Gas airtight suspended warm air heaters - EOLO
10
SYSTEMA S.p.A.
Rev. 10EE0112
3.3 Main control and safety components on the appliance
a) Electronic control nit: one for all models. This controls opening of the gas solenoid valve and
ignition of the burner. After receiving the electrical signal from the ambient thermostat, it checks
that the pressure switch is operating normally (ignition is not enabled unless this check is passed).
It then enables prewash of the combustion chamber (4 exchanges) and then ignition by means of
a spark. If the flame is not detected (ionization probe) within the safety time the appliance shuts
down. To restart it wait a few seconds and press the specific reset button with LED on the control
board.
CONTROL UNIT TECHNICAL SPECIFICATIONS
Make ............................................................ BRAHMA ........................ BRAHMA
Mod .............................................................. CM 31 F.......................... CM 32 F
Supply voltage .............................................. 220 240 V 50 60 Hz ....... 220 240 V 50 60 Hz
Utilization temperature .................................. de -20 °C à + 60°C .........de -20 °C à + 60°C
Prewash time ............................................... 20 sec ............................. 20 sec
Safety time at start-up .................................. max 10 sec ..................... max 10 sec
Safety time at shut-down .............................. < 1sec ............................. < 1 sec
b) Differential press re switch: the aim of this is to interrupt operation of the appliance if the flow rate
of the fan-exhaust fan is insufficient caused either by a fault in the fan or by clogging in the combustion
circuit (combustion air duct, combustion chamber, heat exchanger, combustion products discharge),
both of which can be caused by bad combustion CO forming above the permitted limits. This is
located inside the compartment which houses all the control components, and detects, by means
of two silicone tubes, both the pressure in the combustion air suction duct and the pressure inside
the burner box in which the combustion torch is located. The difference between the two pressure
values with the exhaust fan operating is the control signal for safe and correct combustion.
PRESSURE SWITCH SPECIFICATIONS
Make ..................................................................................................... HUBA CONTROL
Code ...................................................................................................... 605.99501
Assembly position ................................................................................. vertical
Max. working pressure .......................................................................... 5000 Pa
Reset point (opening) ............................................................................ 110 Pa (+ - 16 Pa)
Pneumatic connection ........................................................................... Ø 6,2 mm
Utilization temperature ........................................................................... -30°C, +85°C
c) Gas valve: this is multifunction and multigas with double safety solenoid valve (connected in series)
in class B. Provided with a pressure regulator, slow ignition device and gas filter. Located on the
aluminium body are the threaded gas inlet-outlet connection ½ RP UNI-ISO 7, with relevant pressure
inlet and outlet. Gas valve adjustment and the only maintenance operation that can be performed
on the valve (replacement of the coils) must only be executed by qualified technicians.
GAS VALVE TECHNICAL SPECIFICATIONS
Make ..................................................................................................... SIT CONTROLS
Mod. ...................................................................................................... 830 TANDEM
Supply voltage ....................................................................................... 220 240 V 50 60 Hz
Degree of electrical protection ............................................................... IP 54
Closing time .......................................................................................... < 1s
Utilization temperature ........................................................................... 0° ÷ +60 °C
-20° ÷ +60 °C (on request)
Range of output pressure ...................................................................... 3 ÷ 50 mbar