  9. TemperZone OPA 650RKTB Maintenance and service guide

TemperZone OPA 650RKTB Maintenance and service guide

Other TemperZone Air Conditioner manuals

TemperZone ISD 840KB-P Maintenance and service guide

TemperZone

TemperZone ISD 840KB-P Maintenance and service guide

TemperZone OPA 550RKTB Maintenance and service guide

TemperZone

TemperZone OPA 550RKTB Maintenance and service guide

TemperZone OPA 330RKT Maintenance and service guide

TemperZone

TemperZone OPA 330RKT Maintenance and service guide

TemperZone OSA 840RKTB User manual

TemperZone

TemperZone OSA 840RKTB User manual

TemperZone OSA 160RKTGH Maintenance and service guide

TemperZone

TemperZone OSA 160RKTGH Maintenance and service guide

TemperZone OPA 201RKTYG User manual

TemperZone

TemperZone OPA 201RKTYG User manual

TemperZone OPA 465-960 RKTGH-P ECO Maintenance and service guide

TemperZone

TemperZone OPA 465-960 RKTGH-P ECO Maintenance and service guide

TemperZone OPA 390R Maintenance and service guide

TemperZone

TemperZone OPA 390R Maintenance and service guide

TemperZone OPA 116RKTYH Maintenance and service guide

TemperZone

TemperZone OPA 116RKTYH Maintenance and service guide

TemperZone OPA 250R Maintenance and service guide

TemperZone

TemperZone OPA 250R Maintenance and service guide

TemperZone ISD 840K Maintenance and service guide

TemperZone

TemperZone ISD 840K Maintenance and service guide

TemperZone OPA 161RKTY Maintenance and service guide

TemperZone

TemperZone OPA 161RKTY Maintenance and service guide

TemperZone ISD 500Q Maintenance and service guide

TemperZone

TemperZone ISD 500Q Maintenance and service guide

TemperZone ISD 380KBY Maintenance and service guide

TemperZone

TemperZone ISD 380KBY Maintenance and service guide

TemperZone ISD 380-950 Series Instruction manual

TemperZone

TemperZone ISD 380-950 Series Instruction manual

TemperZone ISF 300K Maintenance and service guide

TemperZone

TemperZone ISF 300K Maintenance and service guide

TemperZone ISD 220Q Maintenance and service guide

TemperZone

TemperZone ISD 220Q Maintenance and service guide

TemperZone GME Series Maintenance and service guide

TemperZone

TemperZone GME Series Maintenance and service guide

TemperZone OPA 1370RKTMG01-PZ Maintenance and service guide

TemperZone

TemperZone OPA 1370RKTMG01-PZ Maintenance and service guide

TemperZone OPA 250 RLTFP-DZ Maintenance and service guide

TemperZone

TemperZone OPA 250 RLTFP-DZ Maintenance and service guide

TemperZone HWP 96 Series Maintenance and service guide

TemperZone

TemperZone HWP 96 Series Maintenance and service guide

TemperZone HWP Series Maintenance and service guide

TemperZone

TemperZone HWP Series Maintenance and service guide

TemperZone HWP 35 Maintenance and service guide

TemperZone

TemperZone HWP 35 Maintenance and service guide

TemperZone OSA 220 Maintenance and service guide

TemperZone

TemperZone OSA 220 Maintenance and service guide

Popular Air Conditioner manuals by other brands

Panasonic CS-E12HKEW operating instructions

Panasonic

Panasonic CS-E12HKEW operating instructions

Mitsubishi Electric MSZ-GE60VA null

Mitsubishi Electric

Mitsubishi Electric MSZ-GE60VA null

Samsung AVMFC052EA0(4) null

Samsung

Samsung AVMFC052EA0(4) null

Haier HSU-09H03/R null

Haier

Haier HSU-09H03/R null

Haier HSU-24C03 null

Haier

Haier HSU-24C03 null

Mitsubishi Electric MSZ-GE22VA null

Mitsubishi Electric

Mitsubishi Electric MSZ-GE22VA null

Samsung AVMCH052CA1 null

Samsung

Samsung AVMCH052CA1 null

nedis ACMB1WT7 quick start guide

nedis

nedis ACMB1WT7 quick start guide

Daikin FCFV50A Operation manual

Daikin

Daikin FCFV50A Operation manual

Fujitsu Inverter ASBA30JFC operating manual

Fujitsu

Fujitsu Inverter ASBA30JFC operating manual

Toshiba RAS-M10SMUV-E installation manual

Toshiba

Toshiba RAS-M10SMUV-E installation manual

Daikin FXLQ20MAVE Operation manual

Daikin

Daikin FXLQ20MAVE Operation manual

CIAT Magister 2 Series Installation, Operation, Commissioning, Maintenance

CIAT

CIAT Magister 2 Series Installation, Operation, Commissioning, Maintenance

Bestron AAC6000 instruction manual

Bestron

Bestron AAC6000 instruction manual

Frigidaire FFRE0533S1E0 Use & care guide

Frigidaire

Frigidaire FFRE0533S1E0 Use & care guide

Samsung AS09HM3N user manual

Samsung

Samsung AS09HM3N user manual

Frigidaire CRA073PU11 use & care

Frigidaire

Frigidaire CRA073PU11 use & care

Soleus Air GB-PAC-08E4 operating instructions

Soleus Air

Soleus Air GB-PAC-08E4 operating instructions

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

OPA 650RKTB
Packaged Reverse Cycle R410A
Air Cooled Air Conditioner
GENERAL
This OPA 650RKTB Outdoor Unit must be
installed in accordance with all national and
local safety codes.
CONFIGURATIONS
The OPA 650RKTB is supplied in one of
two standard configurations :
1. Horizontal supply/return air with box
mounting channel (RKTBH), or
2. Downward supply air with box mounting
channel (RKTBU).
REFRIGERATION SYSTEM
General
The OPA 650 has two independent
refrigeration circuits and two compressors
to provide the flexibility and economy of
two stage operation, i.e. utilising one or
two circuits as conditions vary, plus the
advantage of staggered starting.
Each refrigeration system has been
charged with 9.5 kg each of HFC-410A
(R410A) refrigerant. Tapping points are
provided to measure discharge and suction
operating pressures.
Compressors
The compressors are directional scroll
type. The compressor lubricant is polyol
ester oil (POE). Note, this oil absorbs
moisture quickly if exposed to open air.
On commissioning, the compressors must
be checked for correct rotation (refer Start
Up Procedure). A time delay prevents
simultaneous starting of the compressors.
ECONOMISER (Option)
If the outdoor air temperature or heat
content preferably, is below that of the
return air the fresh air damper opens and
the return air damper closes to provide the
first stage of cooling. A spill air facility in
the building may be necessary for when
the return air damper is closed. The fresh
air damper should return to minimum
setting and the return air damper open
before compressors are allowed to operate
to provide further cooling. A low limit
thermostat is fitted to prevent compressors
operating with a mixed air-on coil
temperature below 18°C; resets at 20°C.
This is by-passed during heating mode.
INSTALLATION
Positioning
Refer to dimension diagrams for minimum
clearances. If multiple units are to be
placed side-by-side then allow at least 2 m
between coil faces.
Installation &
Maintenance
Mounting
The unit should be fastened to a firm flat
horizontal base using the holes supplied in
the mounting channels.
When the unit is being installed on a roof it is
recommended that the unit is installed on a
substantial structure with vibration isolating
springs beneath the unit. These springs are
not supplied with the unit.
Flexible duct connections are recommended
between the supply and return ducts and
the unit.
Condensate Drain
The condensate drain should be 'U' trapped
outside the unit. The trap should have a
vertical height of at least 100 mm. The drain
should have a slope of at least 1 in 50 and
must not be piped to a level above the unit
drain pipe (refer Fig. 3).
Electrical Requirements
Electrical work must be done by a qualified
electrician. The outdoor unit must be wired
directly from a distribution board by means
of a circuit breaker or H.R.C. fuse, and a
mains isolator provided - preferably close to
the unit.
Note: DO NOT USE REWIRABLE FUSES.
The OPA 650 is provided with a 24V AC
control circuit for a thermostat, on/off switch
and/or time clock.
The control transformer 240V primary
voltage is used for countries with 230-240V
power supply. For countries with supply
voltages 200-220V, change the primary
voltage on the transformer to 208V.
Standard units are suitable for use with
thermostats with either manual Heat/Cool
selection or automatic changeover subject to
the contact ratings of the thermostats.
A 24 hour power supply to the compressor
crank case heaters is required, otherwise the
warranty is void.
CHECK TESTS
1. Leave the on/off switch in the off position
and close the mains isolating switch.
A four hour delay period is required to
allow the crankcase heaters to drive any
liquid refrigerant out of the compressor oil.
Bypass the crankcase heater thermostat
(CCHT) for this period only.
2. Check that the shipping blocks beneath
each compressor have been removed
and that each compressor is secure on its
mounts.
3. Check that all fan motors are free running.
4. Check that the thermostat is correctly
wired to the unit and is set at the desired
temperature.
5. Check that the air filters have been
correctly installed if fitted.
6. Check air diffuser dampers are open if
appropriate.
START UP PROCEDURE
Use the supplied Commissioning Sheet to
help you complete the following procedure:
1. After the four hour delay period has
expired, switch on the unit. Ensure the
crankcase heater thermostat has been
reconnected.
2. Check the supply voltage between each
phase and neutral.
3. Compressors fitted are directional. Check
for correct rotation. If rotation is incorrect
the compressor will not pump, be noisy,
and will draw minimal current. To correct
motor rotation, change the phasing at
the main power terminal. If changing the
phasing, check the indoor air fan then
runs in the correct direction also.
4. Measure the current draw on each phase
to the compressor motors and measure
the current draw of each fan motor.
Check all readings against the specified
values in the wiring diagram.
5. Fit R410A compatible gauges and
measure the suction and discharge
pressures of both refrigeration circuits.
6. Check that the outdoor air fan motors are
running smoothly.
7. Test the operation of the reversing valve
by running the unit in both the heating
and cooling mode.
8. Check the indoor unit's fan belt tension
after 20 mins of operation and adjust if
necessary (refer Commissioning Sheet).
9. Check the supply air flow at each outlet.
10.Check the tightness of all electrical
connections and sign the check label.
11.Touch up any outdoor unit paintwork
damage to prevent corrosion.
SETTING SUPPLY AIR FLOW
Consult OPA 650 Technical Data pamphlet
for details of airflow/duct static pressure, if
required.
If the indoor air returning to the unit is
regularly expected to be above 50%RH,
then the coil face velocity should be limited
to be 2.5 m/s or less (refer Air Handling
graph in Technical Data pamphlet).
High humidity levels can occur in tropical or
subtropical conditions, and/or when heavily
moisture laden fresh air is introduced.
Select a fan speed that avoids water carry-
over problems.
In a free blow or low resistance application,
beware of exceeding the fan motor's full
load amp limit (refer wiring diagram).
The indoor air fan motor is fitted with
a factory set adjustable pitch pulley.
Instructions for the adjustment of pulleys is
included on the back page of the supplied
Commissioning Sheet. One revolution of
adjustment is equal to approx. 7% change in
air volume flow rate.
OUTDOOR UNIT CONTROLLER (OUC)
The Outdoor Unit Controller (OUC)
includes a temperature sensing head
pressure control which enables the system
to compensate for outdoor ambient
temperatures below 20°C on cooling cycle,
and above 15°C on heating cycle. The OUC
also has features which protect against icing
or overheating of coils, rapid cycling of the
compressor and loss of refrigerant charge.
If the outdoor air fans take some time
to begin rotating when the system is
powered on, or they don't appear to be
rotating appropriately while the compressor
is running, consult the OUC label on
the electrical box. If necessary, refer
to temperzone for further diagnostic
information.
OPA 650RKTB
DIMENSIONS (mm)
Not to Scale
403
SUPPLY
AIR
RETURN
AIR
225 473 497
135
1878
MOUNTING CENTRES
100
385
2225
1950
1860
OUTDOOR
AIR FLOW
OUTDOOR
AIR FLOW
OPTIONAL
WEATHER
HOOD
1000 MIN. CLEARANCE
500 MIN. CLEARANCE
OPTIONAL
WEATHER
HOOD
570
955
ACCESS
PANEL
UW
X
Z
DRAIN
1" BSP
FEMALE
1000 MIN.
CLEARANCE
FOR FILTER
ACCESS
500 MIN. CLEARANCE
FILTER
ACCESS
60
2335 O/A
35
ACCESS
PANEL
V
Y
1080 1080
MOUNTING CENTRES
Fig. 1 OPA 650RKTBH – Horizontal Supply & Return Air
PROJECTION
Note : A 2 m clearance
is required above the
exhaust air fans
Net Weight 890 kg
MAINTENANCE
Monthly
1. Check air filters, if fitted, and vacuum or
wash clean as necessary.
2. Check condensate drain for free
drainage.
3. Check compressor compartment for oil
stains indicating refrigerant leaks.
Three Monthly (or every 1200 hrs of operation)
Check the indoor unit's fan belt tension and
adjust if necessary.
Six Monthly
1. Check the tightness of electrical
connections.
2. Check the tightness of all fans, motor
mountings, pulleys and belt tension.
3. Check suction and discharge operating
pressures.
4. Replace indoor air filters (if fitted).
5. Check condensate drain for free
drainage.
Yearly
1. Check all refrigerant piping for chafing
and vibration.
2. Check the operation of electric heaters,
if fitted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration
and correct as necessary.
5. Check for insulation and duct damage
and repair as necessary.
6. Remove lint and dust accumulation from
outdoor coil fins.
7. Touch up any paintwork damage to
prevent corrosion.
NOTE
The manufacturer reserves the right to
make changes in specifications at any time
without notice or obligation. Certified data is
available on request.
POINT LOads (kg)
U V W X Y Z
146 135 135 154 154 166
This pamphlet replaces the previous
issue no. 3359 dated 04/10.
Wiring revision F.
OPA 650RKTBDIMENSIONS (mm)
Not to Scale
PROJECTION
NOTE
The manufacturer reserves the right to make
changes in specifications at any time without
notice or obligation. Certified data is available
on request.
Fig. 5 Condensate Drain
OPEN
DRAIN
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
100 mm
MINIMUM
200 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS
OUTDOOR
AIR FLOW
SUPPLY
& RETURN AIR
OUTDOOR
AIR FLOW
305
225
475
560
470
930
210
120
60
405
Fig. 2 OPA 650RKTBU – Downward Supply & Return Air
03/11 Pamphlet No. 3582 © temperzone limited 2011