TSS8030R_R2.2 – October 2018 Page 1
Smoke detector TSS8030R
Short description
TSS8030R smoke detector is designed for early warning of a fire condition responding to fixed
threshold smoke concentration detected in the protected premises. The smoke sensitivity is factory
preset.
The principle of functioning of the detector is based on infrared rays distraction caused by smoke
particles entering the optic chamber. The fire detector is controlled by a microprocessor, operating
on the basis of improved algorithm for self-compensation of the chamber contamination.
Technical parameters
Supply voltage range 10 to 30 VDC
Maximum s
upply
current
18mA/10VDC
55mA/30VDC
Smoke sensitivity
complies with
EN 54-7:2000+ A1:2002
Time to enter Duty mode after power supply is on
up to 40s
Reset time 2s
Time to enter Duty mode after reset
up to 40s
Protected area
circle with diameter 15 m
Height of mounting up to 11 m
Operating temperature range -10 to +55 °C
Operating
h
umidity
resistance
(93 ± 3)% at 40°C
Dimensions
Ø100 mm, h 47mm
Weight 0,100 kg
Cross section of the connecting wire 0.8 to 1.5 mm²
LED indicators
Both LED indicators (pos.3) allow range of visibility 360° and provide information for the status:
- Duty mode - the LEDs are not lit;
- Fire condition - the LEDs produce continuous light;
- Contaminated chamber- the LEDs flash briefly every 1s.
TSS8030R_R2.1 – October 2018 Page 2
Installation
The smoke detector consists of fire detector FD8000 and base with relay output 8000R. The fire
detector (fig.1) consists of a printed circuit board and an optic chamber (pos.4), fixed in a plastic
body (pos.5).
TSS8030R can be used with controllers of series TCW1xx, TCW2XX and TCG1xx which have digital
inputs in “dry contact” mode. Fore mode details see user manuals.
The electrical connection is done according to the schematic below:
TSS8030R_R2.1 – October 2018 Page 3
It is recommended cable shoes to be used. The fire detector is placed on the base (fig.1,pos.1). It is
rotated clockwise until reaching the guiding grooves (fig.1,pos.2). It is rotated until rest (fig.3.1). The
slots of the base and the body should match (fig.3.2).
Locking of the fire detector (fig.4).
Before installation, the key (pos.3) is detached from the base and the rib (pos.1) of the locking click
(pos.2) is cut out. Removing of a fire detector locked to the base. Insert the key into the slot (pos.4)
push in as in the same time the fire detector is rotated anticlockwise. Remove the key and continue
to rotate the fire detector in the same direction until it is released from the base.
Testing
The smoke detector is tested after installation, following this order:
1. Voltage is to the detector from controller or auxiliary power supply unit 24V DC/0,1A.
2. After one minute smoke detector should be activated using a Smoke Detector Tester. It should
enter fire condition within 40s.
3. The supply voltage to the detector is interrupted within 2s. Smoke detector should enter duty
mode and is ready for a new activation within 40s.
TSS8030R_R2.1 – October 2018 Page 4
Service schedule
It is done by authorized personnel and includes the following activities:
1. Inspection for visible physical damage - monthly
2. Testing in real conditions - monthly
3.* Preventive cleaning of the optic chamber - every 6 months
*The fire detector is removed from the base. The body cover (fig.1,pos.6) is removed by rotating to
rest anticlockwise. The optic chamber cover (fig.1,pos.7) and the screen (fig.1,pos.8) are removed.
For the optic chamber cover and the screen it is permitted washing liquid to be used. Then they
should be rinsed out and dried. The optic chamber is dusted with a small brush.
The optic chamber is compulsory dusted when the fire detector enters Contaminated chamber
Mode. If it is not cleaned in due time it will get contaminated to such an extent that it would not
allow the proper functioning of the fire detector which will be signaled as Fire Condition.
Warranty
FD8030 and 8000R are manufactured by Unipos Ltd.
The manufacturer guarantees the normal operation of the fire detector providing that the
requirements set herein have been observed. The manufacturer does not bear warranty liabilities
for damages caused through accidental mechanical damage, misuse, adaptation or modification
after production. The manufacturer bears warranty liabilities for damages in the fire detector
caused through manufacturer's fault only.

Popular Smoke Alarm manuals by other brands

Xtralis ICAM IAS-1 Product guide

Xtralis

Xtralis ICAM IAS-1 Product guide

Meridian WLS906 Instructions for installation and use

Meridian

Meridian WLS906 Instructions for installation and use

wretro WR-5005-SD instruction manual

wretro

wretro WR-5005-SD instruction manual

GE ESL 700 Series installation instructions

GE

GE ESL 700 Series installation instructions

Climax Technology SD-8-EL manual

Climax Technology

Climax Technology SD-8-EL manual

First Alert P1010 user manual

First Alert

First Alert P1010 user manual

koban KDH-BAT manual

koban

koban KDH-BAT manual

Elektrotechnik Schabus GX-D500P operating instructions

Elektrotechnik Schabus

Elektrotechnik Schabus GX-D500P operating instructions

Smartwares FSM-114 quick start guide

Smartwares

Smartwares FSM-114 quick start guide

DSC AMS-220 Installation and operation instruction

DSC

DSC AMS-220 Installation and operation instruction

FireAngel LSI-601 user manual

FireAngel

FireAngel LSI-601 user manual

Nexelec INSAFE Origin instruction manual

Nexelec

Nexelec INSAFE Origin instruction manual

Trader BEAR BESMOKEY Installation and user guide

Trader

Trader BEAR BESMOKEY Installation and user guide

Xtralis VESDA VLI Product guide

Xtralis

Xtralis VESDA VLI Product guide

Unifore VS-WY100 manual

Unifore

Unifore VS-WY100 manual

Kidde i12010S user manual

Kidde

Kidde i12010S user manual

EL EL-4703 installation instructions

EL

EL EL-4703 installation instructions

Firehawk FHB10 manual

Firehawk

Firehawk FHB10 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.