Tenesun KRS-HC Series User manual

New KRS-HC series Wire Controller Operation Manual
- 1 -
Wire controller operation manual
1. Description of key
Refer key-function: read the running status and fault of heat pump
Menu key-function: enter or quit the interface of menu item
up/down key-function: choose menu item or parameter item
+/- key-function: change parameter or password input, etc.
Enter key-function: confirm the mean item, password, etc.

New KRS-HC series Wire Controller Operation Manual
- 2 -
On/off key-function: start and stop heat pump
2. Description of LCD display
A. Start screen
After heat pump is power on, the wire controller appears start screen. Press any key or wait for 10
seconds, the LCD display appears main interface.
B. Main interface
inlet water temperature or outlet water temperature
setting inlet or outlet water temperature
inlet water temperature or outlet water temperature
settinginletoroutletwatertemperature
In the first line of the main interface, it displays date. Year/month/day, week, time.
In the second line of the main interface, it displays inlet water temperature/outlet water temperature and
setting water temperature.
In the third line of the main interface, it displays working status of heat pump.
On/off key: On the normal condition, press the key to start or stop the heat pump. When heat pump is at
anti-freeze status, press Enter key to quit the status of anti-freeze manually. When heat pump is locked
within time limit, press on/off key to enter the status of password input to unlock.

New KRS-HC series Wire Controller Operation Manual
- 3 -
Menu key: enter or quit the menu item interface.
Refer key: when heat pump is without new fault, users could press refer key to read the running status.
When heat pump is with fault, users could press refer key to read the error code.
Note: Heat pump control basis instruction
Control basis of heat pump Inlet water temperature/outlet Setting inlet water temp./outlet
Inlet water Inlet water temperature Setting inlet water temperature
Outlet water Outlet water temperature Setting outlet water temperature
*Descriptions of symbol
: it means now heat pump doesn’t has timer on/off function which has not been carried out.
: it means now heat pump has timer on/off function which has not been carried out.
: it means compressor doesn’t start.
: it means compressor is working.
: it means heat pump is at the status of defrost.
: it means heat pump is on cooling mode.
: it means heat pump is on heating mode.

New KRS-HC series Wire Controller Operation Manual
- 4 -
C. Main menu interface
When wire controller appears main interface, users press Menu key to enter the Menu interface, then
press 【+/-】key to choose menu item. Users could press Enter key to read the function interface, and
press Menu key to return. MENU item includes working status inquiry, parameter setting, and fault
inquiry.
D. Status inquiry interface
When wire controller appears status inquiry interface, users press Enter key to enter above interface. Or
when wire controller appears main interface and heat pump doesn’t have fault, users press Refer key to
enter the interface, then press 【▲/▼】key to choose menu item. Users could press Enter key to read the
function interface, and press Menu key to return. The MENU item includes system status, module
com.status, total run time and sensor status.
E. System status interface
When wire controller appears system status interface, users press Enter key to enter above interface.
Press 【▲/▼】key to choose menu item, and press 【+/-】key to choose compressor number, press
Menu key to return. The MENU item includes oilpreheat status, heater status, pump status, module
compressor status, and defrost status.
: it means compressor is working. : it means defrost is on working.

New KRS-HC series Wire Controller Operation Manual
- 5 -
F. Module com. status interface
When wire controller appears status inquiry interface, users choose module com. Status item and press
Enter key to enter above interface. Press Menu key to return.
: it means the module is on working. : it means the module is not on working.
G. Total run time interface
When wire controller appears status inquiry interface, users choose total run time item and press Enter
key to enter above interface. Press 【+/-】key to choose compressor number, and press Menu key to
return. The interface could guide users to know total run time of water pump and compressor.
H. Sensor status interface
When wire controller appears status inquiry interface, users choose sensor status item and press Enter
key to enter above interface. Press 【▲/▼】key to choose item, press【+/-】key to choose module
number, and press Menu key to return. The interface could guide users to know evaporator temperature,
ambient temperature, outlet water temperature, and inlet water temperature.
I. Edit setting menu

New KRS-HC series Wire Controller Operation Manual
- 6 -
Press 【▲/▼】key, and【+/-】key to choose item and change value.
J. Edit user setting menu
Press 【▲/▼】key, and【+/-】key to choose item and change value.
K. Mode&Temp Setting menu
Press 【▲/▼】key, and【+/-】key to choose item and change value.
L. Timer on/off Setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.

New KRS-HC series Wire Controller Operation Manual
- 7 -
M. Date/time Setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.
N. Other Setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.
O. Controller setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.
P. Edit high setting

New KRS-HC series Wire Controller Operation Manual
- 8 -
Press 【▲/▼】key, and【+/-】key to choose item and change value.
Q. Anti-freeze setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.
R. Pump setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.
S. Defrost setting

New KRS-HC series Wire Controller Operation Manual
- 9 -
Press 【▲/▼】key, and【+/-】key to choose item and change value.
T. Aux-heat setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.
U. Outdoor fan setting
Press 【▲/▼】key, and【+/-】key to choose item and change value.
V. High-low temp protection
Press 【▲/▼】key, and【+/-】key to choose item and change value.
W. Compressor protection

New KRS-HC series Wire Controller Operation Manual
- 10 -
Press 【▲/▼】key, and【+/-】key to choose item and change value.
X. Error relay set
Press 【▲/▼】key, and【+/-】key to choose item and change value.
Y. T-start cycle
Press 【▲/▼】key, and【+/-】key to choose item and change value.
Z. Sensor adjustment
Press 【▲/▼】key, and【+/-】key to choose item and change value.
A2. Maintainer pin
Press 【▲/▼】key, and【+/-】key to choose item and change value.

New KRS-HC series Wire Controller Operation Manual
- 11 -
B2. Edit factory set
Press 【▲/▼】key, and【+/-】key to choose item and change value.
C2. Error inquiry
Press 【▲/▼】key, and【+/-】key to choose item and change value.
D2. Compressor force on/off
Press 【▲/▼】key, and【+/-】key to choose item and change value.

New KRS-HC series Wire Controller Operation Manual
- 12 -
E2. Compressor force on/off
Press 【▲/▼】key, and【+/-】key to choose item and change value.
F2. Password input interface
Press 【▲/▼】key, and【+/-】key to choose item and change value.

New KRS-HC series Wire Controller Operation Manual
- 13 -
3. Parameter code sheet
Code Description Default value Adjustable range
01 Running mode setting Automatic Automatic, cooling,
heating, manual
02 Ambient temperature for starting
heating automatically
16℃0℃-26℃
03 Ambient temperature for starting
cooling automatically
20℃16℃-40℃
04 Outlet water temperature setting
value under heating mode
45℃40℃-50℃
05 Inlet water temperature setting
value under heating mode
40℃35℃-45℃
06 Temperature difference under
heating mode
2℃0℃-9℃
07 Heating control basis Inlet water Inlet water, outlet water
08 Outlet water temperature setting
value under cooling mode
7℃7℃-15℃
09 Inlet water temperature setting
value under cooling mode
12℃12℃-20℃
10 Temperature difference under
cooling mode
2℃0℃-9℃
11 Cooling control basis inlet Inlet water, outlet water
12 Ambient temperature for defrost 18℃6-18℃
13 The temperature for starting
defrost, ambient temperature
minus evaporator temperature
5℃5℃-20℃
14 Defrost period TM1 30minutes 20-120 minutes
15 Defrost period TM2 30 minutes 15-120 minutes
16 Defrost interval temperature -5℃-9℃-0℃
17 Defrost quit temperature 8℃5℃-35℃
18 Defrost working longest time 10 minutes 1-10 minutes
19 Defrost waiting time 5 minutes 5-30 minutes
20 Relay time to start solenoid valve
after defrost
10 秒0-60 秒
21 Ambient temperature for starting
aux-heating
8℃0℃-16℃

New KRS-HC series Wire Controller Operation Manual
- 14 -
22 Outlet water temperature for
starting aux-heating
35℃25℃-48℃
23 Outlet water temperature for
stopping aux-heating
40℃30℃-50℃
24 Two speed fan motor control
temperature under cooling mode
32℃30℃-40℃
25 Two speed fan motor control
temperature under heating mode
9℃0℃-15℃
26 System outlet water temperature
over high
65℃45℃-70℃
27 System outlet temperature over
low
3℃1℃-5℃
28 Inlet and outlet water temperature
alarm
9℃6-20℃
29 Outlet water temperature when
anti-freeze running water pump
4℃2℃-7℃
30 Outlet water temperature when
anti-freeze running compressor
3℃1℃-5℃
31 Outlet water temperature when
anti-freeze stop running
12℃5-15℃
32 Compressor restart interval time 3 minutes 3-10 minutes
33 Compressor stop time at least 3 minutes 2-6 minutes
34 Compressor oil pre-heating time 1h 0-10h
35 low pressure alarm relay under
heating mode
30S 10-90S
36 low pressure alarm relay under
cooling mode
5S 5-30S
37 Relay time for low pressure test
to start compressor
180S 10-240S
38 Relay time for alarm of water
flow switch
5S 3-30S
39 Water flow establish time 15S 15-180S
40 Water pump pre-circulation time 30S 30-250S
41 Water pump stop relay 30S 30-250S
42 Energy load temperature control
period
90S 10-240 S
43 Energy deloading temperature
control period
60S 10-240 S

New KRS-HC series Wire Controller Operation Manual
- 15 -
44 Allowed energy control module
number
12 1-12
45 Inlet water temperature sensor
adjustment
0℃-5℃~5℃
46 Outlet water temperature sensor
adjustment
0℃-5℃~5℃
47 Heat pump series Heating/cooling Only cooling,
heating/cooling
48 LCD contrast ratio 8 1~15
49 Backlight off relay 30S 10~60 S
50 Recover default parameter N N,Y
51 Clear total running time N N,Y
52 Recovery the status before
electric break N N,Y
53 Start-user password N N,Y
54 User parameter password 1616 0000-9999
55 Maintainer parameter password 2828 0000-9999
56 Factory parameter password 1212 0000-9999