manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. TemperZone
  6. •
  7. Air Conditioner
  8. •
  9. TemperZone OPA 161RKTYH Maintenance and service guide

TemperZone OPA 161RKTYH Maintenance and service guide

Other TemperZone Air Conditioner manuals

TemperZone OPA 550RKTB Maintenance and service guide

TemperZone

TemperZone OPA 550RKTB Maintenance and service guide

TemperZone Econex Pro Maintenance and service guide

TemperZone

TemperZone Econex Pro Maintenance and service guide

TemperZone OPA 650RKTB Maintenance and service guide

TemperZone

TemperZone OPA 650RKTB Maintenance and service guide

TemperZone OPA 205RKT Maintenance and service guide

TemperZone

TemperZone OPA 205RKT Maintenance and service guide

TemperZone OPA 201RKTYG User manual

TemperZone

TemperZone OPA 201RKTYG User manual

TemperZone OPA 1370RKTMG01-PZ Maintenance and service guide

TemperZone

TemperZone OPA 1370RKTMG01-PZ Maintenance and service guide

TemperZone ISD 840K Maintenance and service guide

TemperZone

TemperZone ISD 840K Maintenance and service guide

TemperZone ISD 480Q Maintenance and service guide

TemperZone

TemperZone ISD 480Q Maintenance and service guide

TemperZone EcoULTRA OPA 2100RKTM-P Maintenance and service guide

TemperZone

TemperZone EcoULTRA OPA 2100RKTM-P Maintenance and service guide

TemperZone OPA 201RKTY Maintenance and service guide

TemperZone

TemperZone OPA 201RKTY Maintenance and service guide

TemperZone OSA 83RKSH Maintenance and service guide

TemperZone

TemperZone OSA 83RKSH Maintenance and service guide

TemperZone ISD 840KB-P Maintenance and service guide

TemperZone

TemperZone ISD 840KB-P Maintenance and service guide

TemperZone OSA 175RKTHG Maintenance and service guide

TemperZone

TemperZone OSA 175RKTHG Maintenance and service guide

TemperZone HWP 96 Series Maintenance and service guide

TemperZone

TemperZone HWP 96 Series Maintenance and service guide

TemperZone ISD 220Q Maintenance and service guide

TemperZone

TemperZone ISD 220Q Maintenance and service guide

TemperZone OSA 220 Maintenance and service guide

TemperZone

TemperZone OSA 220 Maintenance and service guide

TemperZone ISU KD Series Maintenance and service guide

TemperZone

TemperZone ISU KD Series Maintenance and service guide

TemperZone OSA 200RKTV Maintenance and service guide

TemperZone

TemperZone OSA 200RKTV Maintenance and service guide

TemperZone ISD 80K Maintenance and service guide

TemperZone

TemperZone ISD 80K Maintenance and service guide

TemperZone OPA 186RKTY Maintenance and service guide

TemperZone

TemperZone OPA 186RKTY Maintenance and service guide

TemperZone OSA 840RKTB User manual

TemperZone

TemperZone OSA 840RKTB User manual

TemperZone HWP 35 Maintenance and service guide

TemperZone

TemperZone HWP 35 Maintenance and service guide

TemperZone HWP Series Maintenance and service guide

TemperZone

TemperZone HWP Series Maintenance and service guide

TemperZone OPA 116RKTYH Maintenance and service guide

TemperZone

TemperZone OPA 116RKTYH Maintenance and service guide

Popular Air Conditioner manuals by other brands

Fujitsu ASYG 09 LLCA installation manual

Fujitsu

Fujitsu ASYG 09 LLCA installation manual

York HVHC 07-12DS Installation & owner's manual

York

York HVHC 07-12DS Installation & owner's manual

Carrier Fan Coil 42B Installation, operation and maintenance manual

Carrier

Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity IDUFCI60KC-3 installation manual

intensity

intensity IDUFCI60KC-3 installation manual

Frigidaire FAC064K7A2 Factory parts catalog

Frigidaire

Frigidaire FAC064K7A2 Factory parts catalog

Sanyo KS2432 instruction manual

Sanyo

Sanyo KS2432 instruction manual

LG MultiV Series installation manual

LG

LG MultiV Series installation manual

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

CLIMAVENETA

CLIMAVENETA a-CHD U-2T 606+2209 OPERATING AND INSTALLATION Manual

Midea EWK06CW5 user manual

Midea

Midea EWK06CW5 user manual

Pioneer FAB Series installation manual

Pioneer

Pioneer FAB Series installation manual

SPT WA-1511S user manual

SPT

SPT WA-1511S user manual

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric

Mitsubishi Electric Mr.Slim MSZ-A24NA operating instructions

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Mitsubishi Electric

Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic CS-S18HKQ Service manual

Panasonic

Panasonic CS-S18HKQ Service manual

Panasonic CS-E15NKE3 operating instructions

Panasonic

Panasonic CS-E15NKE3 operating instructions

Gree GWH18TC-K3DNA1B/I Service manual

Gree

Gree GWH18TC-K3DNA1B/I Service manual

Friedrich ZoneAire Compact P08SA owner's manual

Friedrich

Friedrich ZoneAire Compact P08SA owner's manual

Daikin R32 Split Series installation manual

Daikin

Daikin R32 Split Series installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

OPA 161RKTYH (c/w EC motor)
Packaged Reverse Cycle R410A
Air Cooled Air Conditioner Installation &
Maintenance
will stop the indoor fan. A control voltage
of slightly more than 2V will cause the fan
to run at the 'Min. rpm' speed. A 10V DC
signal will run the fan at the 'Max. rpm'
speed. Control voltages between these
two limits can be used to achieve any
desired speed between 'Min.' and 'Max.'
rpm.
Do not use switch combinations
marked with 'DO NOT USE' in the
Speed Selection table.
If the air returning to the indoor unit is
regularly expected to be above 50%RH,
then the coil face velocity should be limited
to be 2.5 m/s or less (refer Air Handling
graph in Technical Data pamphlet).
High humidity levels can occur in tropical or
subtropical conditions, and/or when heavily
moisture laden fresh air is introduced. Select
a fan speed that avoids water carry-over
problems.
CHECK TESTS
1. Leave the remote switch in the off
position and close the mains isolating
switch.
A four hour delay period is required to
allow the crankcase heater to drive any
liquid refrigerant out of the compres-
sor oil. Bypass the crankcase heater
thermostat (CCHT) for this period only.
2. Check that all fan motors are free
running.
3. Check that the thermostat is correctly
wired to the unit and is set at the desired
temperature.
4. Check that the air filters, if any, have
been correctly installed.
5. Check any supply air diffuser dampers
are open.
START UP PROCEDURE
Use the supplied Commissioning Sheet to
help you complete the following procedure:
1. Switch on the unit after the four
hour delay period for the crankcase
heater has expired. Ensure the
crankcase heater thermostat has been
reconnected.
2. Check for correct rotation of the
compressor. If rotation is incorrect the
compressor will not pump, be noisy, and
will draw minimal current. To correct
motor rotation, change the phasing at
the main power terminal.
3. Check the supply voltage.
4. Measure the current draw on the
compressor motor and on each fan
motor. Check all readings against the
specified values - particularly the indoor
fan amps if the unit is installed in a free
blow application.
Compressor
The compressor is directional scroll
type. The compressor lubricant is polyol
ester oil (POE). Note, this oil absorbs
moisture quickly if exposed to open air. On
commissioning, the compressor must be
checked for correct rotation (refer Start Up
Procedure).
ELECTRICAL REQUIREMENTS
Electrical work must be done by a qualified
electrician. The outdoor unit must be wired
directly from a distribution board by means
of a circuit breaker or H.R.C. fuse, and a
mains isolator provided - preferably close to
the unit.
Note: DO NOT USE REWIRABLE FUSES.
Standard units are suitable for use with
thermostats with either manual Heat/Cool
selection or automatic changeover subject
to the contact ratings of the thermostats.
Refer to separate pamphlet for approved
thermostats, or contact the manufacturer's
nearest sales office.
A 24 hour power supply to the crankcase
heaters is required, otherwise the warranty
is void.
INDOOR FAN SPEED
The indoor fan speed can be 'Stepped'
or 'Continuously Variable'. The choice is
made using Switch 1 of 'DIP1' on the EC
Motor Controller. Switches 1 to 5 on 'DIP2'
determine the minimum and maximum fan
speeds.
The same 'Minimum rpm' and 'Maximum
rpm' settings apply to 'Stepped' and
'Continuously Variable'.
The default settings for DIP1 and DIP2 are
highlighted on the Wiring Schematic.
1. Stepped (DIP1 switch 1 = OFF)
Connecting the 24V AC power from the
unit’s 'HOT 24V' terminal to one (and only
one at a time) of the 'LOW 24V' / 'MED
24V' / 'HIGH 24V' terminals, selects the
'LOW' (Min. rpm), 'HIGH' (Max. rpm), or
'MED' (mid-way between) fan speed. The
transitions between speeds are smooth.
2. Continuously Variable (DIP1 switch 1=ON)
When using this method a temperzone
Analog Signal Isolator (No. 201-000-129)
must be fitted and connected as shown
in the wiring schematic. 24V AC or DC
power from the external (BMS) controller
should be provided to the '24V' and '0V'
input terminals of the Signal Isolator
board.
A voltage below 2V DC applied across
the '0V' and the '0-10V' input terminals
(labelled 'From BMS Controller' in the
wiring schematic) of the Signal Isolator
GENERAL
This OPA 161 unit must be installed in
accordance with all national and local safety
codes.
OPTION (Field Fitted)
SAT-2 Controller 24V kit – for stepped fan
speed control.
INSTALLATION
Positioning
Refer to dimension diagram for minimum
clearances. If multiple units are to be placed
side-by-side then allow at least 2 m between
coil faces.
Mounting
Fasten the unit down to a firm flat horizontal
base using the four holes provided in the
mounting rails.
When the unit is being installed on a roof
it is recommended that the unit is installed
on a substantial structure with vibration
isolating springs beneath the unit. These
springs are not supplied with the unit.
Flexible duct connections are recommended
between the supply and return ducts and
the unit.
Condensate Drain
The condensate drain should be 'U' trapped
outside the unit. The trap should have a
vertical height of at least 50 mm. The drain
should have a slope of at least 1 in 50 and
must not be piped to a level above the unit
drain pipe.
For long condensate pipe runs, fit a vent
pipe near the drain trap. The top of the vent
pipe must be at least 100 mm above the
OPA unit's drain tray.
REFRIGERATION SYSTEM
General
The refrigeration system has been charged
with R410A refrigerant; refer wiring
specification table for amount. Tapping
points are provided to measure discharge
and suction operating pressures. Beware of
high system pressures; use correct guages.
OPEN
DRAIN
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
50 mm
MINIMUM
100 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS
UNIT
Dimensions (mm) OPA 161RKTYH
PROJECTION
Not to Scale
 POINTLOads(kg) WEIGHT
W X Y Z (kg)
37 60 60 68 225
5. Fit R410A compatible gauges and
measure the suction and discharge
pressures.
6. Test the operation of the high pressure
safety control by switching off the
outdoor air fan.
7. Test the operation of the reversing valve
by running the unit in both the heating
and cooling mode.
8. Check that the motors are running
smoothly.
9. Check the supply air flow at each outlet.
10. Touch up any outdoor unit paintwork
damage to prevent corrosion.
OUTDOOR UNIT CONTROLLER (OUC)
The Outdoor Unit Controller (OUC) includes
a temperature sensing head pressure
control which enables the system to com-
pensate for outdoor ambient temperatures
below 20°C on cooling cycle, and above
15°C on heating cycle. The OUC also has
features which protect against icing or
overheating of coils, rapid cycling of the
compressor and loss of refrigerant charge.
If the outdoor unit fans take some time
to begin rotating when the system is
powered on, or they don't appear to be
rotating appropriately while the compressor
is running, consult the OUC label on
the electrical box. If necessary, refer
to temperzone for further diagnostic
information.
MAINTENANCE
Weekly For First Four Weeks
1. Check indoor air filters (if fitted) and
vacuum or wash clean as necessary.
2. Check condensate drain for free
drainage.
3. Check compressor compartment for oil
stains indicating refrigerant leaks.
4. Check tightness of electrical
connections.
Six Monthly
1. Check the tightness of all fan and motor
mountings.
2. Check tightness of electrical
connections.
SUPPLY
AIR
RETURN
AIR
1154
MOUNTING CENTRES
1160
OVERALL
1200
OVERALL
OUTDOOR
AIR FLOW
1000 MIN. CLEARANCE
500 MIN. CLEARANCE
X
Y
Z
W
OUTDOOR
AIR FLOW
ELECTRICAL
ACCESS
PANEL 60
342
35 125
ACCESS
PANEL
2000 MIN. CLEARANCE
1070
OVERALL
160
1065
860
725
MOUNTING CENTRES
12 DIA. HOLES
DRAIN
15 BSPF
11
ELECTRICAL
HOLES
25 DIA.
187
225
190
75
3. Check suction and discharge operating
pressures.
4. Replace indoor unit air filters (if fitted).
5. Check condensate drain for free
drainage.
Yearly
1. Check all refrigerant piping for chafing
and vibration.
2. Check the operation of electric heaters,
if fitted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration
and correct as necessary.
5. Check for insulation and duct damage
and repair as necessary.
6. Remove lint and dust accumulation
from outdoor coil fins.
7. Touch up any outdoor unit paintwork
damage to prevent corrosion.
NOTE
The manufacturer reserves the right to
change specifications at any time without
notice or obligation. Certified dimensions
available on request.
© temperzone limited 201209/12 Pamphlet No. 3877
This pamphlet replaces the previous
issue no. 3679 dated 09/12.
Wiring revision B.