- 4 -
combination of dry and wet bulb temperatures) so that free
cooling is used without adding any heat load to the building.
Control by dry bulb temperature alone is not recommended
as often, even though the outdoor dry bulb temperature may
be lower than that of the space, the total heat content of the
air can be higher thereby adding heat load in the form of
moisture content to the space.
If dry bulb temperature is used as the control method the
temperature must be set several degrees lower than the
space temperature to reduce the possibility of extra heat
load being introduced.
An Air Quality (CO2) sensor (supplied by others) can be
used to proportionally control the fresh and return air
dampers (via the control system).
In all situations the UC8 Unit Controller will allow the
compressors to operate with the economiser fresh air
damper open providing the refrigeration system is not
compromised.
The compressor(s) could be stopped from operating by
normal protection devices such as low suction temperature/
pressure or indoor coil frost protection and too many trips
of either fault could lead to a lock out of the compressor(s)
operation. Should this occur then a review of the control
settings may be necessary.
6. START-UP PROCEDURE
6.1 Before starting the compressor
1. Before working on the unit remove mains power from
the unit by opening the mains isolating switch.
2. Remove the shipping wedges from beneath each
compressor. Check that each compressor is securely
mounted.
3. Check the thermostat and/or other controls are
correctly wired to the unit.
4. Check tightness of electrical connections.
5. Check air lters have been correctly installed. (Filters
must be installed before starting the unit.)
6. Check that all indoor fan motors can freely rotate.
7. Apply mains power to the unit by closing the mains
isolating switch.
8. Check the supply voltage between each phase and
neutral.
9. Air Balance the building's ducting system using
an experienced HVAC technician. This will require
temporary isolation of the compressors using the
internal circiuit breakers, and running the fan only.
(Refer 6.3 for fan speed considerations)
10. Apply mains power to the unit by closing the mains
isolating switch.
11. Once Air Balancing is complete, power OFF the unit
and reset the compressor circuit breakers.
12. BEFORE starting the compressors a four hour delay
period is required to allow the crankcase heaters to
drive any liquid refrigerant out of the compressor oil.
Mains power must be switched on during this four hour
delay period.
6.2 Commissioning
After the four hour delay period has expired (see step 10 in
section 6.1) complete the following procedure. You can use
the Commissioning Sheet (refer p.10) to help you.
1. Place the UC8 controller in commissioning mode by
pressing and holding the SW3 push button (see Fig. 4)
until the display shows:
‘0’ [release] ‘1’ [long press] ‘t’; [short press] repeat
to nd ‘c’, then [long press] to select.
This Commissioning mode ‘c’ reduces the waiting times
at start-up and between cycles.for the next half
hour, or until the controller is reset by removing
power.
2. Start compressor in Cooling mode.
3. Check the outdoor fan motor runs smoothly.
Note: The outdoor fan does not necessarily start rotating
immediately after the compressor is started. The fans
may run-on for a short period after the compressor
stops.
Outdoor fan stops during outdoor coil de-ice cycles.
4. Measure the current draw on each phase to the
compressor motor and to each fan motor. Check the
readings against the specied values in the wiring
diagram or specication sheet.
5. The display and pushbutton on the UC8 can be used
to check temperatures and pressures. Short presses
on the pushbutton cycles through the available
options. Table1 on page 8 shows, in sequence, what
information is available – with examples.
Alternatively use a set of pressure gauges suitable for
R32 refrigerant.
!WARNING
Under no circumstances shall potential sources of
ignition be used in the searching for or detection of
refrigerant leaks. If a leak is suspected, all naked ames
shall be removed/extinguished.
If a leakage of refrigerant is found which requires
brazing, all of the refrigerant shall be recovered from the
system, or isolated (by means of shut-off valves) in a
part of the system remote from the leak.
6. Repeat steps 2 to 5 for each compressor.
7. Test operation of the compressors when operating in
heating mode.
8. Check for desired supply air ow rate at each outlet (if
air balancing has not been completed).
9. Touch up any outdoor unit paintwork damage to prevent
corrosion.
10. Sign the check label on the Electrical Box cover.
6.3 Commissioningofvariablespeed(EC)indoorplugfan
A unit equipped with variable speed (EC) indoor plug fan
allows adjustment of the fan speeds to obtain the desired
indoor supply airows.
Using TZT-100 option
If the unit is controlled with a temperzone TZT-100 wall
thermostat then adjustments are made as follows:
i. Ensure the compressor is off and the thermostat or BMS
does not request for the compressor to start. The UC8
display should show a ashing dot (●).
ii. To adjust the fan High speed press and hold down the
SW3 push button on the UC8 circuit board until the
display shows:
‘0’ [release] ‘1’ [long press] ‘t’; [short press] repeat
to nd ‘H’, then [long press] to select.
iii. The fan will start and run at High speed. The display
shows the fan control voltage for the High
speed setting; factory default value is 8.0V.
iv. Each following press on the SW3 push button increases
the indoor fan control voltage in steps of 0.5V, up to a
maximum of 10.0V. Pressing the push button again when
value 10.0 is shown returns the fan control voltage down
to the minimum value of 3.0V and back up again.
v. When the desired setting for high fan speed is displayed,
[long press] to select and save. The controller then exits
the menu and the fan stops.