
EVCOS.p.A.|EVJBasicSplit|Instructionsheetver.1.0|Code104JBSE103|Page2of3|PT49/18
4. Touch the ON/STAND-BY key (or take no action for 60 s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4. Touch the SET key (or take no action for 15 s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15 s to set the value.
8. Touch the SET key (or take no action for 15 s).
9. Touch the SET key for 4 s (or take no action for 60 s) to exit the
procedure.
6.2 Setting the date, time and day of the week (if the EVIF25TBX, EVIF25TWX or
EVIF23TSX module is connected)
N.B.
- do not disconnect the device from the mains in the two minutes after setting the
date, time and day of the week
- if the device communicates with the EVconnect app or the EPoCA remote monitor-
ing system, the date, time and day of the week will be automatically set by the
smartphone or tablet.
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select the label “rtc”.
3. Touch the SET key: the display will show the label “yy” followed
by the last two figures of the year.
4. Touch the UP or DOWN key within 15 s to set the year.
5. Repeat actions 3 and 4 to set the next labels.
LAB. MEANING OF THE NUMBERS FOLLOWING THE LABEL
n month (01… 12)
d day (01… 31)
h hour (00… 23)
n minutes (00… 59)
6. Touch the SET key: the display will show the label for the day of
the week.
7. Touch the UP or DOWN key within 15 s to set the day of the
week.
LAB. MEANING
Mon Monday
tuE Tuesday
UEd Wednesday
thu Thursday
Fri Friday
Sat Saturday
Sun Sunday
8. Touch the SET key: the device will exit the procedure.
9. Touch the ON/STAND-BY key to exit the procedure beforehand.
6.3 Restoring factory (default) settings and saving customised settings
N.B.
- check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- saving customised settings overwrites the factory settings.
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the value.
VAL. MEANING
149 value for restoring the factory information (default)
161 value for saving customised settings
4.
Touch the SET key (or take no action for 15 s): the display will
show the label “dEF” (for setting the “149” value) or the label
“MAP” (for setting the “161” value).
5. Touch the SET key.
6. Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or take no action for 15 s): the display will
show “- - -” flashing for 4 s, after which the device will exit the
procedure.
8. Disconnect the device from the power supply.
9. Touch the SET key for 2 s before action 6 to exit the procedure
beforehand.
7 CONFIGURATION PARAMETERS
NO.
PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
NO.
PAR. DEF. ANALOGUE INPUTS MIN... MAX.
2
CA1
0.0
cabinet probe offset
-25... 25 °C/°F
if P4 = 3, incoming air probe
offset
3 CA2 0.0 evaporator probe offset -25... 25 °C/°F
4 CA3 0.0 auxiliary probe offset -25... 25 °C/°F
5 P0 1 type of probe 0 = PTC 1 = NTC
6 P1 1 enable decimal point °C 0 = no 1 = yes
7 P2 0 temperature measurement unit 0 = °C 1 = °F
8
P3
1
evaporator probe function
0 = disabled
1 = defrost + fans
2 = fans
9
P4
0
configurable input function
0 = digital input
1 = condenser probe
2 = critical temp. probe
3 = outgoing air probe
4 = evaporator probe 2
if P4 = 3, regulation tempera-
ture = product temperature
(CPT)
10
P5
0
value displayed
0 = regulation temperature
1 = setpoint
2 = evaporator temp.
3 = auxiliary temperature
4 = incoming air tempera-
ture
11
P7
50
incoming air effect to calculate
product temperature (CPT)
0... 100 %
CPT = {[(P7 x (incoming air)]
+ [(100 - P7) x
(outgoing air)] : 100}
12
P8 5 display refresh time 0... 250 s: 10
NO.
PAR. DEF. REGULATION MIN... MAX.
13
r0
2.0
setpoint differential
1... 15 °C/°F
if u1c... u5c 1, proportional
band
14
r1 -40 minimum setpoint -99 °C/°F... r2
15
r2 50.0
maximum setpoint r1... 199 °C/°F
16
r3 0 enable setpoint lock 0 = no 1 = yes
17
r4 0.0 setpoint offset in energy saving 0... 99 °C/°F
18
r5
0
hot or cold mode regulation
0 = cold mode
1 = hot mode
19
r6
0.0
setpoint offset in overcool-
ing/overheating 0... 99 °C/°F
20
r7 0 duration overcooling/overheating 0... 240 min
21
r8
2
DOWN key additional function
0 = disabled
1 = overcooling/overheating
2 = energy saving
22
r12
1
differential position r0
0 = asymmetrical
1 = symmetrical
NO.
PAR. DEF. COMPRESSOR MIN... MAX.
23
C0
0
compressor-on delay from
power-on 0... 240 min
24
C1
5
delay between two compressor
switch-ons 0... 240 min
25
C2 3 minimum compressor-off time 0... 240 min
26
C3 0 minimum compressor-on time 0... 240 s
27
C4
10
compressor-off time in cabinet
probe alarm 0... 240 min
28
C5
10
compressor-on time in cabinet
probe alarm 0... 240 min
29
C6
80.0
high condensation signal thresh-
old 0... 199 °C/°F
differential = 2 °C/4 °F
30
C7
90.0
high condensation alarm thresh-
old 0... 199 °C/°F
31
C8 1 high condensation alarm delay 0... 15 min
32
C10
0
compressor days for mainte-
nance 0... 999 days
0 = disabled
33
C11 10 compressor 2 on delay 0... 240 s
34
C12
2
compressor hour value effect to
balance hours and switch-ons
(BHC)
0... 10
BHC = {[C12 x (compressor
hours)] + [C13 x (compres-
sor switch-ons)]}
35
C13
1
compressor switch-ons value ef-
fect to balance hours and switch-
ons (BHC)
0... 10
BHC = {[C12 x (compressor
hours)] + [C13 x (compres-
sor switch-ons)]}
36
C14
1
constraint between compressors
0 = function of C11
1 = function of r0
2 = function of C12 and C13
NO.
PAR. DEF. DEFROSTING (if r5 = 0) MIN... MAX.
37
d00
0
enable "b” mode parameters on
setpoint threshold 0 = no 1 = yes
38
d01
1.0
setpoint threshold to activate “b”
mode parameters r1... r2
activated if setpoint > d01
39
d0
8
automatic defrost interval
0... 99 h
0 = manual only
if d8 = 3, maximum interval
40
d0b
6
automatic defrost interval “b”
mode like d0
41
d1
0
type of defrost
0 = electric
1 = hot gas (do not use with
regulation with 2 com-
pressors)
2 = compressor stopped
42
d1b 2 type of defrost “b” mode like d1
43
d2 2.0 defrost end threshold -99... 99 °C/°F
44
d2b 4.0 defrost end threshold “b” mode like d2
45
d3
30
defrost duration
0... 99 min
if P3 = 1, maximum duration
46
d3b 20 defrost duration “b” mode like d3
47
d4 0 enable defrost at power-on 0 = no 1 = yes
48
d5 0 defrost delay from power-on 0... 99 min
49
d6
1
value displayed when defrosting
0 = regulation temperature
1 = locked display
2 = label dEF
50
d7 0 dripping time 0... 15 min
51
d7b 2 dripping time “b” mode like d7
52
d8
0
defrost interval count mode
0 = hours device on
1 = hours compressor on
2 = hours evaporator tem-
perature < d9
3 = adaptive
4 = in real time
53
d9
0.0
evaporation threshold for auto-
matic defrost interval count -99... 99 °C/°F
54
d11 0 enable defrost timeout alarm 0 = no 1 = yes
55
d15
0
compressor-on consecutive time
for hot gas defrost
-20... 99 min
if values are negative, drip-
ping heaters on time
56
d16
0
pre-dripping time for hot gas de-
frost 0... 99 min
57
d18
40
adaptive defrost interval
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = manual only
58
d19
3.0
adaptive defrost threshold (rela-
tive to optimal evaporation tem-
perature)
0... 40 °C/°F
optimal evaporation tempera-
ture - d19
59
d20
180
compressor-on consecutive time
for defrost 0... 999 min
0 = disabled
60
d21
200
compressor-on consecutive time
for defrost from power-on and
from overcooling
0... 500 min
if (regulation temperature -
setpoint) > 10°C/20 °F
0 = disabled
61
d22
-2.0
evaporation threshold for adap-
tive defrost interval count (rela-
tive to optimal evaporation tem-
perature)
-10... 10 °C/°F
optimal evaporation tempera-
ture + d22
62
d25
0
enable outgoing air probe for de-
frost in evaporator probe alarm 0 = no 1 = yes
63
d26
6
defrost interval in evaporator
probe alarm
0... 99 h
0 = manual only
if d25 = 1
NO.
PAR. DEF. ALARMS MIN... MAX.
64
A0
0
select value for high/low tem-
perature alarms
0 = regulation temperature
1 = evap. temperature
2 = auxiliary temperature
65
A1 0.0 low temperature alarm threshold -99... 99 °C/°F
66
A2
0
type of low temperature alarm
0 = disabled
1 = relative to setpoint
2 = absolute
67
A4
0.0
high temperature alarm thresh-
old -99... 99 °C/°F
68
A5
0
type of high temperature alarm
0 = disabled
1 = relative to setpoint
2 = absolute
69
A6
120
high temperature alarm delay
from power-on 0... 240 min
70
A7
15
high/low temperature alarm de-
lay 0... 240 min
71
A8
15
high temperature alarm delay
post-defrosting 0... 240 min
72
A9
15
high temperature alarm delay
from door closure 0... 240 min
73
A10
10
duration of power failure for sav-
ing alarm 0... 240 min
0 = disabled
74
A11
2.0
high/low temperature alarm re-
set differential 1... 15 °C/°F
75
A12
1
type of power failure alarm signal
0 = LED HACCP
1 = LED HACCP + label PF +
buzzer
2 = LED HACCP + label PF +
buzzer (if duration >
A10)
NO.
PAR. DEF. FANS MIN... MAX.
76
F0
1
evaporator fan mode in normal
function
0 = off 1 = on
2 = on if compressor on
3 = thermoregulated (with
regulation temperature
+ F1)
4 = thermoregulated (with
regulation temperature
+ F1) if compressor on
5 = function of F6
6 = thermoregulated (with
F1)
7 = thermoregulated (with
F1) if compressor on
77
F0b
1
evaporator fan mode in normal
function “b” mode like F0
78
F1
-4.0
evaporator fans regulation
threshold -99... 99 °C/°F
79
F2
0
evaporator fan mode in defrost
and drip mode 0 = off 1 = on
2 = function of F0
80
F2b
0
evaporator fan mode in defrost
and drip mode like F2
81
F3
2
maximum time evaporator fans
off 0... 15 min
82
F3b
2
maximum time evaporator fans
off like F3
83
F4
30
time evaporator fans off in en-
ergy saving 0... 240 s x 10
if F0 ≠ 5
84
F5
30
time evaporator fans on in en-
ergy saving 0... 240 s x 10
if F0 ≠ 5
85
F6
0
function for high/low humidity
0 = for low humidity (with
F17 and F18 if compres-
sor off, on if compressor
on)
1 = for high humidity (on)
86
F7
5.0
evaporator fans on threshold
from dripping (relative to set-
point)
-99... 99 °C/°F
setpoint + F7
87
F8
2.0
evaporator fans regulation
threshold differential 1... 15 °C/°F
88
F9
10
evaporator fans off delay from
compressor off 0... 240 s
if F0 = 2 or 5
89
F11 15.0
condenser fans on threshold 0... 99 °C/°F
90
F12
30
condenser fans off delay from
compressor off 0... 240 s
if P4 ≠ 1
NO.
PAR. DEF. DIGITAL INPUTS MIN... MAX.
91
i0
5
door switch input function
0 = disabled
1 = compressor + evapora-
tor fans off
2 = evaporator fans off
3 = cabinet light on
4 = compressor + evapora-
tor fans off, cabinet light
on
5 = evaporator fans off,
cabinet light on
92
i1
0
door switch input activation
0 = with contact closed
1 = with contact open
93
i2
30
door open alarm delay
-1... 120 min
-1 = disabled
94
i3
15
maximum time for inhibiting
regulation with door open -1... 120 min
-1 = until closed
95
i5
0
multi-purpose input function
0 = disabled
1 = energy saving
2 = alarm iA
3 = alarm iSd
4 = load 1 operated by on
key
5 = load 2 operated by on
key
6 = switches device on/off
7 = alarm LP
8 = alarm C1t
9 = alarm C2t
96
i6
0
multi-purpose input activation
0 = with contact closed
1 = with contact open
97
i7
0
multi-purpose input alarm delay
0... 120 min
if i5 = 3 or 7, compressor on
delay from alarm reset
98
i8
0
number of multi-purpose input
activations for high pressure
alarm
0... 15
0 = disabled
if i5 = 3
99
i9
240
counter reset time for high pres-
sure alarm 1... 999 min
100
i10
0
door closed consecutive time for
energy saving
0... 999 min
after cabinet temperature <
SP
0 = disabled
101
i13
180
number of door openings for de-
frost 0... 240
0 = disabled
102
i14
32
door open consecutive time for
defrost 0... 240 min
0 = disabled
NO.
PAR. DEF. DIGITAL OUTPUTS MIN... MAX.
103
u1c
0
K1 relay configuration
0 = compressor 1
1 = compressor 2
2 = evaporator fans
3 = condenser fans
4 = defrosting
5 = cabinet light
6 = demisting
7 = door heaters
8 = heaters for neutral zone
9 = dripping heaters
10= button-operated load 1
11= button-operated load 2
12= alarm
13= on/stand-by
14= evaporator fans 2
15= defrosting 2
16= speed 2 evaporator fans
17= reversible cond. fans
18= speed 2 cond. fans
104
u2c 2 K2 relay configuration like u1c
105
u3c 4 K3 relay configuration like u1c
106
u4c 5 K4 relay configuration like u1c
107
u2
0
enable cabinet light and load in
stand-by using the key 0 = no 1 = yes
in manual mode
108
u3
0
alarm relay activation
0 = with alarm not active
1 = with alarm active
109
u4 1 enable silencing alarm output 0 = no 1 = yes
110
u5 -1.0 door heaters on threshold -99... 99 °C/°F