thermastor 4028407 User manual

INSTALLER’S & OWNER’S MANUAL
HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER
Dehumidifier & Ventilation System Controller
© 2015 Therma-Stor LLC •Manual P/N TS-1028 11/17 Rev A
4201 Lien Road, Madison, WI 53704 •TOLL-FREE (800)-533-7533 •www.thermastor.com •sales@thermastor.com
DEH3000R
DEH3000R
Part No. 4028407

Table of Contents
1. Contents & Specifications ............................................... 2
2. Installation...................................................................... 2
2.1 Install Instructions ...................................................... 2
2.2 Wiring......................................................................... 3
2.3 Auxiliary Relay, A/C Lockout or Run Central Fan.......... 3
2.4 Dehumidifier, Activate/De-Activate with A/C Unit......... 4
2.5 Testing ....................................................................... 5
2.6 Troubleshooting.......................................................... 5
3. Operation....................................................................... 6
3.1 Display....................................................................... 6
3.2 Setting ....................................................................... 6
3.3 On/Off and Display items............................................ 6
3.4 Setting Clock Time ..................................................... 6
3.5 Adjusting the Relative Humidity Setpoint..................... 6
3.6 Temperature Cutout Programming.............................. 7
3.7 Fan Setting & Operation ............................................. 7
3.8 Damper Operation and Ventilation,
Manual (Hold) mode ......................................................... 8
3.9 Damper Operation and Ventilation,
Programmed Ventilation ................................................... 8
5.0 DEH3000R ............................................................... 10
5.1 Remote Sensor Usage ........................................... 10
5.2 Install and Wiring Instructions................................ 10
Warranty ........................................................................ 11
Read and Save These Instructions
WARNING! — This symbol means important
instructions. Failure to heed them can result in serious
injury or death.
1. Specifications
Part # (P/N): 4028407
Model: DEH 3000R
Operating Voltage: 24 VAC
Max Current - DMP, COMP, FAN 1 AMP each
Humidity Range/Accuracy: 10 – 95% RH,
±
5%
Auxillary Relay Capacity: 5 Amps, 24VAC
Temp Range/Accuracy: 30°-90°F, 2%
Size: 4.95"L x 1.06"W x 4.19"H
2. Installation
Install the DEH 3000R remote sensor in a central area of
the structure where it will sense the relative humidity of the
structure accurately. Do not install the remote sensor where it
may not accurately sense the relative humidity such as near
HVAC supply registers, near exterior doors and windows, or
near a pool or spa. Install in accordance with all applicable
codes and standards.
2.1 Install Instructions
1. Separate the front panel from the back panel by depressing
the middle sections of the top and bottom of the front
panel.
2. Locate the wiring access hole in the wall or other flat
mounting surface. Place the back panel into position and
drill the appropriate mounting holes.
3. Insert the screws and tighten. Level as necessary.
4. Make the electrical connections to the terminals on the
back panel as shown in the applicable wiring diagram (see
Sections 2.2-2.4).
5. Test the installation (see Section 2.5).
2
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
24 V COM
DMPR DEHU FAN
ON-Detect
Common
OFF-Detect
Normally Open
Common
Normally Closed
Optional
Use
Optional
Use
Mounting Hole
Mounting Hole

3
2.2 Wiring
WARNING! DO NOT ALLOW THE YELLOW WIRE
OR +24V TERMINAL ON THE ULTRA-AIRE DEHUMIDIFIER
TO COME IN ELECTRICAL CONTACT WITH THE RED/WHITE
WIRES OR COM/DMPR TERMINALS ON THE ULTRA-AIRE
DEHUMIDIFIER OR DAMAGE TO THE TRANSFORMER WILL
RESULT.
WARNING! THE REMOTE CONTROL OF THE
ULTRA-AIRE DEHUMIDIFIER OPERATES ON A LOW VOLTAGE
CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE
CONNECTED TO A HIGH VOLTAGE CIRCUIT.
WARNING! UNPLUG THE ULTRA-AIRE
DEHUMIDIFIER BEFORE WIRING THE DEH 3000R.
The installer must supply all field wiring, including the wiring
between the Ultra-Aire dehumidifier and the DEH 3000R. Some
of the control wires or terminals on the dehumidifier may not be
used in some control situations and should be left disconnected
with wire nuts taped onto the stripped ends (if necessary).
Be sure to consult the electrical schematic in this manual or
the internal electrical box of the Ultra-Aire dehumidifier before
making any control connections.
WARNING! ONLY CONNECT THE DMPR
TERMINAL TO THE CONTROL IF IT IS WIRED IN A
CIRCUIT THROUGH AN ELECTRIC DAMPER, OTHERWISE
TRANSFORMER DAMAGE MAY RESULT.
The White wire controls the optional motorized damper
that can be installed into a fresh air duct. This damper
provides the ability to control fresh air ventilation using
the ventilation timer function of the DEH 3000 and the
terminal labeled “DMP” on the DEH 3000 (See Section
3.8). Leave the “DMP” terminal unused if a motorized
damper is not used, and cap off the White wire from
the Ultra-Aire dehumidifier.
Standard Wire Colors for Thermostats:
24VAC Red R
Call for Heat White W or W1
Force Fan On Green G
Compressor
Call for Cooling Yellow Y or Y1
Terminal Block Control Operation:
Terminal Function
COM 24Vac Power Transformer Neutral Side
FAN Fan Control
24V Transformer High Side
DEHU Dehumidification (Fan and Compressor Control)
DMPR 24Vac Power Transformer Neutral Side
* Spare Terminal (Open)
2.3 Auxiliary Relay Operation
It may be desirable to coordinate fan operation of the central
heating/cooling system with dehumidifier fan operation. The
DEH 3000R contains a relay that provides this ability.
The relay terminals labeled NC, COM and NO operate according
to the following chart:
FAN COM to NO COM to NC
ON CONNECTED OPEN
OFF OPEN CONNECTED
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
NO
COM
NC

Common uses (assuming standard thermostat wiring colors as
noted):
Lock-out the A/C during dehumidifier fan operation
This will turn off the A/C whenever the dehumidifier fan runs.
1. Wire the Yellow thermostat terminal to the NC terminal on
the DEH 3000R.
2. Run the Yellow wire from the A/C unit to the COM terminal
on the DEH 3000R.
Energize the A/C central fan during dehumidifier fan
operation
To automatically run the A/C FAN when the dehumidifier fan
runs.
1. Attach a second Green wire to the FAN terminal on the
thermostat.
2. Connect the new Green wire to the COM terminal on the
DEH 3000R.
3. Run a wire from the Red terminal on the thermostat to the
NO (Normally Open) terminal on the DEH 3000R.
2.4 Dehumidifier
Lock-Off or
Lock-On:
A/C Sensor Feature
To automatically activate
or deactivate the
dehumidifier when the
air conditioner runs.
Activate dehumidification when the A/C is running
A voltmeter is required for the next steps to ensure the correct
wiring from the A/C transformer is used to set up the Lock-in
dehumidifier function.
1. The common wire from the existing A/C transformer (usually
Black) must be attached to the "COM" sensor terminal
between "ON-D" and "OFF-D" on the DEH 3000R.
TIP: The common wire can be identified as the wire from
the A/C transformer that reads 0 volts between it and
the Yellow air conditioning call for cooling wire.
The incorrect wire will give a 20 to 28 volt reading.
2. Another Yellow wire must be added to the thermostat Yellow
terminal and run to the “ON-D” sensor terminal on the DEH
3000R.
Deactivate dehumidification when the A/C is running
A voltmeter is required for the next steps to ensure the correct
wiring from the A/C transformer is used to set up the Lock-out
dehumidifier function.
1. The common wire from the existing A/C transformer
(usually Black) must be attached to the "COM" sensor
terminal between "ON-D" and "OFF-D" on the DEH 3000R.
TIP: The common wire can be identified as the wire from
the A/C transformer that reads 0 volts between it and
the Yellow air conditioning call for cooling wire.
The incorrect wire will give a 20 to 28 volt reading.
2. Another Yellow wire must be added to the thermostat
Yellow terminal and run to the “OFF-D” sensor terminal on
the DEH 3000R.
4
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
ON-D
COM
OFF-D
DEH 3000
HVAC THERMOSTAT
NC
COM
RED
GREEN
YELLOW
COMP
FAN
24VAC
YELLOW
A/C
UNIT
A/C
TRANSFORMER
COM
BLAC
K
DEH 3000
HVAC THERMOSTAT
NO
COM
RED
GREEN
GREEN
COMP
FAN
24VAC
A/C
UNIT
A/C
TRANSFORMER
COM
BLAC
K
YELLOW
RED
DEH 3000
HVAC THERMOSTAT
ON-DETECT
COM
RED
GREEN
COMP
FAN
24VAC
A/C
UNIT
A/C
TRANSFORMER
COM
BLAC
K
YELLOW
YELLOW
BLAC
K
DEH 3000
HVAC THERMOSTAT
OFF-DETECT
COM
RED
GREEN
COMP
FAN
24VAC
A/C
UNIT
A/C
TRANSFORMER
COM
BLAC
K
YELLOW
YELLOW
BLAC
K

2.5 Testing
Verify the wiring connections.
WARNING! ONLY CONNECT THE DMPR
TERMINAL TO THE CONTROL IF IT IS WIRED IN A
CIRCUIT THROUGH AN ELECTRIC DAMPER, OTHERWISE
TRANSFORMER DAMAGE MAY RESULT.
After checking the wiring, this short test will confirm proper
hook-up.
1. Install front cover of the DEH 3000R; connect the top first,
then the bottom.
2. Plug in the Ultra-Aire dehumidifier. The DEH 3000R should
power up.
3. Turn the DEH 3000R ON by pressing the “ON/OFF” button.
4. Verify dehumidification operation by adjusting the RH
“SETPOINT” to below the “%RH” reading on the display.
Use the down “RH” button. Confirm Ultra-Aire fan and
compressor operation. Both should be ON now.
Increase the RH “SETPOINT” on the display to well above the
“%RH” reading on the display. Press the “RH” up arrow to
increase the RH “SETPOINT”.
After running the dehumidifier compressor, the DEH 3000R
applies a 10 minute restart lockout on all functions. You will
have to wait for the restart lockout to expire.
5. Verify FAN-only operation:
a. Check the “VENT” mode on the display, it will either
be “CLOSED” or “OPEN”. If it is “CLOSED”, go to the
next step. If it is “OPEN”, press and hold the “VENT”
key until “OPEN” flashes on the display, release the key
and then press it one more time. “OPEN” will change to
“CLOSED”. Don’t touch the keys for several seconds until
it stops flashing.
b. Press and hold the “FAN” button until “AUTO” begins
flashing on the display, release it, and then press it again
to switch the fan to the “ON” setting.
c. Confirm that the Ultra-Aire fan is ON. Ultra-Aire
compressor must be OFF. Ventilation damper (if used)
should be CLOSED.
6. Verify optional VENT operation (if electric damper is installed):
a. Press and hold the “FAN” button until “ON” flashes on
the display.
b. Release the “FAN” button, then press it again to switch
fan operation to “AUTO”.
c. Press and hold the “VENT” button until “CLOSED”
flashes on the display.
d. Release the “VENT” button, then press it again to switch
vent mode to “OPEN”.
e. Confirm that the Ultra-Aire fan is ON. Ventilation damper is
OPEN. Ultra-Aire compressor must be OFF.
f. Press and hold the “VENT” button until the “OPEN”
flashes on the display.
g. Release the “VENT” button, then press it again to switch
vent mode to “CLOSED”.
WARNING! DO NOT MAKE ANY OTHER
CONNECTIONS OR TRANSFORMER DAMAGE MAY RESULT.
7. Verify any additional optional control operations such as fan
interlock or A/C lockout.
8. Proceed to the Operation section.
2.6 Troubleshooting
FOR THE HVAC PROFESSIONAL:
n No display on initial start up.
Note: This is often the result of a drained capacitor. The
capacitor will recharge once power is applied or re-applied to
the unit.
– Verify unit has power.
– Turn unit off then on.
– Disconnect the unit from power source then re-apply
power to the unit. Display should now operate.
n Function not working properly.
– Verify wiring.
– Verify voltage with voltmeter.
n Dehumidifier not working properly.
– See chart below:
5
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
Wire Terminal
Connections Connections Operation
Yellow & Blue 24V and DEHU Fan & Compressor
Yellow & Green 24V and FAN Fan Only

FOR INSTALLER & HOMEOWNER:
3. Operation
On the display screen, a solid “O” in front of any of the 3
functions (SETPOINT, VENT, FAN) indicates the function is
operating. A flashing “O” indicates it is in a wait mode and
not available at the moment. No “O” indicates the function is
currently OFF.
Solid “O” Before Indicates
SETPOINT Dehumidifier on
VENT Fresh air ventilation cycle in progress
FAN Fan on
Wait mode is a factory-programmed time period meant to
prevent short cycles. This extends the life of the dehumidifier.
When a flashing “O” is encountered, the unit is in wait mode
and IT COULD BE UP TO 10 MINUTES BEFORE OPERATION
RESUMES.
3.1 Display
• Whenever there is power to the control, it will display the time,
the day, % relative humidity, and temperature.
• When the control is actually switched ON, the %RH setpoint,
fan status, run mode (program or hold), and fresh air
ventilation status is displayed.
• When a key is pressed the display will light for approximately
½ a minute.
• The Time and Day is displayed at the top of the screen.
• RH and Temperature are displayed in real time.
• A solid “O” before the SET POINT, VENT, OR FAN indicates the
function is operating.
• A flashing “O” before the SET POINT, VENT, OR FAN indicates
the unit is in wait mode.
3.2 Setting
During the set-up process, if you make a mistake, simply
continue. You can always go back to adjust the settings. If you
leave the control alone and don’t touch any buttons for 10
seconds, the control will remember any changes made and
return to the normal display screen, allowing you to proceed to
the next step.
3.3 On/Off and Display Items
Press the “ON/OFF” button to turn the system ON or OFF.
When the system is ON, the setpoint, fan status, operation mode
(RUN or HOLD), and fresh air vent status is displayed.
When the system is OFF, the control will display the time, day,
%RH, and temperature.
When the unit is shipped, it is in manual (hold) mode.
3.4 Setting Clock Time
1. Press and hold the “CLOCK” button. The hour display will
flash. Release the button.
2. Use the up/down “RH” buttons to change the value.
3. Press the “CLOCK” button again and the minute display will
flash. Use the “RH” buttons to change the value.
4. Press the “CLOCK” button again and AM or PM will flash.
Use the “RH” buttons to change the value.
5. Press the “CLOCK” button again and the day display will
flash. Use the “RH” buttons to change the value.
6. Don’t touch any buttons for several seconds until the display
stops flashing, this will save your settings. If you need to
change anything, go back to step #1.
3.5 Adjusting the Relative Humidity “SETPOINT”
The DEH 3000R senses the ambient relative humidity (%RH) of
the space where the remote sensor is located. It comes factory
preset to hold 50% relative humidity.
6
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

The relative humidity “SETPOINT” (desired RH to be
maintained) operates the dehumidifier function of the Ultra-Aire
dehumidifier. It has no effect on the optional VENT (fresh air
ventilation) or FAN (household air recirculation) functions if they
are being used.
Operation
The standard range that the dehumidifier holds around your
“SETPOINT” is 3%. With a setpoint of 50%, the dehumidifier
will run until the relative humidity reaches 47%. The
dehumidifier will then switch off until the relative humidity
reaches 53%.
If the setpoint is higher than the ambient relative humidity, the
space does not need to be dehumidified, so the dehumidifier
will not run.
Example: Setpoint: 50% RH
Current condition: 45% RH –The dehumidifier will be off (no “O”
indicator will be displayed).
If your setpoint is below the ambient condition, the dehumidifier
will be on and “O” will display.
Example: Setpoint: 50% RH
Current condition: 55% RH –The dehumidifier will be on (“O”
displayed).
3.6 Temperature Cutout Programming
Dehumidifiers produce heat when dehumidifying and depending
upon outside conditions, the ventilation function may also
introduce warm air. Some conditions may introduce enough
heat to drive household temperatures up. The DEH 3000R
temperature cutout feature disables all Ultra-Aire operations if
household temperatures reach the cutout setpoint.
In most installations this feature will not need to be used (the
cutout is factory set to 99°F). If a lower temperature cutout
is desired, program the setpoint by pressing and holding the
“PROGRAM ENTER” button until the “PROGRAM” screen
appears. Press the up/down “RH” buttons until “TEMP
CUTOUT” highlighted. Then press the “PROGRAM ENTER”
button again to select it. Now use the “RH” up or “RH” down
buttons to adjust the setpoint. Press “PROGRAM ENTER” to
return to the home screen.
Personal Settings Reference List
Please record your settings here.
Function Factory Setting My Setting
SETPOINT (%RH) 50%
VENT Closed
FAN Auto
TEMP CUTOUT 99°
3.7 Fan Setting and Operation
Use the “FAN” button to change the fan operation. There are 2
choices for fan operation: “ON” or “AUTO”. The factory preset
is “AUTO”.
“ON” –The fan in the Ultra-Aire dehumidifier will run
continuously. This does not affect either the dehumidification
or ventilation functions of the system. The system may or may
not be ventilating or dehumidifying while the fan is running. This
setting is commonly used for maximum air filtration and/or air
recirculation.
“AUTO” – Indicates the fan will run when the DEH 3000R calls
for dehumidification or ventilation. If the control has not called
for dehumidification for 3 hours, the control will automatically
run the dehumidifier fan for 10 minutes.
After a dehumidification cycle, the fan automatically shuts off
for 10 minutes. This pause allows the water to drain from the
dehumidifier.
A solid “O” indicates the fan is operating. A flashing “O”
indicates the fan is in a wait mode. No “O” indicates the fan is
OFF.
To set the operation:
1. Press and hold the “FAN” button. The current fan setting will
begin to flash on the display. Release the button.
2. Press the “FAN” button to toggle between the “ON” and
“AUTO” modes.
7
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

With the fan in the “AUTO” mode, the fan will operate only
when needed by other functions of the system. The fan will
remain OFF unless the system is dehumidifying or ventilating.
The fan always runs during dehumidification and ventilation and
the fan “O” icon will be lit. To completely turn the system OFF,
use the “ON/OFF” button as described earlier.
3.8 Damper Operation and Ventilation,
Manual (Hold) Mode
The “VENT” setting controls the ventilation function of the
system. It has no control over the dehumidification function. In
order to provide ventilation, the motorized damper must be open
and the fan must be running. The controller takes care of these
two functions automatically so that whenever the damper is
open, the fan is running.
The ventilation indicator “O” will be displayed whenever the
unit is ventilating. The fan operation indicator “O” will also be lit.
There are three damper operation modes:
1. “OPEN” – hold mode: The damper will be open and the
dehumidifier fan will be continuously operating to introduce
fresh air into the space. Use this mode for continuous fresh
air ventilation. The fan is always on when the damper is open.
2. “CLOSED” – hold mode: The damper will never open, and
the dehumidifier will not ventilate. The fan will still operate
normally for recirculation and dehumidification.
3. “PROGRAMMED” mode: The DEH 3000R will operate the
motorized damper and the dehumidifier fan according to the
programmed ventilation schedule (Section 3.9).
The factory preset for the “VENT” setting is “CLOSED”.
To set “OPEN” – hold or “CLOSED” – hold ventilation
operation:
1. Press the “VENT” button. The current setting will begin to
flash on the display. Release the button.
2. Press the “VENT” button again to switch between “OPEN”
and “CLOSED”.
3. Leave the control alone for 10 seconds and your settings will
be saved.
3.9 Damper Operation and Ventilation,
Programmed Ventilation
This example shows the system in program mode (denoted by
the schedule 15 minutes on, 5 minutes off and the word RUN in
the lower right corner of the display).
The DEH 3000R will operate fresh air ventilation according to
your ventilation program. The control needs to be programmed
to turn the ventilation function ON and OFF at the desired
intervals. This is done by programming the ventilation timer.
There are two programs available for ventilation:
1. Monday through Sunday
2. Monday through Friday & Saturday/Sunday
Each block of days has a morning schedule and a night
schedule. Morning is the first 12 hours of the day and night is
the second 12 hours.
Each schedule has:
• A “START” time when the ventilation schedule begins,
• An “OPEN FOR” duration for the amount of time the damper
stays open in 5 minute intervals, from 0 to 60,
• And “CLOSED FOR” duration which closes the damper for a
specified time in 5 minute intervals from 0 to 60.
Setting the Ventilation Program:
1. Press the “PROGRAM ENTER” button until the following
menu appears:
8
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

2. Using the up/down “RH” buttons, highlight “PROGRAM”
and select it by pressing the “PROGRAM ENTER” button.
The following menu appears:
You can select from:
“MON-FRI” “SAT-SUN” for separate weekday and weekend
schedules, or “MON-SUN” which gives you equal weekday and
weekend schedules.
3. Using the Up/Down “RH” buttons, highlight and then select
one of the two choices. The example given shows how to
program separate weekday and weekend schedules. The same
method is used if you choose the other program.
Example menu when you select “MON-FRI” “SAT-SUN”:
1. Enter the starting time for weekdays using the up/down “RH”
buttons to change the time.
2. Press the “PROGRAM ENTER” button to switch to the
“OPEN FOR” setting. Using the up/down “RH” buttons,
change the duration that the damper will ventilate fresh air.
3. Press the “PROGRAM ENTER” button to switch to the
“CLOSED FOR” setting. Using the up/down “RH” buttons,
change the duration that the damper will remain closed
between ventilation cycles.
For the example given, starting at 8:00AM in the morning, the
control will ventilate fresh air for 15 minutes then stop for 15
minutes. This schedule of 15 minutes open, 15 minutes closed
will continue until the start time of the night schedule.
Morning schedule is available anytime from 12:00AM until
11:59AM.
Night schedule is available anytime from 12:00PM until
11:59PM.
4. Press “PROGRAM ENTER” again to go to the “MON-FRI”
night schedule. Repeat the steps listed above for this and the
“SAT-SUN” day and night schedules.
When you have finished programming your schedule (either the
7-day version or the weekday/weekend split version), use the
down “RH” button to highlight the EXIT option and then press
“PROGRAM ENTER” to select it.
Running the Ventilation Program:
Press and hold the “PROGRAM ENTER” button until the
“PROGRAM” screen appears.
Use the down “RH” button to highlight “RUN PROGRAM”:
Then press “PROGRAM ENTER” to select it. The display will
appear as follows:
9
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

5.1 Remote Sensor Usage
IMPORTANT!
The use of spray paint on the sensor housing may damage
the sensor and is not covered by the product warranty.
The remote sensing option is used when an installation
requires mounting the DEH 3000R out of the conditioned
space or when it is desired to specifically monitor and
control the conditions at a particular location in a larger
conditioned space.
Both the need for and location of the remote sensor should
be determined by a heating/cooling professional. In most
installations, the onboard sensor in the DEH 3000R will be
sufficient to monitor and control the conditioned space.
5.2 Install and Wiring Instructions
1. Routing signal wires:
You will be required to supply and route 24 gauge, 4
conductor solid wire (2-line telephone wire) between the
DEH 3000R controller and the remote sensor location. The
wiring run should be no longer than 100 ft. Avoid routing
this interconnect wire parallel to high voltage wiring.
Maintain a distance of 2 ft. or more from high voltage lines.
2. Sensor connection:
The sensor can be mounted to a wall or ceiling surface.
Ideal sensor location is 5 ft. above the floor. Wires should
exit through a ½” diameter hole in the mounting surface at
the mounting location. Use the provided splice connectors to
connect the 4 wires from the remote sensor to the user-
supplied interconnect wire. Be sure to keep proper colors
attached to each other.
3. Sensor mounting:
You will need two screws to mount the sensor. Use the two
slotted holes to mount the base of the sensor to the wall and
then snap the cover into place.
4. Controller connection:
Use the provided splice connectors to connect the 4 wires
from the DEH 3000R to the user-supplied interconnect wire.
Be sure to keep the proper colors attached to each other.
Continue with the installation as described in the rest of this
manual.
10
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
5.0 DEH3000R — Remote sensor option. This section is applicable only to customers who have
purchased a remote sensor package. The standard DEH 3000 controller does not offer remote
functionality.

11
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
Dehumidifier & Ventilation System Controller
DEH3000R
DEH3000R
WARRANTOR:
Therma-Stor LLC
4201 Lien Rd
Madison, WI 53704
Telephone: 1-800-533-7533
WHO IS COVERED: This warranty extends only to
the original residential end-user of the DEH 3000R
Dehumidifier & Ventilation System Controller, and may
not be assigned or transferred.
FIRST YEAR WARRANTY: Therma-Stor LLC warrants
that, for one (1) year the DEH 3000R Dehumidifier &
Ventilation System Controller will operate free from any
defects in materials and workmanship, or Therma-Stor
LLC will, at its option, repair or replace the defective
part(s), free of any charge.
END-USER RESPONSIBILITIES: Warranty service must
be performed by a Servicer authorized by Therma-
Stor LLC. If the end-user is unable to locate or obtain
warranty service from an authorized Servicer, he should
call Therma-Stor LLC at the above number and ask for
the Therma-Stor LLC Service Department, which will
then arrange for covered warranty service. Warranty
service will be performed during normal working hours.
The End-user must present proof of purchase (lease)
upon request, by use of the warranty card or other
reasonable and reliable means. The end-user is
responsible for normal care. This warranty only applies
to residential applications and does not cover any
defect, malfunction, etc. resulting from misuse, abuse,
lack of normal care, corrosion, freezing, tampering,
modification, unauthorized or improper repair or
installation, accident, acts of nature or any other cause
beyond Therma-Stor LLC's reasonable control.
LIMITATIONS AND EXCLUSIONS: If any DEH 3000R
Dehumidifier & Ventilation System Controller part is
repaired or replaced, the new part shall be warranted
for only the remainder of the original warranty period
applicable thereto (but all warranty periods will be
extended by the period of time, if any, that the DEH
3000R Dehumidifier & Ventilation System Controller is
out of service while awaiting covered warranty service).
UPON THE EXPIRATION OF THE WRITTEN WARRANTY
APPLICABLE TO THE DEH 3000R Dehumidifier &
Ventilation System Controller OR ANY PART THEREOF,
ALL OTHER WARRANTIES IMPLIED BY LAW, INCLUDING
MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, SHALL ALSO EXPIRE. ALL WARRANTIES
MADE BY THERMA-STOR LLC ARE SET FORTH HEREIN,
AND NO CLAIM MAY BE MADE AGAINST THERMA-STOR
LLC BASED ON ANY ORAL WARRANTY. IN NO EVENT
SHALL THERMA-STOR LLC, IN CONNECTION WITH THE
SALE, INSTALLATION, USE, REPAIR OR REPLACEMENT
OF ANY DEH 3000R Dehumidifier & Ventilation System
Controller OR PART THEREOF BE LIABLE UNDER
ANY LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR
CONSEQUENTIAL DAMAGES INCLUDING WITHOUT
LIMITATION WATER DAMAGE (THE END-USER SHOULD
TAKE PRECAUTIONS AGAINST SAME), LOST PROFITS,
DELAY, OR LOSS OF USE OR DAMAGE TO ANY REAL OR
PERSONAL PROPERTY.
Some states do not allow limitations on how long an
implied warranty lasts, and some do not allow the
exclusion or limitation of incidental or consequential
damages, so one or both of these limitation may not
apply to you.
LEGAL RIGHTS: This warranty gives you specific legal
rights, and you may also have other rights which vary
from state to state.

4201 Lien Rd • Madison, WI 53704
Phone: 608-222-5301 • Fax: 608-222-1447
www.thermastor.com • sales@thermastor.com
Information in this document is subject to change without notice. No part of this document
may be reproduced or transmitted in any form or by any means, electronic or mechanical,
for any purpose, without the express written permission of Therma-Stor LLC. © 2007
Therma-Stor LLC. All rights reserved.
DEH 3000R Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
This manual suits for next models
1
Table of contents
Other thermastor Controllers manuals