumenttitledTestandcontrolchartaccompaniesaggregatesupply(acopy
ofthedocumentisalsoledwiththemanufacturer).Thischartshowsthesettingsapplied.
Athoroughinspectionoftheunitisdonebythemanufacturerbeforedelivery.Theunitshouldstillbe
checkedagainbyanelectricianbeforedeployment.
Itisimportantthatanychangestosettingsrecordedinthecommissioningprotocol.
Fig.1Regulator
Beforestartingtheunit
•Theunitsaredeliveredinsections,ttedwithquickconnectorsforthecontrolandmotorcables
betweeneachsection.Makesurethatthesecouplingsareconnected.
•DVCompactisequippedindifferentways,forexample,withwaterheaterorelectricheatingcoil.The
controlunitisttedwithcablestowedoutoftheunit.Makesurethatthesecablesareconnected
accordingtotheschedule.Theunitsaresuppliedwithamasterswitch,whichisalsothepointat
whichtheelectricianwillconnecttheunittothemains.Checkvoltage-measurebetweenallphases
andbetweenallphasesandearth.ElectricHeatingBatteriessuppliedforaseparatepowersupply.
Alsocheckallphases.
•Supplyairsensorismountedinthechannel.Checkthatthissensorisnotdamagedandisfarenough
awayfromtheheatingcoil.
•Controlpanelwithdisplayisincludedwiththedelivery(pickledinthecabinet)andshallbeconnected
tothebuscable.
Turnonmainswitchandfusesintheelectricalcabinet.Waitafewminuteswhilethecontrolpanelloadsall
values.Anyerrormessagesisshownonthedisplay.
Theunitshouldnowbereadytostart.
DVCompactCommissioningRecord
2083841SystemairAB

2CommissioningProtocol
Company:
Responsible:
CustomerDateInstallation
Object/UnitItemInstallationaddress
ModelSerialnumber
Timeanddateset:Weeklyprogramset:
Externalconnections(sensors,dampers,externalalarm,etc.)performed:
FunctionDefaultsettingSetvalue
Temp.(°C)
RegulatoryFunction
Temp.SupplyRoomSupplyRoom
Outsidecompensatorysupplyairtemp.Outsidecompensatorysupplyairtemp.
Outdoortemperature
compensation(supply
air)
Setpoint21,0°C°C
Breakpoint1,2and3-20,0/25,0-10,0/23,0//
Breakpoint4,5and6-5,0/23,05,0/20,0//
Breakpoint7and810,0/18,0/
Lowsetpointsupply
air14,0°C°C
Highsetpointsupply
air30,0°C°C
Temperaturefor
switchingbetween
supply-andcascade
control13,0°C°C
DVCompactCommissioningRecord
2083842SystemairAB

FunctionDefaultsettingSetvalue
Airow
FancontrolAirow(m3/h)Airow(m3/h)
Pressure(Pa)Pressure(Pa)
Setpointnormal1InletfanInletfan
Setpointreduced1InletfanInletfan
Outdoor
temperature
compensationLowerpoint-22°C-500m3/hLowerpoint°Cm3/h
Higherpoint3°C0m3/hHigherpoint°Cm3/h
1.Theairowandpressureisaccordingtothecalculationinthetechnicaldescription
Settingtheweeklyprogram
•Timesfornormalandreducedfanspeedisfactorysetasshownbelow.
•Period1.07:00to16:00MondaytoFriday,normalfanspeed.00:00to00:00Saturday-Sundayand
holidays.
•Period2.00:00to00:00MondaytoSundayandpublicholidays.00:00to00:00offperiod.
•OBS!Normalfanspeedhaspriorityoverareducedfanspeed.
WeekdayPeriodNormalfanspeedReducedfanspeed
Monday1:—::—:
2:—::—:
Tuesday1:—::—:
2:—::—:
Wednesday1:—::—:
2:—::—:
Thursday1:—::—:
2:—::—:
Friday1:—::—:
2:—::—:
Saturday1:—::—:
2:—::—:
Sunday1:—::—:
2:—::—:
Holiday(month.day)Holiday(month.day)Holiday(month.day)Holiday(month.day)
1..—.7..—.13..—.19..—.
2..—.8..—.14..—.20..—.
3..—.9..—.15..—.21..—.
4..—.10..—.16..—.22..—.
5..—.11..—.17..—.23..—.
6..—.12..—.18..—.24..—.
DVCompactCommissioningRecord
2083843SystemairAB

FunctionDefaultsettingSetvalue
NightCooling
LocationOnOffOnOff
Activationatoutdoor
temperatureshigherthan22°C°C
Stoppedatoutdoornight
temperatureshigherthan15°C°C
Stoppedatoutdoornight
temperatureslowerthan5°C°C
Stoppedatroomtemperatures
lowerthan18°C°C
CO2—adjustment
ActiveNeverAtofftimechannelNeverAtofftimechannel
AlwaysAtontimechannelAlwaysAtontimechannel
Shortestrunningtime20minmin
ActivationLevelHalfspeed800ppmHalfspeedppm
Fullspeed1000ppmFullspeedppm
Difference(below
half-speed,fanstops)160ppm
Difference(below
half-speed,fanstops)ppm
FireFunction
SupplyfansatreNoYesNoYes
FireentrySealingSealing
BreakingBreaking
FunctionDefaultsettingSetvalue
HWHeatPump
Pumpend(generatingsetsoff)OnOffOnOff
StopDelay5minmin
Pumpstopatoutdoor
temperature10°C°C
Hysteresis1°C°C
Hoursforexercising15hh
Cooling,coldwaterpump
StopDelay5minmin
Other
Extendedoperation60minmin
DVCompactCommissioningRecord
2083844SystemairAB

AlarmsettingsDef.settingSet
value
AlarmsettingsDef.settingSetvalue
1.Malfunction,supplyfan10.MoistureDeviation
ClassAClassNot
active
Delay120sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
2.Malfunctinl,P1–heat,
HW-pump
(HW-units)
11.Highinletairtemperature
ClassNot
active
ClassB
Delay5sDelay300s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
Highinletair
temperature
35°C
3.Malfunction,P1–cooling
(Coldwaterpump)
12.Lowinletairtemperature
ClassNot
active
ClassA
Delay5sDelay300s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
Lowinletair
temperature
35°C
4.Filterguard13.Inletfan,upperlimit
ClassBClassNot
active
Delay180sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
5.Pressuresensor14.Inletfan,lowerlimit
ClassNot
active
ClassNot
active
Delay5sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
6.Externalfreezeguard15.Highroomtemperature
ClassNot
active
ClassNot
active
Delay0sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
Highroomtemperature30°C
7.Firealarm16.Lowroomtemperature
ClassAClassNot
active
Delay0sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
Lowroomtemperature10°C
8.Externalswitch17.Overheating,electricheating
(OffonHW-units)
ClassCClassA
DVCompactCommissioningRecord
2083845SystemairAB

AlarmsettingsDef.settingSet
value
AlarmsettingsDef.settingSetvalue
Delay0SDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmYes
9.Externalalarm18.Freezeprotection
ClassBClassNot
active
Delay0sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
AlarmsettingsDef.settingSet
value
AlarmsettingsDef.settingSetvalue
19.Lowfreezeprotection
temperature
(AppliestoHW-units)
27.Inletfan,freq.conv.manual
ClassAClassNot
active
Delay0sDelay0s
TheunitstoppedatalarmYesTheunitstoppedatalarmNo
Freezing
limit
2°C
20.Sensorfailure28.Heatingcoilinmanualmode
ClassBClassNot
active
Delay5sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
21.Firedampers29.Coolingcoilinmanualmode
ClassNot
active
ClassNot
active
Delay0sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
22.Inletfan,controlerrors30.P1–heatinmanualmode
(OnlyforHW-units)
ClassBClassNot
active
Delay15minDelay0s
TheunitstoppedatalarmYesTheunitstoppedatalarmNo
Largestdiff.betweenmust
/isvalue
200Pa
23.Inletfan,external
operating
31.P1–Coolinginmanualmodee
ClassNot
active
ClassNot
active
Delay1200sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
24.Ventilationinmanual
modee
32.Firedampersmanual
ClassNot
active
ClassNot
active
Delay0sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
DVCompactCommissioningRecord
2083846SystemairAB

AlarmsettingsDef.settingSet
value
AlarmsettingsDef.settingSetvalue
25.Supplyaircontrolin
manualmodel
33.Erroroninternalbattery
ClassNot
active
ClassA
Delay0sDelay0s
TheunitstoppedatalarmNoTheunitstoppedatalarmNo
26.Supplyfaninmanual
mode
ClassNot
active
Delay0s
TheunitstoppedatalarmNo
DVCompactCommissioningRecord
2083847SystemairAB

lastpage
SystemairABreservestherighttomakechangesandimprovementstothecontents
ofthismanualwithoutpriornotice.
SystemairAB
Industrivägen3
SE-73930Skinnskatteberg,Sweden
Phone+4622244000
Fax+4622244099
www.systemair.com
208384
Other manuals for DVCompact
1
Table of contents
Popular Power Supply manuals by other brands

Altronix
Altronix TROVE T1MK1F4D installation guide

Larson Electronics
Larson Electronics BPLI-400W user manual

Rockwell Automation
Rockwell Automation Allen-Bradley 1606-XLE120ED installation instructions

Kikusui
Kikusui PWX Series quick start guide

Teledyne
Teledyne Battery-Backed Power Supply Installation and operation guide

ENERMAX
ENERMAX Platimax EPM500AWT user manual