
REFRIGERATION PIPING
Pipe Connection Sizes & Type
Liquid : 16 mm OD (5/8") sweat
Suction : 35 mm OD (11/8") sweat
The ISD is shipped from the factory with
a pressurised holding charge of nitrogen.
Immediately before removing any brazed
pipe connection's seal, reduce holding
charge to atmospheric pressure.
Warning: failure to do so may cause injury.
Refer to the Outdoor Unit 'Installation &
Maintenance' pamphlet for evacuation
procedure and piping requirements.
ELECTRICAL WIRING
The electrical supply required (via the
Outdoor Unit) is specied on the Outdoor
Unit's wiring diagram.
Electrical work must be carried out by a
qualied electrician in accordance with local
supply authority regulations and the wiring
diagram.
In a free blow or low resistance application,
beware of exceeding the fan motor's full
load amp limit (refer Outdoor Unit's wiring
diagram).
To make the indoor fan switch off during
de-ice cycle, refer to the Outdoor Unit wiring
diagram for the appropriate changes.
INDOOR FAN SPEED
The fan speed is continuously variable
via the 0-10V DC control signal applied
between terminals 'FAN GND' and '0–10V'.
Once the maximum design air ow has been
set (refer Commissioning), the fan speed
can be controlled as follows:
1. ON/OFF
a.) Connect 24V a.c. control signal to
either 'LOW 24', 'MED 24V' or 'HIGH
24V', and 'COM 24V',
or
b) Wire a N/O control relay contact (or
switch) between 'FAN 10V' and '0–10V'.
2. Variable Speed
Apply an external variable 0–10V DC
control voltage to '0–10V' terminal.
Connect 0V reference to 'FAN GND'.
COMMISSIONING
Indoor Unit
1. Check that the thermostat is
correctly wired and set at the desired
temperature.
2. Link terminals 'FAN 10V' to '0–10V'.
Adjust the 'POT' to deliver your
maximum design air ow. Remove link
'FAN 10V' to '0–10V' when fan speed
has been set.
2. Check that any air lter (if tted) is
clean.
3. Check that the fan runs freely without
vibration.
4. Check the airow at each air outlet
(diffuser) and adjust if necessary.
5. Check condensate drain for free
drainage.
6. Run the unit in cooling mode and
heating mode.
MAINTENANCE
Weekly For First Four Weeks
1. Check air lter (if tted); vacuum clean as
necessary.
2. Check condensate drain for free
drainage.
Monthly
Check air lter (if tted); vacuum clean as
necessary.
Six Monthly
1. Check condensate drain for free
drainage.
2. Check heat exchanger coil; vacuum or
brush clean as necessary.
3. Check the tightness of the fan motor
mountings.
4. Check that fan motor is free running.
5. Check tightness of electrical connections.
6. Check air supply at diffuser outlets.
WARNING
This unit is designed for use ONLY with the
refrigerant HFC-410A (R410A). The use
of other refrigerants is NOT authorised or
approved by the manufacturer and may
cause operational problems such as poor
performance and efciency, loss of capacity,
degradation of materials and refrigerant
leaks.
The use of ammable or explosive
materials as a refrigerant creates the
additional risks of re and explosion
which may result in property damage,
personal injury or death.
NOTE
The manufacturer reserves the right to
change specications at any time without
notice or obligation. Certied dimensions
available on request.