Tescom DS300T-HF1 Series User manual

DS300T-HF1 SERIES
DSP Controlled UPS
10-20-30kVA
3 Phase In - 3 Phase Out
USER MANUAL


CONTENTS
I. GENERAL DESCRIPTION ...................................................................................... 3
1.1 Introduction ....................................................................................................... 3
1.2 Design Concept................................................................................................. 5
1.2.1 Description of Blocks................................................................................ 6
1.3 Front view of UPS Conditions of ups................................................................. 7
1.4 Technical Specifications.................................................................................... 9
II. UPS INSTALLATION .............................................................................................. 10
2.1. Introduction ....................................................................................................... 10
2.2. Unpacking......................................................................................................... 10
2.3. Equipment Positioning....................................................................................... 10
2.4. Connecting the UPS Power Cables................................................................... 11
2.5. Safety Earth ...................................................................................................... 11
2.6. Cable Connection Procedure ............................................................................ 11
2.6.1. Description of Connection Terminals of the UPS ....................................... 12
2.7. Battery Installation............................................................................................. 13
III. FRONT PANEL ....................................................................................................... 14
3.1. Introduction ....................................................................................................... 14
3.2. Front Panel Menu Descriptions ......................................................................... 15
3.2.1 MEASUREMENTS menu ........................................................................... 17
3.2.2 ALARM LOGS menu .................................................................................. 18
3.2.3 INFORMATION menu ................................................................................ 18
3.2.4 OPTIONS menu ......................................................................................... 19
3.2.5 COMMAND menu ...................................................................................... 21
3.2.6 TIME menu................................................................................................. 21
3.2.7 SERVICE menu.......................................................................................... 21
3.2.8 ADJUST menu ........................................................................................... 22
3.2.9 User Pasword............................................................................................. 22
3.3. Alarms and warning messages ......................................................................... 22
3.4. Status Codes .................................................................................................... 25
3.5. Alarm messages and quick troubleshooting ...................................................... 31
IV. OPERATING INSTRUCTIONS................................................................................ 36
4.1 Introduction.......................................................................................................... 36
4.2 Operating ups in online mode.............................................................................. 36
4.2.1 Starting ups from a completely shut down position..................................... 36
4.2.2 Shutting down the ups................................................................................ 36
4.2.3 Switching the UPS from a normal
operation to maintenance bypass condition.............................................. 37
4.2.4 Switching the UPS from a maintenance
bypass condition to normal operation ....................................................... 37
4.3 UPS Behavior During mains outage.................................................................. 38

1
V. PARALLEL OPERATION……………………………………………………………….. 39
5.1 Introduction……………………………………………………………...……...…....39
5.2
Parallel Operation Mode settings of DS300 Series UPSs……………………….40
5.3 Parallel mode status codes of the UPS……………………………………….......43
VI. PARALLEL OPERATING INSTRUCTIONS……………………………………….......49
6.1 INTRODUCTION………………………………………………………………………49
6.2 OPERATING INSTRUCTIONS FOR PARALLEL CONNECTED UPSs…….…..49
6.2.1 Starting UPSs from a completely shut down position…………………………...49
6.2.2 Shutting down the UPS……………………………………………………………..49
6.2.3 Switching the UPS from a Normal Operation to Maintenance
Bypass Condition………………………………………………………………….……....50
6.2.4 Switching the UPS from a Maintenance Bypass Condition
to Normal Operation……………………………………………………………….….…..50
VII. MAINTENANCE......................................................................................................51
7.1 Scheduled maintenance ....................................................................................51
7.2 Daily checks ......................................................................................................51
7.3 Weekly checks...................................................................................................51
7.4 Annual Maintenance..........................................................................................52
7.5 Storage conditions and transportation of ups.....................................................52
VIII. FAULTS AND TROUBLESHOOTING ..................................................................52
8.1. General Procedure for fault checking and troubleshooting.................................52
8.2. Before calling service.........................................................................................52
IX. UPS REMOTE MANITORING AND CONTROL......................................................54
9.1. Using Serial Port................................................................................................54
9.2. Serial Communication port connection cable .....................................................54
9.3. Modem connection ............................................................................................55
9.3.1 Hardware configuration ...............................................................................55
9.3.2 Functioning Principle...................................................................................55
9.3.3 Modem Programming Procedure ................................................................55
9.3.3.1 Smart modem (SM) programming ...................................................55
7.3.4 Modem – UPS Connection Cable................................................................55
9.4. Dry contact (ınterface) connections ...................................................................56
9.5. Remote monitoring panel connection of UPS.....................................................56
X.EFFICIENT USAGE OF UPS IN TERMS OF ENERGY CONSUMPTION....................57

2
SAFETY
IMPORTANT NOTICES
1. Read instructions carefully before installing and starting the UPS.
2. All warnings in the manual should be adhered to.
3. All operating instructions should be followed.
4. The unit should be supplied by a grounded outlet. Do not operate the unit without a ground source.
5. Power cables of the UPS should be routed carefully so that they are not to be walked on.
6. Please save this manual.
7. Please save or recycle the packaging materials.
WARNING!
•Do not insert any object into ventilation holes or other openings.
•To reduce the risk of fire or electric shock, install in temperature and humidity controlled
indoor area free of conductive contaminants.
•To reduce the risk of fire, replace fuses with the same type and rating when necessary.
CAUTION!
•Only qualified personnel should install or service UPS/batteries.
•Risk of electric shock, do not remove cover. No user serviceable parts inside, refer
servicing to qualified service personnel.
•The output may be energized even when the unit is not connected to a mains supply.
•Risk of electric shock! Hazardous live parts inside. This unit is energized from the
battery supply even when the input AC power is disconnected.
•To reduce the risk of electric shock, disconnect the UPS from the mains supply before
installing a computer interface signal cable. Reconnect the power cables only after signaling
interconnections have been made.
CAUTION !
Units are designed to operate on the concrete floor.
ABOUT THE BATTERIES
CAUTION: RISK OF ELECTRIC SHOCK!
The battery circuit is not isolated from the mains voltage. Hazardous voltages
may occur between the battery terminals and the ground!
•A battery can present a risk of electric shock or burn from high short circuit currents. The
following precautions should be taken when working on batteries :
* Remove watches, rings or other metal objects.
* Use tools with insulated handles.
•The batteries in this UPS are recyclable. Batteries must be disposed of according to local
environmental laws. The batteries contain lead and pose a hazard to the environment and human
health if not disposed of properly.
•
Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate the
batteries. They contain an electrolyte which is toxic and harmful to the skin and
eyes. If electrolyte
comes into contact with the skin the affected area should be washed immediately.
•The internal energy source (the battery) cannot be de-energized by the user.
•When changing batteries, install the same number and same type of batteries.

3
I. GENERAL DESCRIPTION
1.1 Introduction
TESCOM DS300T-HF1 Series Uninterruptible Power Supplies are double-conversion;
on-line UPS’s manufactured with the latest IGBT and PWM technology, to produce an
uninterruptible, fully DSP (Digital Signal Processor) controlled pure sine wave output to
critical loads.
TESCOM DS300T-HF1 Series units are 3-phase in/3-phase out devices, and they are
installed between a three phase critical load, and a 3-phase+N mains supply
The advantages of using DS300T-HF1 UPS:
•Power blackout protection:
If the mains power fails, the UPS continues to supply the critical load using the
energy stored in its batteries, keeping the load immune from power disturbances.
•Increased power quality:
The UPS has its own internal voltage and frequency regulating software, which
ensures that, its output to the critical load is maintained within close tolerances, independent
of voltage and frequency variations on the mains power lines.
•Fully digital control by three DSP controller for each UPS:
The UPS is controlled by 3 independent DSP chips which are communicating each
other continuously. Rectifier, Inverter and User Interface modules have separate DSP’s to
achieve the highest performance. Each DSP module has many parameters to control and
monitor the system to have the best electrical power output and to help diagnostic.
•Increased noise rejection:
By rectifying the input AC power to DC power and then converting it back to AC
(Double-Conversion) any electrical noise present on the input mains supply line is effectively
isolated from the UPS output. Therefore the critical load is supplied with only clean and
uninterrupted AC power.

4
Basic Features:
•3 DSP controlled modular structure
•Galvanic inverter isolation transformer
•Separate main control board advantage for rectifier and inverter
•DSP controlled technology and fully digital structure
•Less electronic components and SMD technology
•Low input current total harmonic distortion (THDi)
•High input power factor
•High efficiency up to 94%
•Selectable input/output voltage/frequency range
•Static and maintenance by-pass switch
•High charge current capacity
•Eco Mode operation (optional)
•Split by-pass input (dual input)
•Advanced LCD front panel and mimic led diagram
•Compliant with IEC EN62040 directive
•Conforms to CE, TSE and GOST standards
•ISO9001, ISO14001 compliant production
•Advanced control at the input
•3 level battery protection
•Output current limitation
•Output DC leakage protection
•External REPO input
•512 events memory (46.000 alarm)
•Clock and calender (battery supported)
•Automatic battery test, remaining battery time indicator
•2 RS232 serial ports and 4 programmable dry contact outputs
•Optional 12 dry contact outputs
•Optional SNMP, MODBUS and Remote Monitoring Panel
•Viewing device operating parameters
•Advanced remote control features
•User and central service password-protected security
•2 years warranty
•10 years spare parts warranty

5
Rectifier /
Charger
Static Bypass
Maintenance Bypass Switch
3 PHASE
MAINS I/P 3 PHASE
AC Output
Battery (Dual Polarity)
S2
(F4-F5-F6)
S1
(F1-F2-F3) S4
(F7-F8-F9)
K2
K1
S5
(F10-F11-F12)
-
-
S3
(connected if
S2 not used)
SB
Output Isolation
Transformer
1.2 Design Concept
Figure 1.1 Block Diagram Of The UPS
S1 (F1-F2-F3) : Rectifier Input Switch / Fuse
S2 (F4-F5-F6) : Bypass Input Switch / Fuse
S3 : Maintenance Bypass Switch
S4 (F7-F8-F9) : Output Switch / Fuse
S5 (F10-F11-F12) : Battery Switch / Fuse
K1 : Rectifier Input Contactor
K2 : Inverter Output Contactor

6
1.2.1 DESCRIPTION OF BLOCKS
RECTIFIER: In DS300T-HF1 Series UPSs, a DSP controlled IGBT rectifier with PWM technique is used to
increase input power factor (PFC) and to decrease input current harmonics (THDI).
The IGBT rectifier accepts 3-phase AC input and produces a dual polarity DC voltage for both supplying
the inverter and charging the batteries.
BATTERIES: Batteries are used as reserve DC power supply for the Inverter in case of mains failure. In
DS300T-HF1 Series, batteries are connected in series with a center-tap output to obtain a dual polarity DC
supply.
Batteries are discharged by the inverter during mains failure. The discharged batteries are re-charged by
the IGBT Rectifier on a constant voltage / current limiting basis, if AC mains power is available.
INVERTER: It is manufactured by using the latest IGBT and DSP (Digital Signal Processing) technologies,
and Pulse Width Modulation (PWM) technique. The Inverter converts the DC BUS voltage supplied by the
IGBT Rectifier and / or the batteries into a well regulated, fully digital controlled 3-phase AC voltage with
fixed voltage and frequency.
The output of the inverter is used to supply the critical loads connected to the UPS output.
STATIC TRANSFER SWITCH (STATIC BYPASS): This is an electronically controlled transfer switch,
which enables the critical load to be connected either to inverter output or to by-pass power source. During
normal operation, the load is supplied by the inverter output, but in case of an overload or a UPS failure it is
automatically transferred to the bypass source without any interruption.
MAINTENANCE BYPASS SWITCH (MBS): This is a manually controlled mechanical switch, which is used
to supply the critical load, using the bypass source, when the UPS is shut down for maintenance or
troubleshooting purposes.
The load is unprotected against mains supply disturbances and black-outs when it is connected to either
static or maintenance bypass supply.
1.2.2. OPERATING CONDITIONS OF UPS
UPS may be in one of the following operating conditions:
A. Normal Operation (If Mains supply is available):
All fuses and power switches are closed (except the Maintenance Bypass Switch), and the load is supplied
by the Inverter Output. During normal operation, the Rectifier supplies DC power to the Inverter and
charges the Batteries at the same time.
B. Battery Operation :
The Batteries are connected to the Rectifier output. In case of a mains failure (mains power outage or AC
input voltage out of tolerance), the Rectifier stops operating and the DC voltage necessary for the inverter
operation is supplied by the batteries. Therefore the AC voltage output supplying the critical load is not
interrupted, until the batteries are fully discharged. At the end of the discharging time the inverter is turned
off and it start again automatically, together with the rectifier, when the mains power is restored, and the
UPS returns o normal operation. For UPS with a split bypass source, at the end of discharging time, static
transfer switch transfers the load to the split bypass source without interruption if the split bypass source is
available and in acceptable tolerances about voltage and frequency, as still the rectifier input is not
available.
The Rectifier is also turned off and inverter operates on batteries during automatic or manual battery test
procedure.
C. By-Pass Operation :
If the Inverter output is overloaded or in case of a problem in the UPS, the static switch transfers the load to
the bypass supply without any interruption, provided that the bypass supply is available and within the
tolerated limits regarding voltage and frequency. At the end of the overloading period, if the fault condition
is restored, static switch transfers the critical load again to the inverter output. Note that, during operation
from the bypass supply, the critical load may be effected by any possible disturbances or power failure in
the bypass supply.

7
1.3 Front view of UPS Connection Panel
Figure 1.3.a 10-20 kVA Fuses and Switches Panel
COM1 - RS232
Communication Socket
(DB9 Female)
Relay Output Contacts and Inputs
S7
On / Off
Switch
S5
(Battery Input, F10-F11-F12)
S1
(AC Input, F1-F2-F3)
S3
(Maintenance By-pass)
S2
(By-Pass, F4-F5-F6)
S4
(AC Output, F7-F8-F9)
SNMP Adapter
(Optional)
COM2 - RS232
Communication Soc
ket
(DB9 Female)
Battery
Circuit
Breaker
Generator
input
Repo
input
TH1
Sensor
Relay
2
Relay
3
Relay
4

8
Figure 1.3.b 30 kVA Fuses and Switches Panel
S5
(Battery Input, F10-F11-F12)
S1
(AC Input, F1-F2-F3)
S3
(Maintenance By-pass)
S2
(By-Pass, F4-F5-F6)
S4
(AC Output, F7-F8-F9)
COM1 - RS232
Communication Socket
(DB9 Female)
S7
On / Off
Switch
SNMP Adapter
(Optional)
COM2 - RS232
Communication Soc
ket
(DB9 Female)
Relay Output Contacts and Inputs
Battery
Circuit
Breaker
Generator
input
Repo
input
TH1
Sensor
Relay
2
Relay
3
Relay
4

9
1.4 Technical Specifications
MODEL
DS310T
-
HF1
DS320T
-
HF1
DS330T
-
HF1
Power (kVA) 10 kVA 20 kVA 30 kVA
Power kW 9 kW 18 kW 27 kW
Power Factor (Output)
0,9
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40%
(at 70% load)
Power factor (at 100% load) ≥0.99
THDI (*) ≤%3
GirişFrekansı 50Hz / 60Hz, ± %10
By-pass voltage 380/400 VAC 3 Phase + N, ± 10%
Protections Fuses, Voltage & Frequency tolerance, Input power limit, Phase
sequency indicator
OUTPUT
Voltage 380/400 VAC 3P + N, ± 1%
Frequency 50Hz / 60Hz
Frequency tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0.1%
Efficiency (@ 100% load) up to 94%
Crest factor 3:1
Overload capacity 100% - 125% load: 10 min, 125% - 150% load: 1 min,
- > 150% load: by pass
Other protections Advanced short circuit, Voltage tolerance, DC balance,
Regenerative load, Current limiting
VoltageTHD ≤2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Number of batteries 40 pieces (adjustable)
Charge voltage 540 VDC
End of discharge voltage 400 VDC
Battery cabinet Harici
Battery ambient temperature 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit,
Temperature compensation (optional)
Automatic testing Standard every 72 hours (adjustable)
GENE
RAL
Standards EN62040-1, EN62040-2, EN62040-3
User interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor,
Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over
RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact
alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset kit Standard (programmable)
Software Standard T-Mon UPS Management Software (3 clients + 1
server management)
Alarm logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature
high alarm
Temperature ranges 0ºC - 40ºC
Protection degree IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Acoustic noise < 57 dBA < 62 dBA
Weight (kg) 187 244 270
Dimensions (mm) HxWxD 400x815x1040
(*) Depending on power and input/output conditions

10
II. UPS INSTALLATION
2.1 Introduction
WARNING!!!
•Do not apply electrical power to the UPS equipment before the arrival of authorized service
personnel.
•The UPS equipment should be installed only by qualified service personnel.
•The connection of the batteries and the maintenance should be done by qualified service
personnel.
•Do not make any short- circuit to the battery poles. Because of high voltage and high short-
circuit current, there is risk of electrical shock or burn.
•Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings,
watches and all metal objects. Only use tools with insulated handles. Wear rubber gloves.
This chapter contains location installation information of the UPS and the batteries. All the
establishments have their own specialties and needs. So in this part, the installation procedure is
not being explained step by step. Instead, general procedure and the applications are explained
for the technical personnel.
2.2 Unpacking
The UPS is packed and enclosed in a structural cardboard carton to protect it from damage.
1) Inspect for damage that may have occurred during the shipment If any damage is noted, call
the shipper immediately and retain the shipping carton and the UPS.
2) Carefully open the carton and take the UPS out.
3) Retain the carton and packing material for future use.
Unit package contents:
1) A user manual and Guarantee certificate.
2) Battery cabinet and/or shelf (Optional)
3) Battery connection cables.
2.3 Equipment Positioning
ATTENTION: Units are designed to operate on the concrete floor.
1. The equipment’s installation place must be an easy serving place.
2. Install the UPS in a protected area with adequate air flow and free of excessive dust.
3. You must therefore allow for a minimum gap of 250 mm behind the unit to allow adequate air
flow
4. Select a suitable place (temperature between 0°C and 40°C) and the relative humidity (%90
max)
5. It is recommended to place the equipment in an air-conditioned the room (24°C)
6. Temperature is a major factor in determining the battery life and capacity. Keep batteries away
from main heat sources or main air inlets etc.
7. In case of an operating the UPS in a dusty place, clean the air with a suitable air filtration
system.
8. Keep out of your equipment from explosive and flammable items.
9. Avoid direct sunlight, rain, and high humidity.
WARNING!!! Check the capacity of the forklift if it is available for lifting.
DO NOT LEAN OR LIFT THE UPS CABINET AFTER THE BATTERIES HAVE
BEEN INSTALLED.

11
2.4 Connecting the UPS Power Cables
WARNING!!! A separate power line should be used to supply the UPS AC input. Never use the
same line to supply another electrical device. Do not use any additional cable to
increase the length of the UPS’s input cable. It is advised to use an MCCB suitable
for the input current on the UPS’s input line.
The connection of the electrical panel should be supplied by a grounded outlet. Otherwise,
the UPS and the load connected to the output will be left ungrounded. The
grounding system must be checked, and must be strengthen if required. Potential
difference between ground and neutral must be less than 3V AC.
Descriptions of the UPS input output cable connection terminals are shown in figure 2.1
Recommended input line cable and fuse ratings are given in the table below.
NOTES: The neutral conductor should be sized for 1,5 times the output/bypass phase current. These
recommendations are for guideline purposes only and are superceded by local regulations
and codes of practice.
2.5 Safety Earth
The safety earth cable must be connected to the earth BUS BAR and bonded to each cabinet in
the system and also the earthing and neutral bonding arrangements must be in accordance with
the local laws.
ATTENTION!!! Failure to follow adequate earthing procedures can result in electric shock hazard to
personnel, or the risk of fire.
2.6 Cable connection procedure
WARNING!!! All connections of the UPS must be done by qualified service personnel
After positioning the UPS, the cables must be connected as described below:
1. Verify all switches and fuses in front of the UPS are at “0” position. (OFF)
2. Connect the 3 phase AC input coming from the mains distribution panel to the AC input terminals as
shown on the label. (Figure 2.1)
ATTENTION!!!: ENSURE CORRECT PHASE SEQUENCE.
If there is a phase sequence error, UPS doesn’t transfer the load to INVERTER output. If
you can’t see SYNC:OK in the INFORMATION MENU on LCD, then change the input phase sequence.
3. Connect the output of the UPS to the load distribution panel.
4. Connect the battery groups. Refer to battery installation section.
UPS
power
(kVA)
Recommended cable size (mm
2
)
Line
input
Bypass input /
UPS output
External
Battery
Input / output
Cable
connections
U-V-W-N
Battery
connections
+ & -
INPUT
Fuses
Output/
Bypass
Fuses
Battery
Fuses
10 10 10 6
16mm
2
terminal
16mm
2
terminal
50A 32A 32A
20 10 10 10
16mm
2
terminal
16mm
2
terminal
63A 40A 50A
30 16 16 16
16mm
2
terminal
16mm
2
terminal
80A 63A 50A

12
WARNING :
- CHECK BOTH OF THE BATTERY GROUPS FOR CORRECT POLARITY AND VOLTAGE
- DO NOT TURN ON THE BATTERY SWITCH (F5) BEFORE STARTING THE UPS
5. Connect the copper earth bus, to the safety earth of the mains distribution panel.
NOTE : The earth and the neutral connections must be in accordance with the local rules.
WARNING: Note that the Input Neutral (N1) MUST also be connected to K10 terminal
2.6.1 Description of connection terminals of the UPS :
•As shown on the power connection label of the UPS, U1, V1 and W1 phase of the incoming 3 phase
supply are used as the bypass inputs under normal conditions, if there is not a separate bypass supply
(split bypass).
•If there is a separate 3- phase AC supply for bypass (Split Bypass):
a-) Remove the links between K4 – K5, K6 – K7 and K8 – K9.
b-) Connect the phases of the bypass source U2, V2 and W2 to K5, K7 and K9 respectively.
c-) Connect the Neutral (N2) of the Bypass source to K11.
Note that the Neutral of the 3 phase input supply (N1) and the Neutral of the 3-phase bypass supply (N2)
must always be connected together to form the Neutral of the AC output.
Figure 2.2 10-20-30 kVA Cable Connection
Rectifier Inputs
(3 P+N AC)
By-Pass
Input
(3 P+N AC)
UPS Output
(3 P+N AC)
+
+
(+)
Battery
Group
(-)
Battery
Group

13
2.7 Battery Installation
WARNING!!! Be careful while connecting batteries.
ATTENTION!!! Open the battery switch/fuse before making any connection on the batteries.
The batteries associated with the UPS equipment are usually contained in a purpose-built battery cabinet.
Where battery racks are used, they should be sited and assembled in accordance with the battery
manufacturer’s recommendations. In general, batteries require a well-ventilated, clean and dry environment
at reasonable temperatures to obtain efficient battery operation.
In general a minimum space of 10 mm must be left on all vertical sides of the battery block. A minimum
clearance of 20 mm should be allowed between the cell surface and any walls. All metal racks and cabinets
must be earthed.
2 Unpack each battery and check its terminal voltage with a suitable load. Any battery with terminal
voltage less than 10,5V must be charged before installation.
3 Please check the battery connecting hardware and documents. (cables, trays, connection diagrams)
4 Please locate suitable number of batteries on each rack, according to the battery installation and
connection diagram given with the unit.
5 Start locating the batteries from top to the bottom on the racks.
6 Be careful about the connection between the racks and polarities.
7 After interconnecting the batteries, connect “+”, “0” and “-“ leads of the batteries to the battery input
terminals on the UPS. Be careful to connect the batteries correctly and do not turn on (S5) before
checking all connections and before starting the UPS. In DS300T-HF1 Series UPS, 40 blocks of
batteries are connected in series, in such a way that they form two strings of batteries with opposite
polarity; with a center tap connection to the NEUTRAL (N1-N2) internally.
NOTE THAT SEPARATE CABLES FROM EACH BATTERY GROUP SHOULD BE CONNECTED TO K2
TERMINALS TO FORM THE MIDPOINT CONNECTION.
WARNING!!! NEVER TURN ON S5 (BATTERY FUSE) WITHOUT CENTER POINT CONNECTION TO K2.

14
III. FRONT PANEL
3.1 Introduction
The front panel of UPS, consisting of a high resolution TFT screen together with 5 function keys, allows
the complete monitoring of the UPS status including all measurements related to UPS operation. The mimic
flow diagram helps to comprehend the operating status of the UPS. By using the function keys the operator
can move on menus and change some parameters. Touch screen operation is also possible.
Figure 3.1 Control panel oft he UPS
L1 :
Maintenance bypass switch
L2 :
Load on bypass indicator lamp
L3 :
Input voltage indicator lamp
L4 :
Rectifier run pilot lamp
L5 :
Battery operation indicator lamp
L6 :
Load on UPS indicator lamp
L7 :
Output switch on indicator lamp
There are 5 control buttons on the UPS Front panel ,ENTER button provides selection decleration,up and
down buttons provides to surf on menus, (+) and (-) buttons are used for adjustments or option selection.

15
3.2 Front Panel Menu Descriptions :
By using (↑), (↓) and ENTER buttons you can access the following menus. At the end of each menu there
is <ENTER> EXIT message will be showed, if you press enter you will exit to upper menu. All menus have
3 or 4 levels.
Main menu (Level 1)
Men
u
Usage
1 STATUS →Enter Status menu
2 MEASUREMENTS →Enter Measurements menu
3 ALARM LOGS →Enter Alarm logs menu
4 INFORMATION →Enter Information menu
5 OPTIONS →Enter Options menu
6 COMMAND →Enter Command menu
7 TIME →Enter Time menu
8 SERVİCE →Enter Service menu
9 ADJUST →Enter Adjust menu
10 T. CALIB →Enter TFT Panel Calibration menu
Goto 1 →Back to Status Menu
Sub menus (Level 2)
Level 1
Level 2
Page
Level 3
STATUS
STATUS OF THE UPS
MEASUREMENTS
INPUT Input measurements
BYPASS Bypass measurements
INVERTER Inverter measurements
OUTPUT Output measurements
DC DC measurements
GENERAL General measurements
TEMPS (ONLY IN DX 100-250)
ENTER
-
EXIT
ALARM LOGS
UPS
LOG RECORD
Page1
ENTER CLEAR LOG
Page1
INFORMATION RS232 COMM 1:-- Page1
RS232 COMM 2:-- Page1
MAX POWER (VA) Page1
NOMİNAL VALUE Page1
INV VERSİON Page1
PFC VERSİON Page1
LCD VERSİON Page1
MODEL Page1
PROTOCOL Page2
CHASSİS NO Page2
OPTIONS LCD OPTIONS LCD panel options
COMMUNICATION OPTIONS Communication options
ALARM OPTIONS Alarm options
BYPASS OPTIONS Bypass options
COMMAND ENTER <BYPASS> Page1
ENTER <BOOST> Page1
ENTER <B.TEST> Page1
RELAY TEST Page2
ENTER:MODEM INIT Page1
ALARM SOUND : ON/OFF Page1
ENTER - EXIT
TIME
TİME AND DATE ADJUST

16
Level 1
Level 2
P
age
Level 3
SERVİCE
HOURMETER :
Page1
MAXLOAD: 000 000 000
Page1
ENTER <FAULT RESET>
Page1
FAN MAINT :
Page1
BAT MAINT :
Page1
GEN. MAINT :
Page1
LOGOUT....:
Page1
ADJUST
(in English)
GROUP ADJUSTMENTS
Page1
Automatic settings
INVERTER FACTORY OPTİONS
Page1
Options list
RECTİFİER FACTORY OPTİONS
Page1
Options list
PANEL ADJUSTMENTS
Page1
Options list
AC İNPUT ADJUSTMENTS
Page1
AC input settings
AC BYPASS ADJUSTMENTS
Page1
AC bypass settings
AC OUTPUT ADJUSTMENTS
Page1
AC output settings
DC ADJUSTMENTS
Page2 DC settings
POWER ADJUSTMENTS
Page2 Power settings
ENTER - EXIT
T. CALIB.
TFT PANEL CALIBRATION MENU

17
3.2.1 MEASUREMENTS menu
All mesasured values of the UPS can be monitored from this menu.
Use up and down buttons to move on submenu
MEASUREMENTS / INPUT (Level 2)
All rectifier input measurements are located in this menu, use up and down buttons to move on submenu
MEASUREMENTS
/
INPUT
(Level 2)
P-N L1 L2 L3 Page header
V: 221/222/223 V Phase to neutral measured AC input voltages
I: 000/000/000 A Measured RMS AC input phase currents
P-P L1-3 L2-1 L3-2 Page header
V: 381/382/383 V Phase to phase measured AC input voltages
FREQ: 49.6 Hz Measured rectifier input frequency
MEASUREMENTS / BYPASS (Level 2)
All by-pass input measurements are located in this menu, use up and down buttons to move on submenu
MEASUREMENTS
/
BYPASS
(Level 2)
P-N L1 L2 L3 Page header
V: 221/222/223 V Phase to neutral measured AC bypass input voltages
OK OK -- Bypass voltage status
P-P L1-3 L2-1 L3-2
Page header
V: 381/382/383 V
Phase to phase measured AC bypass input voltages
FREQ:
50.0
/
OK Hz
Measured bypass input frequency
MEASUREMENTS / INVERTER MENU (Level 2)
All inverter measurements are located in this menu, use up and down buttons to move on submenu
MEASUREMENTS
/
INVERTER
(Level 2)
P-N L1 L2 L3 Page header
V: 221/222/223 V Phase to neutral measured AC Inverter output voltages
FREQ: 50.0 Hz Measured Inverter output frequency
MEASUREMENTS / OUTPUT MENU (Level 2)
All UPS output measurements are located in this menu, use up and down buttons to move on submenu
MEASUREMENTS
/
OUTPUT
Page 1 (Level 2)
P-N L1 L2 L3 Page header
V: 221/222/223 V Phase to neutral measured AC UPS output voltages
I: 00.0/00.0/00.0 A Measured AC RMS load currents
P-P L1-3 L2-1 L3-2 Page header
V: 381/382/383 V Phase to phase measured AC UPS output voltages
FREQ: 50.0 Hz Measured UPS output frequency
Left previous page, right next page
MEASUREMENTS
/
OUTPUT
Page 2 (Level 2)
L1 L2 L3 Page header
Load 000/000/000 % Measured load percentage
KW 000.0/000.0/000.0 Measured output watt power
KVA 000.0/000.0/000.0 Measured output KVA power
PF: ---- ---- ---- Load power factor
C.F: 0.0 / 0.0 / 0.0 Load crest factor
Left previous page, right next page
Table of contents
Other Tescom UPS manuals

Tescom
Tescom TEOS 400E-EB PRO User manual

Tescom
Tescom CL115D Series User manual

Tescom
Tescom 400 VA User manual

Tescom
Tescom DS300SHPA Series User manual

Tescom
Tescom DS3100 User manual

Tescom
Tescom DS3250A User manual

Tescom
Tescom NEOLINE PLUS 1102ST User manual

Tescom
Tescom CL110D User manual

Tescom
Tescom XA-200P Series User manual

Tescom
Tescom AVR 11 User manual

Tescom
Tescom DS300S Series User manual

Tescom
Tescom DS3200H User manual

Tescom
Tescom T-3250P User manual

Tescom
Tescom DS310HB User manual

Tescom
Tescom DS3100A User manual

Tescom
Tescom T-102 User manual

Tescom
Tescom DS300HT Series User manual

Tescom
Tescom DS300-110 Series User manual

Tescom
Tescom DS300T Series User manual

Tescom
Tescom T-3250 User manual