8-Way Relay Card (TS1041)
Installation Sheet
Description
An 8-Way Relay Card (TS1041) adds relays to the
Challengerseries panels,IntelligentAccess Controllers,
Network Access Controllers or to standard DGPs.
In mostinstances,theTS1041 card adds eightrelays.
However, thefirst TS1041 card connected to aChallenger
series panel provides only seven relays becauserelay 2 is the
panel’s strobe output.
A series of interconnected TS1041 cards can be used to
expand the number of relays (outputs) at the panel’s or the
DGP’s address, as permitted by the Challenger numbering
system and by practical limitations.
For practicality, the workablelimitfor a series of physical relays
is 512, which limits the number of 8-way relay controllers to a
total of 64. This is limited to the specification of the Challenger
panel.
Product contents
Quantity
Item
1
TS1041 8-Way Relay Card with 10-way cable
2
2-wayplug on screw terminal
8
3-wayplug on screw terminal
7
M3x10 pan-head Phillips screw
6
PCB support stand off
1
Ring terminal
1
Installation Sheet
Inspect the packageand contents for visible damage. If any
componentsaredamaged or missing,do notusetheunit;
contactthesupplierimmediately.Ifyou need to return the unit,
youmust ship itin theoriginalbox.
Installation
TS1041 cards are mounted on standoffs (supplied)using
M3 x 10 mm pan head screws (supplied)insideaDGP
enclosure or aseparate enclosure.The TS1041 PCB is
size ‘BB’.
NOTICE! A qualified serviceperson,complyingwith all
applicablecodes,shouldperformall required hardware
installation
Figure 1: TS1041 layoutand connectors
1.
Data and powerconnection fromChallengerpanel,Intelligent
AccessController, Network Access Controller, standard DGP, or
from a TS1041 card via ten-way LEV8-10-500P cable (supplied).
2.
Optional+12 and 0V powerterminalswhen using an external
powersupplyorheaviergauge cable than thesupplied10-way
ribbon. If used, remove the powerfromthe ten-way cable (see
“Wiring” on page 2).
3. Optional + and –auxiliarypowerterminalsare separate fromthe
+12 and 0V powerterminals. The AUX terminalsmay be used to
supply the relays’ common contacts to + or – voltage, as set by
the relays’ links. 48 VDC maximum.

2 / 2
P/NMAINST-TS1041 • REV 1.4 • ISS 1.4
4.
Links (for each relay)to connect + or –auxiliarypowerto the
relays’ common contacts, if required.
5.
LEDs (for each relay)to indicate when the relayis active.
6.
Data and powerconnection to a TS1041 card.
7.
Eight single-pole relayswith connection terminalsto the common
(C), normally open (NO),and normallyclosed (NC) contacts.
8.
M3 threaded earth terminal.
To install the card:
1. Disconnecttheplug pack and battery fromthe panel or
DGP.
2. Insertsix standoffs (supplied)into theDGPenclosureor a
separate enclosureata location suitablefor theten-way
cable to connectthecard to thecontrol panel,DGP,or
other card,as needed.
3. Use six M3 x 10 pan head screws to fix the card to the
standoffs.
4. Connecttheten-way cable to the controlpanel,DGP,or
other TS1041 card.
5. Connecttherelay cables to the card as required.
6. Reapply power to thepanel or DGP.
Configure theChallenger series panel,IntelligentAccess
Controller, or standard DGP accordingly:
•If connectingto a Challenger series panel, setthe value of
System Options >Relay Controllers to avalue greaterthan
0 where 1 represents every 8 relays available.
•If connectingto an IntelligentAccess Controller /Network
Access Controller,setthevalue of Controller Options >
Relay Controllersto avalue greater than 0 where 1
represents every 8 relays available.
•If connectingto astandard DGP,set the configuration DIP
switch segment6 to ON.
Wiring
Connectthecard viathe IN connector,usingthesupplied
ten-way cable, to oneof thefollowingdevices (the
connector number varies with the device):
•J14 on a Challenger series panel
•J21 on a 4-Door or 4-Lift Controller
•J8 on a standard (TS0820 orTS0824) DGP
•J200 on a Network Access Controller
•Out connector onaTS1041 card
8-Way Relay Cards may be daisy chained together.
The IN connectorofonecard is connected to theOUT
connector ofanother.See theSpecification tablefor
the number of daisy chainedcards supported by each
device.
Chains of1 or 2 cards may be powered fromthe parent
devicelisted above.The+12V link on theparentdevice
must be closed with ajumper.
Chains of3 ormore cards must be supplied with +12V
from an external supply to thepowerinputterminals
(Figure1, item 2). The+12V link on theparentdevice
must be open (jumper removed).
8-Way Relay Cards must be earthed (Fig 1, item 8).
Before you begin:
•Upon being powered up,relay cards may take up to 15 seconds to
activate
•If relays are powered externally and power to thepanel is lost,the
state ofall relays will reset(turn off)after 30 seconds
•Relays will indicatebut notreliably operatewhen voltageis less
than 9.5V
Specifications
Voltage
13.8 VDCsupplied by Challengerpanel,
DGP, or auxiliarypowersupply
Number of relays
Eight NO or NC dry contact relays
Contact rating
1 A at 0 to 30 VDC, reducing to 300 mA at
48 VDC
Current
Standby
All relaysactive
50 mA
250 mA at 13.8 VDC
Challengerpanelmax.
32 ~ 64cards (practicallimitation)
4-Door/ Lift max.
2 / 32cards (practicallimitation)
Standard DGP max.
2 cards
Connection
10-waycable (supplied)
Dimensions (W × H)
Tecom ‘BB’ size (176 x 52 mm)
Regulatory Information
Manufacturer
Carrier Fire & Security Australia Pty Ltd
10 Ferntree Place
Notting Hill, Victoria 3168
Yearof manufacture
Manufacture date can be determinedby the
serial number:
276YYDDDNNNN
276:Product code forTS1041
YY:2 digit year format (eg 19 = 2019)
DDD: 3 digit day of year(eg 014 = Jan 14)
NNNN: 4 digit production number
Compliance
ACMA C-tick forAustraliaand
NewZealand
NOTICE! This is a Class A product. In a domestic environment this
product may cause radio interference in which case the usermaybe
required to take adequate measures.
Disclaimer
The customer is responsiblefor testing and determiningthe
suitability ofthis productfor specific applications.In no eventis
Carrier Fire & Security Australia responsible or liable for any
damages incurred by the buyer or any third party arisingfrom
its use, or their inability to usethe product.
Contact information
For contactinformation, see www.firesecurityproducts.com.au.