Tesla POWERWALL 2 AC User manual

Powerwall 2 AC Installation Manual
with Backup Gateway

For the latest Powerwall installation documents in all supported languages, visit:
www.tesla.com/support/powerwall.
To secure the full 10-year product warranty, Powerwall must be registered by
completing the commissioning process and sending system information to Tesla.
Warning: Read this entire document before installing or using Powerwall. Failure to
do so or to follow any of the instructions or warnings in this document can result in
electrical shock, serious injury, or death, or can damage Powerwall, potentially
rendering it inoperable.
PRODUCT SPECIFICATIONS
All specifications and descriptions contained in this document are verified to be
accurate at the time of printing. However, because continuous improvement is a goal
at Tesla, we reserve the right to make product modifications at any time.
The images provided in this document are for demonstration purposes only.
Depending on product version and market region, details may appear slightly
different.
ERRORS OR OMISSIONS
To communicate any inaccuracies or omissions in this manual, send an email to:
energy-pub[email protected].
ELECTRONIC DEVICE: DO NOT THROW AWAY
Proper disposal of batteries is required. Refer to local codes for disposal
requirements.
MADE IN THE USA
©2017 TESLA, INC. All rights reserved.
All information in this document is subject to copyright and other intellectual property rights
of Tesla, Inc. and its licensors. This material may not be modified, reproduced or copied, in
whole or in part, without the prior written permission of Tesla, Inc. and its licensors. Additional
information is available upon request. The following are trademarks or registered trademarks
of Tesla, Inc. in the United States and other countries:
TESLA
TESLA MOTORS
POWERWALL
All other trademarks contained in this document are the property of their respective owners
and their use herein does not imply sponsorship or endorsement of their products or services.
The unauthorized use of any trademark displayed in this document or on the product is
strictly prohibited.

1
TABLE OF CONTENTS
Powerwall Electrical Specifications ........................................................................................................................................................................5
Powerwall Environmental Specifications .............................................................................................................................................................5
Powerwall Mechanical Specifications ....................................................................................................................................................................6
Backup Gateway Electrical Specifications ..........................................................................................................................................................6
Backup Gateway Environmental Specifications ...............................................................................................................................................6
Backup Gateway Mechanical Specifications ......................................................................................................................................................6
Powerwall Physical Requirements........................................................................................................................................................................... 7
Powerwall Dimensions and Space Requirements ............................................................................................................................................8
Powerwall Temperature Requirements ................................................................................................................................................................8
Powerwall Installation Requirements .....................................................................................................................................................................9
Backup Gateway Installation Requirements.......................................................................................................................................................9
Powerwall Box Contents............................................................................................................................................................................................ 10
Backup Gateway Box Contents.............................................................................................................................................................................. 10
Required Tools................................................................................................................................................................................................................ 10
Required Supplies............................................................................................................................................................................................................11
Step 1. Plan the Installation Site ................................................................................................................................................................................11
Step 2. Transport and Unpack Powerwall ..........................................................................................................................................................12
Step 3. Anchor the Powerwall Mounting Bracket.......................................................................................................................................... 14
Step 4. Prepare Powerwall for Mounting ............................................................................................................................................................21
Step 5. Mount Powerwall on the Bracket.......................................................................................................................................................... 23
Step 6. Prepare the Backup Gateway for Mounting .................................................................................................................................... 25
Step 7. Mount the Backup Gateway .....................................................................................................................................................................27
Step 8. Connect Powerwall and the Backup Gateway ............................................................................................................................... 29
Step 9: Connect a Demand Response Controller (Australia and New Zealand only)................................................................ 34
Step 10: Make AC Power Connections ............................................................................................................................................................... 35
Step 11. Install Energy Metering for the System ............................................................................................................................................. 37
Step 12. Close the Wiring Compartments and Turn On the System ....................................................................................................46
Step 13. Commission the System .......................................................................................................................................................................... 47
Step 14. Finish and Demonstrate the Installation ..........................................................................................................................................49
Troubleshooting............................................................................................................................................................................................................50
Technical Support ..........................................................................................................................................................................................................51
Maintenance ......................................................................................................................................................................................................................51

2 Powerwall Installation Manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions for the Tesla Powerwall 2 AC and Backup
Gateway that must be followed during installation and maintenance of the system.
Powerwall and Backup Gateway installation and service require knowledge of low voltage
electricity and should only be performed by Tesla Certified Installers. Tesla assumes no liability
for injury or property damage due to repairs attempted by unqualified individuals or a failure
to properly follow these instructions. These warnings and cautions must be followed when
using Powerwall and the Backup Gateway.
Symbols Used
These symbols indicate important safety information in this guide or on the equipment:
WARNING: indicates a hazardous situation which, if not avoided, could result in injury
or death.
CAUTION: indicates a hazardous situation which, if not avoided, could result in minor
injury or damage to the equipment.
NOTE: indicates an important step or tip that leads to best results, but is not safety or damage
related.
REFER TO OPERATING INSTRUCTIONS: indicates that user should refer to
operating or installation instructions before proceeding.
RISK OF ELECTRIC SHOCK: indicates components that present risk of electrical
shock.
CAUTION, RISK OF ELECTRIC SHOCK, ENERGY STORAGE TIMED
DISCHARGE. Discharge time is 5 minutes from de-energization.
BIDIRECTIONAL TERMINAL: Indicates location of combined input/output connector
on the equipment.
PROTECTIVE CONDUCTOR TERMINAL: Indicates location of grounding connection
on the equipment.

3
General Information
WARNING: Read this entire document before installing or using Powerwall. Failure to do
so or to follow any of the instructions or warnings in this document can result in electrical
shock, serious injury, or death, or may damage Powerwall, potentially rendering it inoperable.
WARNING: A battery can present a risk of electrical shock, fire, or explosion from vented
gases. Observe proper precautions.
WARNING: Powerwall installation must be carried out only by Tesla Certified Installers
who have been trained in dealing with low voltage electricity.
WARNING: Powerwall is heavy. Use of lift equipment is recommended.
WARNING: Use Powerwall only as directed.
WARNING: Do not use Powerwall if it is defective, appears cracked, broken, or otherwise
damaged, or fails to operate.
WARNING: Before beginning the wiring portion of the installation, ensure that Powerwall
is switched off, and open any associated circuit breakers and disconnect switches (if
applicable for the installation).
WARNING: Do not attempt to open, disassemble, repair, tamper with, or modify
Powerwall. Powerwall and its components are not user serviceable. Batteries in Powerwall are
not replaceable. Contact the Tesla Certified Installer who installed the system for any repairs.
WARNING: To protect Powerwall and its components from damage when transporting,
handle with care. Do not impact, pull, drag, or step on Powerwall. Do not subject Powerwall to
any strong force. To help prevent damage, leave Powerwall in its shipping packaging until it is
ready to be installed.
WARNING: Do not insert foreign objects into any part of Powerwall.
WARNING: Do not expose Powerwall or its components to direct flame.
WARNING: Do not install Powerwall near heating equipment.
WARNING: Do not immerse Powerwall or its components in water or other fluids.

4 Powerwall Installation Manual
CAUTION: Do not use solvents to clean Powerwall, or expose Powerwall to flammable or
harsh chemicals or vapors.
CAUTION: Do not use fluids, parts, or accessories other than those specified in this
manual, including use of non-genuine Tesla parts or accessories, or parts or accessories not
purchased directly from Tesla or a Tesla-certified party.
CAUTION: Do not place Powerwall in a storage condition for more than one (1) month, or
permit the electrical feed on the Powerwall to be severed for more than one (1) month,
without placing Powerwall into a storage condition in accordance with Tesla’s storage
specifications.
CAUTION: Do not paint any part of Powerwall, including any internal or external
components such as the exterior shell or casing.
CAUTION: Do not connect Powerwall directly to photovoltaic (PV) solar wiring.
CAUTION: When installing Powerwall in a garage or near vehicles, keep it out of the
driving path. If possible, install Powerwall on a side wall and/or above the height of vehicle
bumpers.
Environmental Conditions
WARNING: Install Powerwall in a location that prevents damage from flooding.
WARNING: Operating or storing Powerwall in temperatures outside its specified range
might cause damage to Powerwall.
WARNING: Do not expose Powerwall to ambient temperatures above 60°C (140°F) or
below -30°C (-22°F).
CAUTION: Ensure that no water sources are above or near Powerwall, including
downspouts, sprinklers, or faucets.
CAUTION: Ensure that snow does not accumulate around Powerwall.

5
1. Registering Powerwall
Tesla Powerwall comes with a warranty whose term depends on the connection of Powerwall
to the Internet.
To secure the full 10-year warranty for Powerwall, it must be reliably connected to the Internet
to allow remote firmware upgrades from Tesla. If an Internet connection is not established or is
interrupted for an extended period, and Tesla is unable to contact the owner, the warranty
may be limited to 4 years. To ensure that the owner can receive the full 10-year warranty, be
sure to complete the commissioning process so that registration information is sent to Tesla.
For more information, refer to the Powerwall Warranty for your region at www.tesla.com.
2. Specifications
Powerwall Electrical Specifications
Energy1
13.5 kWh
AC Voltage (Nominal)
230 V
Maximum Continuous Current
25 A
Frequency (Nominal)
50/60 Hz
Real Power, max continuous
5 kW (charge and discharge)
Apparent Power, max continuous, 1.0 pf
5 kVA (charge and discharge)
Power Factor Output Range
+/- 1.0 adjustable
Overvoltage Category
Category III
Maximum Supply Fault Current
10 kA
Maximum Output Fault Current
32 A rms
Maximum Inrush Current
0.4 A
Round Trip Efficiency (Beginning of Life)1
> 90%
1Values provided for 25°C (77°F), 3.3 kW charge/discharge power
Powerwall Environmental Specifications
Operating Temperature2
-20°C to 50°C
Operating Humidity (RH)
Up to 100%, condensing
Storage Conditions (up to 12 months)
-20°C to 30°C
Up to 95% RH, non-condensing
State of Energy (SoE): 25% initial
Maximum Altitude
3000 m
Noise Level @ 1 m
< 40 dBA at 30°C
Ingress Rating
IP67 (battery and power electronics)
IP56 (wiring)
Wet Location Rating
Yes
Pollution Degree Rating
PD3
Seismic Rating
AC156, IEEE 693-2005 (high)
2Performance may be de-rated in extreme ambient temperatures.

6 Powerwall Installation Manual
Powerwall Mechanical Specifications
Height
1150 mm
Width
755 mm
Depth
155 mm
Weight
125 kg
Backup Gateway Electrical Specifications
Disconnect Current
200 A
Overvoltage Category
Category III
AC Meter
Revenue grade
Backup Gateway Environmental Specifications
Operating Temperature
-20°C to 50°C
Operating Humidity (RH)
Up to 100%, condensing
Maximum Altitude
3000 m
Ingress Rating
IP44
Pollution Degree Rating
PD3
Backup Gateway Mechanical Specifications
Height
691 mm
Width
378 mm
Depth
129 mm
Weight
16.4 kg

7
3. Site Requirements
Powerwall Physical Requirements
Powerwall can be mounted on a floor or wall. When floor-mounted, it must also be anchored
to an adjacent wall. In both types of installation, the wall must be capable of supporting the full
weight of Powerwall and its mounting hardware. The wall must extend to all edges of the
system, allowing no access to the back of the unit once it is mounted.
Powerwall includes a mounting bracket (Fig. 1) that supports the unit in both floor- and wall-
mount configurations, and includes shims to level the unit in floor-mount configurations. Do
not use other hardware to anchor Powerwall to the wall or floor.
Figure 1: Powerwall 2 Mounting Bracket Dimensions
Powerwall requires adequate clearance for installation, cabling, and airflow. Do not mount any
other objects within the clearance space (Fig. 2), except those explicitly required by the
installation (for example, conduit, a junction box, or an electrical disconnect, depending on
local installation codes). Do not install anything above Powerwall that limits access to the unit
or that might fall and damage the unit. Do not mount Powerwall horizontally or upside down.
NOTE: Powerwall has a pump and fan that enable Powerwall to maintain ideal battery
temperature. They produce a gentle hum during operation, comparable to a typical
refrigerator. The noise level depends on the ambient temperature and the power level of
operation. Consider these noise levels when choosing where to install Powerwall.

8 Powerwall Installation Manual
Powerwall Dimensions and Space Requirements
Figure 2: Powerwall 2 Dimensions and Space Requirements
Powerwall Space Requirements
Minimum lateral wall space
960 mm
Minimum clearance from left side (air intake)
50 mm
Minimum clearance from right side (air exhaust)
150 mm
Minimum clearance above single Powerwall
50 mm
Minimum clearance above side-by-side Powerwalls
300 mm
Minimum clearance between side-by-side Powerwalls
250 mm
Maximum height above ground
1.5 m to bottom of unit
Maximum slope
+/– 2° side-to-side
+/– 5° front-to-back
Powerwall Temperature Requirements
Powerwall is capable of charging and discharging within the full ambient temperature range
listed in the Specifications section. At the high and low ends of the temperature range,
Powerwall may limit charge or discharge power based on battery cell temperature to improve
battery lifespan.
Installation in full sun raises the temperature inside the enclosure above ambient temperature.
This temperature rise is not a safety risk, but may impact battery performance. To optimize
performance, avoid installing Powerwall in locations that are exposed to the sun for extended
periods.
Do not install Powerwall in locations with sustained high or low temperatures. The average
ambient temperature over the system's life should be between 0°C and 30°C.

9
Powerwall Installation Requirements
Powerwall comes with a separate Backup Gateway and power meter to enable integration
with solar systems and the electrical grid. The Backup Gateway communicates with the
system by means of wireless and wired connections. Wiring and conduit (where required)
must be provided by the installer. Where conduit is required, the installation must comply with
local codes.
AC disconnect and interconnection requirements between the Powerwall system and the main
switchboard are subject to local codes. Ensure that the installation meets local disconnect and
interconnection requirements.
When Powerwall is installed in a dwelling unit, fire detection and protection equipment should
be installed in accordance with local building and fire codes.
All installations must conform to the laws, regulations, codes, and standards applicable in the
jurisdiction of installation.
Backup Gateway Installation Requirements
The Backup Gateway must be wall-mounted and can be configured for cable entry at the top,
bottom, or sides of the enclosure. It requires adequate clearance for installation and cabling or
conduit. Wiring and conduit (where required) must be provided by the installer. Where
conduit is required, the installation must comply with local codes.
Mount the Backup Gateway vertically, in the orientation shown below (Fig. 3). Do not mount
the Backup Gateway enclosure horizontally or upside down.
All installations must conform to the laws, regulations, codes, and standards applicable in the
jurisdiction of installation.
Figure 3: Backup Gateway Dimensions

10 Powerwall Installation Manual
4. Installation Instructions
Powerwall Box Contents
•Powerwall 2 AC unit
•Mounting bracket
•Accessory bag containing:
o(1) 3-pin male to 2-terminal female, 2-conductor AC power harness (600 V, 105 deg C)
o(1) 2-pin terminal block connector (green) for AC power connection
o(1) 4-pin terminal block connector (black) for connection to Backup Gateway
o(1) 4-pin terminal block connector (green) with 120-Ohm terminating resistor
o(1) T20 Torx driver bit
o(1) drillable threaded cable gland for side cable entry into Powerwall, with lock washer
o(2) 25 mm reducing washers for side cable entry port into Powerwall
o(1) 32-mm reducing washer for side cable entry port into Powerwall
o(1) 35-mm rubber grommet for back cable entry port into Powerwall
o(2) shims for leveling floor-mounted units
o(1) Safety Instructions document
•On the outside of the box: printed Tesla Battery Emergency Response Guide (ERG)
Backup Gateway Box Contents
•(1) Backup Gateway enclosure
•(1) Powerwall 2 AC Owner’s Manual
•(1) Meter Kit containing:
o(1) Voltage line harness
o(1) Antenna extension cable
o(2) 3-pin wiretaps
o(2) Antenna extension knockout plugs (1/2-inch and 3/4-inch)
o(2) 4 mm2wire jumpers
o(2) Self-drilling screws for mounting the meter
o(1) Wirenut
Required Tools
•Personal protective equipment (safety glasses, gloves, protective footwear)
•Drill and drill bit for drilling pilot holes in mounting surface
•Torque screwdriver with 1/4-inch bit holder (for the provided T20 Torx bit)
•Large (5 mm) flathead driver bit (for ground bar)
•Small (2 mm) flathead screwdriver (for wiring connector spring terminals)
•Torque wrench with 5/16-inch Allen bit (for Backup Gateway power connections)
•Wire strippers/cutters for 0.2 mm2to 120 mm2wires
•Installation tools (level, stud sensor, tape measure, pencil, painter’s tape, flashlight)
•Lift equipment capable of lifting and supporting 125 kg
•Ratcheting strap to secure Powerwall to lift equipment
•Digital camera or smartphone for documenting the installation
WARNING: Powerwall is heavy. Wear appropriate personal protective equipment (such as gloves
and protective footwear) when handling the unit. Only a sufficient number of trained movers should lift
Powerwall. Use of lift equipment is recommended.

11
Required Supplies
•Mounting bracket hardware (see “Step 3: Anchor the Powerwall Mounting Bracket”)
•Conduit fitting or cable gland (depending on local electrical requirements)
•Conduit or raceway (depending on local electrical requirements)
•Minimum 300 V rated 4-conductor or double-insulated (with one twisted pair) shielded copper
(Cu) cable (for communication connection between Powerwall and the Backup Gateway)
•Minimum 600 V, 90 deg C rated copper (Cu) cable (for power connections to Powerwall and the
Backup Gateway)
•Siemens HS-style conduit hub (for sealed entry into the top of the Backup Gateway enclosure)
Step 1. Plan the Installation Site
The installation location for Powerwall must accommodate placement of the Backup Gateway
and meet all conditions described above in “Site Requirements.” In addition, consider the
following points when choosing where to install Powerwall.
Wall mounting: Choose a wall capable of supporting the full weight of Powerwall, with one of
the following characteristics: wood studs at regular intervals, plywood sheeting of sufficient
thickness, solid concrete or masonry, or metal studs of sufficient gauge.
Floor mounting: Choose a level surface adjacent to a wall space that meets all the
requirements for wall mounting described above. Make sure the area is isolated from hazards
that may damage the unit, such as vehicle traffic or flooding.
Cable entry: Determine whether cables will be routed into Powerwall from the side or from the
back of the unit. With side cable entry, a conduit fitting or cable gland must be used to seal
the entry into the wiring compartment. With back cable entry, a wire cover should be used to
seal the entry into the wiring compartment.
NOTE: If Powerwall is mounted on a wall with studs spaced 24 in (610 mm) apart, cable entry
from the back of Powerwall may be blocked.
Backup Gateway configuration: Determine whether cable entry into the Backup Gateway will
be from the top, bottom, or side. (Optional: when cable entry is from the bottom half of the
enclosure, the back panel of the unit may be rotated 180 degrees to simplify cable runs.)
NOTE: For cable entry at the top of the Backup Gateway enclosure, an HS-style hub should be
used in order to maintain enclosure ingress protection.
Electrical service connection: The Backup Gateway is service entrance rated, and can be
located between the main switch and the switchboard.

12 Powerwall Installation Manual
Cable gauge and length: Powerwall requires cable connections to the Backup Gateway, main
switchboard, and an Internet router. Position Powerwall, the Backup Gateway, and other
electrical components to minimize cable lengths, based on local code requirements.
Cable Type Connection Cable Gauge Maximum
Cable Length
Power Powerwall to main switchboard 6-10 mm245 m
Power Backup Gateway to main switchboard 16–120 mm2[Local Code]
Communication Powerwall to Backup Gateway
4-conductor shielded
(1 twisted pair),
1.5 mm2
- or -
CAT5 (shielded)
50 m
Communication Backup Gateway to wireless router CAT5 (shielded) 45 m
Conduit or raceway: Calculate the amount and size of conduit or raceway needed for the
installation, based on fill limits and local code requirements. With conduit, an adapter may be
required between the entry into the Powerwall wiring compartment and the conduit.
Step 2. Transport and Unpack Powerwall
CAUTION: Powerwall is heavy. Wear appropriate personal protective equipment (such as
gloves and protective footwear) when handling the unit. Only a sufficient number of trained
movers should lift Powerwall. Use of lift equipment is recommended. For more information,
refer to Powerwall 2 Transportation and Storage Guidelines.
1. Keep Powerwall in its box until ready for installation. Store the box flat on its back (front
facing up) during transport. The box can be carried in any orientation to the job site.
2. Open the box by cutting the packing straps, removing the lid, and setting it aside.
3. Remove the box containing the mounting bracket and the bag containing the accessories.
Figure 4: Removing the Mounting Bracket Box and Accessory Bag

13
4. Verify that the contents of the bracket box and accessory bag are complete and
undamaged (see “Powerwall Box Contents,” above).
5. Remove the top panel and set it aside.
Figure 5: Removing the Top Panel
6. Find the bottom of Powerwall by identifying the feet at the base of the unit.
7. Remove the piece of foam next to the bottom of Powerwall.
8. Open the bottom edge of the box (nearest the bottom of Powerwall) by removing the
staples and folding the cardboard back.
Figure 6: Opening the Bottom of the Powerwall Box
9. Optional: Remove the foam blocks from the top panel and use the cardboard as protective
padding on the lift equipment.
10. Move the lift equipment into place next to the bottom of the Powerwall box.

14 Powerwall Installation Manual
11. Grasp the top of the Powerwall and carefully tilt it upright until it sits vertically in the box,
with the front of the unit facing the lift equipment.
Figure 7: Removing Powerwall from Its Box
12. Position the Powerwall on the lift equipment, with the mounting cleats facing away from
the lift equipment.
13. Strap the Powerwall to the lift equipment with a ratcheting tie-down strap.
Step 3. Anchor the Powerwall Mounting Bracket
1. Before mounting the wall bracket, double-check that the mounting location will allow access
to the chosen cable entry port (side or back) during installation. If applicable, use a stud
sensor to locate and mark the centers of the studs in the wall.
2. Determine the appropriate type and number of fasteners for the mounting bracket location.
Be sure to take into account the thickness of the mounting bracket, washers, and wall material
when choosing fasteners. The following guidelines apply to both wall- and floor-mount
installations.
NOTE: The details below are minimum guidelines and are not guaranteed to be applicable.
Refer to local building codes to ensure the use of appropriate fasteners. Refer to Powerwall 2
Anchorage Details for complete mounting information.

15
Wood Studs (spaced from 300 mm to 600 mm)
•If anchoring directly into wood studs, use at least four (one in each corner) 10 mm
wood screws with washers, of sufficient length for at least 64 mm embedment into the
studs.
Figure 8: Anchoring the Bracket to Wood Studs
•If anchoring to blocking between wood studs, use minimum 50 mm x 100 mm blocks,
end-nailed into studs with two 16d (100 mm) nails or toe-nailed into studs with four 8d
(75 mm) nails. Use at least four (one in each corner) 10 mm wood screws with
washers, of sufficient length for at least 64 mm embedment into the blocking.
Figure 9: Anchoring the Bracket to Blocking between Wood Studs

16 Powerwall Installation Manual
Plywood
•If anchoring to plywood wall material, the plywood must be minimum 38 mm thick. Use
at least four (one in each corner) 10 mm wood screws with washers, of sufficient
length to penetrate at least 7 mm beyond the backside of the plywood.
Figure 10: Anchoring the Bracket to Plywood
Metal Studs (spaced from 300 mm to 600 mm)
•If anchoring directly to metal studs, studs must be minimum 1.2 mm thick. Use at least
four (one in each corner) 10 mm sheet metal screws with washers, of sufficient length
to penetrate at least 3 threads beyond the stud.
Figure 11: Anchoring the Bracket to Metal Studs

17
•If anchoring to backing between metal studs, studs must be minimum 0.5 mm thick,
and backing must be minimum 0.7 mm thick. Use at least eight (two in each corner)
10 mm sheet metal screws with washers, of sufficient length to penetrate at least 3
threads beyond the backing.
Figure 12: Anchoring the Bracket to Metal Backing
•If anchoring to backing between metal studs in an outdoor high wind area, studs must
be minimum 0.5 mm thick, and backing must be minimum 0.7 mm thick. Use at least
twelve (three in each corner) 10 mm hexhead sheet metal screws with washers, of
sufficient length to penetrate at least 3 threads beyond the backing.
Figure 13: Anchoring the Bracket to Metal Backing – High Wind Area

18 Powerwall Installation Manual
Concrete or Masonry
•Minimum strength must be 18 MPa (concrete), 12 MPa (clay brick), or 11 MPa (masonry).
•Use at least four (one in each corner, in any available anchor slot) 10 mm fasteners
with washers, of sufficient length for at least 50 mm embedment into the material.
Figure 14: Anchoring the Bracket to Concrete or Masonry
Channel Strut (Unistrut)
•Struts must be minimum 42 mm x 42 mm x 2.5 mm thick.
•If mounting on wood studs, attach the strut to at least three studs, using at least one
10 mm wood screw with washer per stud, of sufficient length for at least 64 mm
embedment into the studs.
•If mounting on metal studs, attach the strut to at least three studs, using at least two
10 mm sheet metal screws with washers per stud, of sufficient length to penetrate at
least 3 threads beyond the studs.
•To attach the bracket to the struts, use at least four (one in each corner) 10 mm
hexhead screws with washers and strut nuts.
Figure 15: Anchoring the Bracket to Channel Strut
Other manuals for POWERWALL 2 AC
6
Table of contents
Popular Storage manuals by other brands

Transcend
Transcend StoreJet 25F user manual

BIOS AP
BIOS AP DVT10U3 user manual

Lexar
Lexar MOBILE MICROSD - DATASHEET REV A datasheet

Cowon
Cowon HI-SPEED USB 2.0 FLASH DISK - TYPE 1 user guide

Sans Digital
Sans Digital Towerraid TR4UT-B Detailed user guide

MCE Technologies
MCE Technologies Xcaret Pro installation guide