Thomas&Betts AFM-FAS Series User manual

INSTALLATION INSTRUCTIONS:
(Floor Box)
STEP 1
Orient AFM-FAS Series Floor Box so that the knock out (K.O.)
plates are aligned with the Conduit Space of the Raised Floor
Panel. The Retainer Clips must be flush against the side of the
floor box prior to placing the box into the floor. This is to ensure
the floor box is centered inside the raised floor panel (see Fig. A).
AFM-FAS Series Floor Boxes are to be used with AFM-FAS-C-BLK (black) or AFM-FAS-C-GRY (gray) Covers
(4) 2” x 1” Knock Outs
(K.O.’s) for Data Cables
STEP 2
All four Mounting Tabs must be flat against the top surface of
Raised Floor Panel. Locate both Retainer Clips (see Fig. B). Once
the floor box is in place, use a screwdriver to secure Retainer
Clips by tightening the Screw located on top of the Mounting Tab
clockwise to secure the Retaining Clip (see Fig.B). The Floor Box
should not be able to move once secured properly.
FIG. B
AFM-FAS SERIES ACCESS FLOOR MODULE
Installation Instructions
Cat. Nos. AFM-FAS-B and AFM-FAS-B-CII
TA04494 C Page 1 of 4
CAUTION
Read all Instructions before installing
the AFM Floor Box.
WARNING
RISK OF SHOCK, DISCONNECT POWER
BEFORE INSTALLATION.
Wire Tunnel
(Sold Separately)
AFM-FAS Series Access Floor Modules
Device Panels
(Sold Separately)
AFM-FAS-B
(4) 1/2 K.O.’s
AFM-FAS-B-CII
(2) Panels for 10-Pin
Modular Connector
Retainer Clip
K.O. Plate Floor Box
Conduit
Space
Raised Floor
(Not Included)
Retainer
Clip
FIG. A
Mounting
Tab
Retainer Clip & Screw
Raised
Floor Panel

ACTIVATION:
(Floor Box)
STEP 3
Remove the 1/2 K.O. Plate (Figure C) or 10-Pin Modular
Connector Plate (Figure C.1) from inside of Floor Box by
removing screw and lifting Plate out of slot.
AFM-FAS-B
Remove the knock-out(s) as required from the 1/2 K.O. Plate
(see Figure C). If K.O. Plate is bent, straighten before installing
conduit. Pull conduit through the openings in Floor Box and
Plate, and install using appropriate conduit fitting. Reinstall
the Plate to the Floor Box.
AFM-FAS-B-CII
Use the 10-Pin Modular Connector Plate(s) (see Figure C.1).
Install Connector (not shown) to Plate. Reinstall the Plate to
the Floor Box.
NOTE: A Blank Plate is provided for applications where only
one side of the Floor Box is activated.
STEP 4
OPTION A: Electrical Power Only
Connect wires to the electrical device(s) and mount to the
appropriate Device Panel (see Fig. D). When mounting an
additional device, remove the Device Knockout.
OPTION B: Data Only
Remove 1/2 K.O. Plate or 10-Pin Modular Connector Plate,
and oval knockouts as required.
OPTION C: Electrical and Data
See STEP 5 and STEP 6 . Voltage-divider(s) AFM-FAS-DIV
required (sold separately).
TA04494 C Page 2 of 4
FIG. D
Device Panel
(Sold Separately)
Knockout for
low voltage
cables
FIG. C
1/2 K.O. Plate
Slot
Conduit Fitting
FIG. C.1
Device
Knockout
Electrical
Device(s)
Mounting
Screws
Mounting
Nuts
Electrical
Conduit
K.O. Plate

TA04494 C Page 3 of 4
STEP 5 (Option C -Electrical and Data)
Install the Voltage-divider (AFM-FAS-DIV) in the marked location
of the Floor Box (see Figures E.1 and E.2). Electrical power
will be on side where the 1/2 K.O. Plate or 10-Pin Modular
Connector Plate is mounted. The oval knockout on the other
side of the Voltage-divider should be removed to allow passage
of data cable. Make certain back edge of Voltage-divider is up
against inside vertical wall of Floor Box. The Device Panel (not
shown) will secure the Voltage-Divider in place.
Optional Wire Tunnel, AFM-FAS-WT (sold separately) can be
used to extend power to the other Device Panel on opposite
side of Floor Box (see Step 6).
STEP 6 (Option C-Electrical and Data)
Use Wire Tunnel, AFM-FAS-WT, under one of the following
conditions (see Figure G):
A. Extending power from one Device Panel to the other
Device Panel on other side of Floor Box.
B. Power Device is not accessible to 1/2 K.O. Plate or
10-Pin Modular Connector Plate because of the
Voltage-divider.
Remove the knockouts for the Wire Tunnel from the Device
Panels (see Figure F.1). Place electrical wires under Wire
Tunnel and install as shown in the figure. Secure in place
using the Device Panels (see Figure F.2).
Voltage Divider
(Sold Separately)
Mark Location for
Voltage Divider
Wire for
Power
Open K.O. for
low-voltage
cable
Low-Voltage
Cable to right
side of Wire
Tunnel
Power to left
side of Wire
Tunnel
FIG. E.1
FIG. E.1
FLOOR
BOX
FLOOR
BOX
FIG. F.1
FIG. F.2
Device Panel
Knock Out for
Wire Tunnel
Wire Tunnel
(Sold Separately)
Device Panel
Electrical Wires
Wire Tunnel
(Installed)
FLOOR
BOX
FLOOR
BOX

© 2009 Thomas & Betts. All Rights Reserved.
WARRANTY: Thomas & Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability of this product for the user’s intended application.
Thomas & Betts warrants that this product will be free from defects in materials and workmanship for a period of two (2) years following the date of purchase. Upon prompt notication of any
warranted defect, Thomas & Betts will, at its option, repair or replace the defective product or refund the purchase price. Proof of purchase is required. Misuse or unauthorized modication of the
product voids all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED,
INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY
FOR BREACH OF THE ABOVE WARRANTY IS LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER NO CIRCUMSTANCES WILL THOMAS & BETTS BE
LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
TA04494 C Page 4 of 4
Elec. Wires *Wire Tunnel
Floor Box
*Elec.
Device
*Voltage
Dividers
*Device
Panels
Data
Side
Data
Side
FIG. G *SOLD SEPARATELY
TOP VIEW
11-3/4”
10-1/2”
FIG. H
STEP 7 (Finished Floor)
Create opening in finished floor, 10-1/2” x 11-3/4”. For wood or tile floors, notch out around the four mounting tabs to allow easy
removal of the Floor Box.
Install AFM-FAS Series Cover (sold separately). See Figure H.
NOTES:
Popular Control Unit manuals by other brands

WAGO
WAGO 750-1405/040-000 manual

Mitsubishi Electric
Mitsubishi Electric QJ71MB91 user manual

Ventus
Ventus VS 10-75 CG OPTIMA Operation and maintenance manual

Eaton
Eaton Crouse-hinds series instruction manual

Allen-Bradley
Allen-Bradley ControlLogix 1756-OV32E installation instructions

Watts
Watts Lync DigiTemp Jr V23 User guide/instruction manual