EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 109.12.19
Installation manual for
EVC-RZHC-HUB Room/Zone-Hub with cabinet
The room / zone hub is designed for the connection of a room controller,
two volume flow controllers with actuator LMVAX-D3-MOD, a CO2, VOC
or humidity sensor, a heating and cooling valve, a change-over sensor, a
presence detector and a condensation monitor or window contact.
The Hub module is used to supply power to the connected actuators and
sensors, as well as signal distribution. Factory-made, the hub is
delivered in a surface-mounted housing.
After removal from the housing, the base board is also suitable for
mounting on DIN rail
Dimensions (mm)
Technical data
Supply voltage
DC 48 V
Possible operating range
30 … 48 V DC
Power Consumption
4 W (without connected devices)
Operating temperature range
0 … +40°C
Relative humidity during operation
10 … 90% r.H., non-condensing
Storage conditions
-20 … +40°C, non-condensing
Protection class
III safety extra-low voltage
Enclosure class
IP30 (IP00 without housing)
Mounting location
Wall or ceiling, switch cabinet
Mounting
Screw or DIN rail mounting
Weight
ca. 500 g
Dimensions with housing
160 x 140 x 65 mm
Dimensions without housing
110 x 100 x 40 mm
Electrical connection to master cabinet EVC-MC
1x RJ45, DC supply >30 V and Modbus RTU, network cable
type SF/UTP, min. Cat.5e,AWG 26/7, max.150 m, alt.
Network cable Type S/FTP, Cat.7,
AWG 23, max. 250 m
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 209.12.19
Electrical connection to room controller RC-C3DOC
2x Microfit, DC supply 24V, Modbus RTU and Signal wires,
cable EVC-RCC-10 Room controller-connection cable 10m
or EVC-RCCE-10 extension cable 10m for EVC-RCC-10,
max. 50 m
Electrical connection to volume flow controller supply air and extract air
2x RJ12, DC supply 24V and Modbus RTU,
Cable EVC-DC-10_Damper-connection cable 10 m, max. 30
m
Electrical connection to CO2, VOC, RH- Sensor, heating valve, cooling
valve, Change-Over Sensor, presence detector, condensation sensor,
window contact
Screw terminals, 1,5 mm², 3x 4-pole, 1x 3-pole, 2x double-
pole
Before installation and operation, these instructions must be read and all
instructions given must be observed!
Important information:
- If the device is operated outside the specification range, all warranty claims are void.
- This device is only to be used for the specified purpose. The corresponding safety regulations of the VDE,
the federal states, their monitoring bodies, the TÜV and the local power supply companies must be observed.
- The buyer must ensure compliance with the construction and safety regulations and avoid all types of
hazards.
- For defects and damages caused by improper use of this device, no warranties and liability will be
assumed.
- Consequential damages caused by faults on this device are excluded from warranty and liability.
- The devices may only be installed by qualified personnel.
- Only the technical data and connection conditions of the assembly and operating instructions supplied with
the device apply. Deviations from the catalogue presentation are not additionally listed and are possible in the
sense of technical progress and continuous improvement of our products.
- If the user modifies the devices, all warranty claims are void.
- The housing and housing accessory dimensions may have small tolerances to the specifications in these
instructions.
- Changes to these documents are not permitted.
- Please, also observe the operating and assembly instructions of all components to be connected.
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 309.12.19
1. Mounting
1.1 Surface mounting
Factory-made, the hub is delivered in a surface-mounted housing. The distances between
the holes for wall mounting are shown in the drawing below.
Alternatively, the base board can be removed from the housing. The board is then suitable
for mounting on a DIN rail.
2. Connection of the RZHC-HUB to the master cabinet EVC-MC
A free network port of the main switch cabinet EVC-MC is connected to the RZHC-HUB at
the "Controller BACnet/Modbus" port.
Connection via RJ45 network cable.
Total cable length: max. 150 m (AWG 26/7)
Alternatively, a network installation cable + network connector RJ45 can also be used for
on-site assembly. Total cable length: max. 250 m (AWG 23)
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 409.12.19
3. Fitting ASRC-1 adapter set to RC-3DOC room controller
The circuit boards (Fig. 1) must be inserted into the lower part (Fig. 2) of the room
controller and the screws must be tightened carefully.
Fig. 1 Fig. 2 front view back view
3.1 Connect the RC-C3 DOC Argus Room Controller to the RZHC-HUB
with cable EVC-RCC-10 Room controller connection cable 10m or EVC-RCCE-10
Extension cable 10m for EVC-RCC-10, total cable length: max. 50 m
The connection cable is connected to the room controller and to the RC sockets of the hub
If the cable is laid under plaster, an empty pipe with a diameter of ≥23 mm is
required!
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 509.12.19
GD0
GD0
G0
G
G0
G0
G
UO3
UO1
UO2
UO3
UO1
UO2
RS485(A)
RS485(A)
RS485(B)
RS485(B)
AI1
AI1
AI2
AI2
AGND
AGND
+C
+C
DI2/CI
DI2/CI
DI1
DI1
socket assignment RZHC-HUB connector block assignment RC-C3 DOC
4. Connection Volume Flow Controller Optima-R with LMVAX-D3-MOD to RZHC-HUB
The volume flow controllers are each
connected to the RZHC hub with a 10 m EVC-
DC-10 damper connection cable,
total cable length: max. 30 m
- Connect exhaust air volume flow
controller to VAV ETA socket
- Connect supply air volume flow
controller to VAV SUP socket
5. connection CO2, VOC or humidity sensor to the RZHC-HUB
with a cable, total cable length: max. 50 m
Only one CO2/VOC/humidity sensor can be connected per hub. The connection of the
respective sensor to the hub is described in the following section
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 609.12.19
5.1 CO2 Sensors
CO2 sensors are connected to the terminal block CO2/VOC according to the wiring
diagrams below.
5.1.1 Connection of the wall-mounted CO2 sensor #14904
5.1.2 Connection of the wall-mounted CO2 sensor with display #14905
5.1.3 Connection of the CO2 duct sensor #14906
5.2 VOC Sensors
VOC sensors are connected to the terminal block CO2/VOC according to the wiring
diagrams below.
5.2.1 Connection of the wall mounted VOC-Room sensor #156812
5.2.2 Connection of the VOC-duct sensor #156813
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 709.12.19
5.3 Connection of the RH-duct sensor #13756
RH sensors are connected to the terminal block CO2/VOC according to the wiring diagram
below.
6. Connection of a cooling or heating valve to the RZHC-HUB
with a cable, total cable length: max. 50 m
6.1 Cooling valve:
Cooling valves are connected to the CV terminal block as shown in the wiring diagrams
below.
6.1.1 Actuator 0-10V
6.1.2 Actuator 2-Point
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 809.12.19
6.2 Heating valve:
Heating valves are connected to the HV terminal block as shown in the wiring diagrams
below.
6.2.1 Actuator 0-10V
6.2.2 Actuator 2-Point
7. Connection of a Change-Over Sensor #7284 to the RZHC-HUB
with a cable, total cable length: max. 15 m
Change-over sensors are connected to the terminal block COS according to the wiring
diagram below.
8. Connection of a presence detetector #6995 to the RZHC-HUB
With a cable, total cable length: max. 50 m.
Presence detectors are connected to the PD terminal block according to the wiring
diagram below.
EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019 909.12.19
9. Connection of a condensation sensor #63357 to the RZHC-HUB
With a cable, total cable length: max. 50 m.
Condensation sensors are connected to the terminal block CD according to the wiring
diagram below.
10. EU Declaration of Conformity
This product carries the CE Mark. For more information please visit
www.systemair.de
Contact
Systemair GmbH
Seehöfer Straße 45
97944 Boxberg
Germany

Other System air Switch manuals

System air Fantech RTS-W Installation instructions

System air

System air Fantech RTS-W Installation instructions

Popular Switch manuals by other brands

Subject Link RPT-1008G-X2 Hardware user manual

Subject Link

Subject Link RPT-1008G-X2 Hardware user manual

ZLG CANSwitch-AF2S2 user manual

ZLG

ZLG CANSwitch-AF2S2 user manual

API APD 1600 instructions

API

API APD 1600 instructions

Alcatel-Lucent OmniStack 6200 Brochure & specs

Alcatel-Lucent

Alcatel-Lucent OmniStack 6200 Brochure & specs

QUBINO LUXY smart light quick start guide

QUBINO

QUBINO LUXY smart light quick start guide

EMC Connectrix B Series Hardware reference manual

EMC

EMC Connectrix B Series Hardware reference manual

Panasonic WJMS424 - QUAD UNIT operating instructions

Panasonic

Panasonic WJMS424 - QUAD UNIT operating instructions

Hawking PN1616ES Specifications

Hawking

Hawking PN1616ES Specifications

Altusen KM0032 user manual

Altusen

Altusen KM0032 user manual

Cisco SRW2008MP Firmware upgrade FAQ

Cisco

Cisco SRW2008MP Firmware upgrade FAQ

Avaya P113F installation guide

Avaya

Avaya P113F installation guide

GeoVision GV-APOE0410-E user manual

GeoVision

GeoVision GV-APOE0410-E user manual

Panasonic AW-HS50N operating instructions

Panasonic

Panasonic AW-HS50N operating instructions

PI Manufacturing HDMI-401-MS Operation manual

PI Manufacturing

PI Manufacturing HDMI-401-MS Operation manual

ENSA ENSA-PS1 instruction manual

ENSA

ENSA ENSA-PS1 instruction manual

HP FlexFabric 12900E series Command reference

HP

HP FlexFabric 12900E series Command reference

ZyXEL Communications VDSL SWITCH VES-1616F-3X user guide

ZyXEL Communications

ZyXEL Communications VDSL SWITCH VES-1616F-3X user guide

METREL A 1507 instruction manual

METREL

METREL A 1507 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.