1.4 Technical Specifications
MODEL DS310H DS315H DS320H DS330H
Output (KVA) 10 kVA 15 kVA 20 kVA 30 kVA
Output (KW) 9 kW 13,5 kW 18 kW 27 kW
Output Power Factor 0,9
INPUT
Number of Phases 3 Phase + Neutral
Input Voltage 220/380, 230/400 or 240/415 Vac
Input Voltage Tolerance +20% , -25% (+15% at 240/415Vac)
Input Power Factor (PF) 0,98 - 0,99 (at full load)
Input THDI <= 4% (at full load)
Input Frequency 50 Hz. ±5%
By-pass Voltage 220/380, 230/400 or 240/415 Vac 3 Phase + Neutral
By-pass Frequency 50 Hz. ±2%
RFI Level EN62040-2
OUTPUT
Number of Phases 3 Phase + Neutral
Output Voltage 220/380, 230/400 or 240/415 Vac
Output Voltage Tolerance ±1%
Output Frequency 50 Hz.
Output Frequency Tolerance (Synchronous) ±2%
Output Frequency Tolerance (Battery) ±0,2%
Efficiency (100% Load) up to 94%
Load Crest Factor 3:1
Output Voltage THD (linear load) <3%
Overload 125% Load 10min. , 150% Load 1min.
BATTERY
Total Number 60 blocks 12V (2x30 serial 60 batteries)
Float Charge Voltage (25
C) ±405V DC
End of Discharge Voltage ±300V DC
Battery Test Automatic and Manual
Boost Charge Available
COMMUNICATION INTERFACES
RS232 Com Port 2 each standard (COM1 and COM2)
External Temperature Measurement Input Available (standard)
RS485 Comm. Port Optional
Remote Monitoring Panel Optional
SNMP Adapter Optional
Modbus Adapter Optional
Alarm Relay Contacts 4 each dry contacts (function programmable) 8 optional
Digital Inputs 2 each optional
Emergency Power-Off Input Available (standard)
ENVIRONMENT
Operating Temperature 0 – 40
C
Operating Humidity <= %90 (non-condensing)
Acoustic Noise <55dB <57dB <61dB
Dimensions (WxDxH) (mm) 400x815x1035
Device Type and Protection Class Class 1 – IP20
Weight (Without Batteries) (app. kgs) 87 91 100
H MODELS / P.F = 0,9 DS330H DS340H DS360H DS380H DS3100H DS3120H DS3160H DS3200H DS3250H DS3300H DS3400H
TESCOM CODE UPS.0647 UPS.0276 UPS.0649 UPS.0650 UPS.0651 UPS.0652 UPS.0653 UPS.0654 UPS.0655 UPS.0656 UPS.0321
HB MODELS / P.F = 1 DS330HB DS340HB DS360HB DS380HB DS3100HB DS3120HB DS3160HB DS3200HB DS3250HB DS3300HB DS3400HB
TESCOM CODE UPS.0641 UPS.0555 UPS.0556 UPS.0557 UPS.0558 UPS.0559 UPS.0560 UPS.0561 UPS.0671 UPS.0616 UPS.0642
Power (kVA) 30 40 60 80 100 120 160 200 250 300 400
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz , ± 5%
Power factor (at 100% load) ≥ 0.99
THDI (*) ≤ 3%
By-pass voltage 380/400 VAC 3 Phase + N, ± 10%
Voltage distortion ≤ 10%
Protections Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequence indicator
OUTPUT
Power (kW) H Models P.F = 0,9 27 36 54 72 90 108 144 180 225 270 360
Power (kW) HB Models P.F = 1 30 40 60 80 100 120 160 200 250 300 400
Power factor H MODELS = 0.9 / HB MODELS =1
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency up to 95%
Crest factor 3:1
Overload capacity 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
Voltage THD ≤ 3% (at 100% linear load)
BATTERY
Type VRLA AGM / GEL / NiCd
Number of batteries 2x30 (±30) : 60 pieces
Charge voltage 2x405 VDC
End of discharge voltage 2x300 VDC
Battery cabinet Internal External
Battery ambient temperature 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic testing Standard every 72 hours (adjustable)
GENERAL
Standards EN62040-1, EN62040-2, EN62040-3
User interface 4 lines LCD panel, Mimic LEDs, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset kit Standard (programmable)
Software Standard T-Mon UPS Management Software (3 clients + 1 server management)
Alarm logging Standard: with time & date 512 events
Protections Power module over-temperature, Over-current, Temperature high alarm
Temperature ranges 0ºC - 40ºC
Protection degree IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Acoustic noise < 57 dBA < 62 dBA < 65 dBA < 68 dBA
Net weight (kg) 100 173 197 209 220 232 265 470 525 635 680
Dimensions (mm) HxWxD 1040x400x815 1440x515x855 1900x880x775 1900x1250x775
OPTIONS
Transformer Galvanic isolation transformer at the input & output (internal)
Software T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parallel operation up to 8 units