DANGER
HIGH VOLTAGE
Dangerous Voltages Inside !
No user serviceable parts inside
Do not remove covers
Dangerous internal voltages exceeding
400 Volts - DO NOT REMOVE COVERS !
Equipment must be installed & serviced
by suitably qualied service personnel in
a restricted access area.
General
These power supplies are designed for indoor use only.
TPS12-10DC models are high performance, extremely low noise, Dual Channel Switch Mode power supplies offering 12Vdc at 10A
continuous.
When operating from mains, these models provide an output of 12Vdc ( to power connected equipment) and are configured with a
separate 13.8Vdc battery charging channel. Available battery charge current is 1.4A @ 13.8Vdc (total supply output current 11.4A )
In the event of mains failure, battery voltage is clamped to 12Vdc and instantaneously powers the load - this is particularly useful for
powering voltage sensitive loads such as CCTV cameras.. When the mains voltage is restored, batteries are disconnected from the load
and recharging commences automatically.
Output short-circuit and overload protection are provided . Removal of the fault / short circuit condition will return the power supply
to normal operation ( Auto-Reset ).
Model Variants
TPS12-10DC Single 10A Output - Supply only - no cabinet (273L x 145W x 80H )
TPS12-10DC-B Single 10A Output - Medium steel enclosure ( 340W x 436H x 145D mm )
TPS12-10DC-BD10 10 x 1A Outputs - Medium steel enclosure ( 340W x 436H x 145D mm )
TPS12-10DC-BD20 20 x 500mA Outputs - Medium steel enclosure ( 340W x 436H x 145D mm )
TPS12-10DC-ME Single 10A Output - Large steel enclosure ( 482W x 470H x 185D mm )
TPS12-10DC-MED10 10 x 1A Outputs - Large steel enclosure ( 482W x 470H x 185D mm )
TPS12-10DC-MED20 20 x 500mA Outputs - Large steel enclosure ( 482W x 470H x 185D mm )
TPS12-10DC-MED40 40 x 250mA Outputs - Large steel enclosure ( 482W x 470H x 185D mm )
Connection
10-way removable terminal block provides the following:
( See over the page for a layout )
* 12Vdc Output
* 13.8Vdc Output for SLA (Sealed Lead Acid) Batteries
* Battery Test load (not used on this model)
* AC OK Relay Output ( SPST )
* Battery Fault/Low Battery Relay Output ( SPST )
12Vdc Output is via individually fused outputs ( 10, 20 or 40 )
10-way removable terminal block provides the following:
( See over the page for a layout )
* 13.8Vdc Output for SLA (Sealed Lead Acid) Batteries
* Battery Test load (not used on this model)
* AC OK Relay Output ( SPST )
* Battery Fault/Low Battery Relay Output ( SPST )
Caution when handling batteries:
Exercise care when terminating and connecting batteries. Mishandling or short circuit of SLA batteries can cause severe damage and fire.
TPS12-10DC_Rev B.pdf www.tacpower.com.au