ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service informa-
tion pack upon completion of work.
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
WARNING:
Installer’s Guide
General Information 1
Unit Installation 3
Upflow 3
Downflow 4
Horizontal Left 6
Horizontal Right 7
Duct Connections 8
Refrigerant Piping 8
Brazing to Evaporator 8
Condensate Drain Piping 9
Electrical — Power Wiring 10
Control Wiring 10
Hook-up Diagrams 11
Outline Drawing 14
Checkout Procedures 16
Contents
A. GENERAL INFORMATION
WARNING
!
SAFETY HAZARD
THIS INFORMATION IS FOR USE BY INDIVIDUALS
HAVING ADEQUATE BACKGROUNDS OF ELECTRICAL
AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO
REPAIR A CENTRAL AIR CONDITIONING PRODUCT
MAY RESULT IN PERSONAL INJURY AND/OR PROP-
ERTY DAMAGE. THE MANUFACTURER OR SELLER
CANNOT BE RESPONSIBLE FOR THE INTERPRETA-
TION OF THIS INFORMATION, NOR CAN IT ASSUME
ANY LIABILITY IN CONNECTION WITH ITS USE.
CAUTION
!
To prevent shortening its service life, the air handler
should not be used during the finishing phases of con-
struction. The low return air temperatures can lead to
the formation of condensate. Condensate in the pres-
ence of chlorides and fluorides from paint, varnish,
stains, adhesives, cleaning compounds, and cement
creates a corrosive condition which may cause rapid
deterioration of the cabinet and internal components.
These instructions do not cover all variations in sys-
tems or provide for every possible contingency. Should
further information be desired or particular problems
arise which are not covered sufficiently by this manu-
al, contact your local distributor or the manufacturer
as listed on the air handler nameplate.
These air handlers are shipped from the factory in the
upflow or horizontal right configuration and are fully
convertible to downflow or horizontal left. Refer to Sec-
tion B beginning on page 3 for additional information.
INSPECTION
Check carefully for any shipping damage. This must be
reported to and claims made against the transporta-
tion company immediately. Check to be sure all major
components are in the unit. Any missing parts should
be reported to your supplier at once, and replaced with
authorized parts only.
CAUTION
!
Cardboard packing material must be removed from in-
side the blower assembly before starting the unit.
Failure to do so may cause indoor blower motor failure.
INSTALLATION LIMITATIONS & RECOMMENDATIONS
The general location of the air handler is normally
selected by the architect, contractor and/or home own-
er for the most effective application and satisfaction.
NOTE: CONDENSATION MAY OCCUR ON THE SUR-
FACE OF THE AIR HANDLER WHEN INSTALLED IN AN
UNCONDITIONED LOCATION. WHEN UNITS ARE IN-
STALLED IN UNCONDITIONED SPACES, VERIFY THAT
ALL ELECTRICAL AND REFRIGERANT LINE PENE-
TRATIONS ON THE AIR HANDLER ARE SEALED COM-
PLETELY.
18-GE08D1-10
Convertible Air Handlers
2 – 5 Ton
4TEC3F24B1000A
4TEC3F36B1000A
4TEC3F42C1000A
Available in French Canadian (FC)
4TEC3F48B1000A
4TEC3F60B1000A
© 2012 Trane 2 18-GE08D1-10
Installer’s Guide
static pressure of the air handler. Reference ACCA
Manual D, Manual S and Manual RS along with
the air handler Product Data and Service Facts for
additional information.
5. The area around refrigerant lines must be sealed
and electrical inlets need to be sealed at both the
low and the high voltage.
6. It is recommended that the outline drawing be stud-
ied and dimensions properly noted and checked
against selected installation site. By noting in ad-
vance which knockouts are to be used, proper clear-
ance allowances can be made for installation and
possible future service.
7. Allow a minimum of 21 inches clearance in front
of the air handler to permit service and removal of
filter.
8. When air handler with supplementary heater is to
be installed in the downflow position on combusti-
ble flooring an accessory subbase (TAYBASE101 for
4TEC3F24-36B or TAYBASE100 for 4TEC3F42B-
60B) must be used. See Figure 1.
9. If supplementary heat is to be added, power supply
must be sufficient to carry the load. In addition,
minimum air flow settings, unit and duct clearanc-
es to combustible material must be maintained as
stated on the air handler rating nameplate.
These air handlers are suitable for installation in a clos-
et, alcove or utility room with free, non-ducted, air re-
turn, using the area space as a return air plenum. With
ducted supply air, if the minimum clearances to com-
bustible materials and service access are observed, the
above installations are suitable.
This area may also be used for other purposes, includ-
ing an electric hot water heater – but in no case shall
a fossil fuel device be installed and/or operated in
the same closet, alcove or utility room.
In addition, these air handlers are suitable for installa-
tion in an attic, garage or crawl space with ducted sup-
ply and return air.
This equipment has been evaluated in accordance with
the Code of Federal Regulations, Chapter XX, Part 3280
or the equivalent. “SUITABLE FOR MOBILE HOME
USE.”
For proper installation the following items must be
considered:
1. If adequate power is available and correct accord-
ing to nameplate specifications.
2. Insulate all ducts, particularly if unit is located
outside of the conditioned space.
3. Pursuant to Florida Building Code 13-610.2.A.2.1,
this unit meets the criteria for a factory sealed air
handler.
4. To ensure maximum efficiency and system perfor-
mance, the existing supply and return duct system
static pressures must not exceed the total available
B
A
JOIST
JOIST
JOISTS
HEADER
JOISTS
HEADER
NAILS
REAR
FLANGE
FRONT OF
UNIT
HEADER
1"
NAILS
HEADER
MIN. SPACING TO
ANY COMBUSTIBLE
MATERIAL.
1"
APPROX. 3/4" FLANGES ON FIELD
FABRICATED DUCT OR PLENUM
ONE INCH DUCT SPACERS
FLOOR
SUBBASE
UNIT
AIR HANDLER SUBBASE
1
FLOOR OPENING - SIZE
MODEL NO. A B
TAYBASE100 23-3/4 14-13/16
TAYBASE101 21-3/4 14-13/16
TAYBASE102 26-3/4 14-13/16
18-GE08D1-10 3
Installer’s Guide
CAUTION
!
For air handlers not equipped with a factory installed
electric heater, a field installed heater is available from
Trane. Only heaters built by Trane are approved for use
in the air handler. These heaters have been designed
and tested in accordance with UL standards to provide
safe and reliable operation. A list of approved heaters
is provided on the air handler rating nameplate. Heat-
ers that are not factory approved could cause damage
and are not covered under equipment warranty.
NOTE: If air handler is used WITHOUT a supplementary
electric heater, a sheetmetal plate is required to cover
the open hole in the airflow system. See Figure 2. Also
seal the cabinet air tight where the wire enters.
10. If the unit is installed without a return air duct,
applicable local codes may limit this air handler
to installation only in a single story residence and
within conditioned space.
11. If the outdoor unit is to be installed later, or by
others, then installation of the air handler must be
made to allow access for refrigerant lines, or attach
refrigerant lines to air handler when installing.
12. Make sure there are provisions for installing con-
densate drain lines.
13. If side, front or rear return is required, air han-
dler must be elevated or placed on a plenum (TAY-
PLNM100 for 4TEC3F24 - 60B). Connecting return
duct directly to the side, front or rear of the cabi-
net is not approved.
14. Route refrigerant and condensate drain lines away
from air handler so they do not interfere with ac-
cess panels and filters.
15. When external accessories are used, the additional
height and width requirements must be considered
in the overall space needed.
16. These units are not approved for outdoor installa-
tion.
17. These units are approved for draw-through appli-
cation only.
NOTE: No atomizing style humidifier is allowed in the
return plenum with the use of this unit.
18. Flow-through Bypass Humidifiers
Excessive bypass air may cause water blow-off,
which will adversely affect system operation and air
cleaner performance. To verify bypass airflow, fol-
low the Bypass Humidifier Pre-Installation Check-
out and Set-Up Procedures available through your
local distributor. Ask for publication number 18-
CH37D1-1.
Steam and Flow-through Fan Power Duct-
mounted Humidifiers
Follow the humidifier installation instructions.
These should only be installed on the supply air side
of the system.
B. TWO PIECE CABINET DISASSEMBLY
(OPTIONAL)
NOTE: For easier installation into tight areas, the 4
and 5 ton air handlers can be disassembled and reas-
sembled after moved to an attic or other space.
Steps for disassembly and reassembly (See Figures 3
and 4)
1.Disconnect wiring.
2.Remove center bracket.
3.Remove blower assembly.
4.Remove coil.
5.Cut foil tape - minimum 3" foil tape.
6.Remove top 8 screws. See Figure 3.
7.Lift upper section.
8.Set air handler in place.
9.Attach screws - insure gaskets are aligned
along flange.
10.Use foil tape to seal - use minimum 3" foil tape.
11. Insert coil.
12.Reinstall blower assembly.
13.Reinstall center bracket.
14.Reconnect wiring.
NOTE: In Downflow, remove coil before blower by
reversing steps 4 and 5.
C. UNIT INSTALLATION
UPFLOW
a. For maximum efficiency, the horizontal drip
tray should be removed. See Figures 6, 7 and 8.
Drip tray removal requires that the coil be re-
moved by sliding the coil out on the coil channel
supports. The drip tray is detached by remov-
ing the two screws at the drain pan and the two
screws holding the two brackets at the top of
the coil. Remove the two screws holding the two
brackets at the top of the coil. Remove drip tray
by gently breaking the seal between the drip
tray and drain pan.
From Dwg. 21B140413
4" 6"
17"
1"
3/8"
1/4" HOLES (4)
ACCESSORY BAY99X123
IF AIRHANDLER IS USED WITHOUT A FACTORY FURNISHED
SUPPLEMENTARY HEATER, A PLATE IS REQUIRED TO COVER
THE OPEN HOLE IN THE AIR FLOW SYSTEM
2
4 18-GE08D1-10
Installer’s Guide
b. Remove the factory installed baffle assembly
from the apex of the coil by using a 5/16" nut-
driver to remove the screws. Replace this
baffle with the factory supplied narrow coil
baffle using the screws removed previously (See
Figure 5). Reinstall coil assembly.
▲CAUTION
!
When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.
c. Position unit on Pedestal or other suitable foun-
dation. If Pedestal is not used, a frame strong
enough to support the total weight must be pro-
vided. Provide a minimum height of 14 inches
for proper unrestricted airflow.
d. If a return air duct is connected to the air han-
dler, it must be the same dimensions as shown
in the outline drawing.
e. On units with sheetmetal returns: Return ple-
num should be flanged. Sheetmetal screws must
be 1/2" in length or shorter.
f. No sheetmetal screws may be used to attach re-
turn duct work on the side of the unit.
g. Pedestal and unit should be isolated from the
foundation using a suitable isolating material.
h. Openings where field wiring enters the
cabinet must be completely sealed. Location
of power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electri-
cal knockouts. See Figure 11.
i. After ductwork connections are made, seal air-
tight and per local codes.
DOWNFLOW
a. For maximum efficiency, the horizontal drip
tray should be removed. See Figures 6, 7 and 8.
Tray removal requires that the coil be removed
by sliding the coil out on the coil channel sup-
ports. The tray is detached by removing the
two screws at the drain pan and the two screws
holding the two brackets at the top of the coil.
Remove drip tray by gently breaking the seal
between the drip tray and drain pan.
2 PIECE WRAPPER SPEAR
4
Remove
and
Discard
Replace
with
Narrow
Baffle
FOR MAXIMUM EFFICIENCY ON
HORIZONTAL LEFT,
UPFLOW AND DOWNFLOW
5
CLOSEUP OF SPEAR LOCATIONS
3
1
2
3
4
SCREWS 5-8
LOCATED ON
LEFT SIDE
18-GE08D1-10 5
Installer’s Guide
b. Remove the factory installed baffle assembly
from the apex of the coil by using a 5/16" nut-
driver to remove the screws. Replace this baffle
with the factory supplied narrow coil baffle us-
ing the screws removed previously (See Figure
5).
▲CAUTION
!
When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.
NOTE: INSTALLATION OF THE DOWNFLOW BAFFLE
KIT INCLUDED WITH UNIT IS REQUIRED ON DOWN-
FLOW APPLICATIONS. SEE FIGURE 9.
c. Remove front shield by removing screws on
right side. Make sure to reinstall front shield
after baffle changes. See Figure 9.
d. Detach the coil from the drain pan by removing
4 screws as shown in Figure 9.
e. Remove the front triangular baffle from the coil
and install the 1/2" wide gasket provided per
Figure 9. Trim the gasket length to fit the baffle.
Reinstall the baffle to coil, with gasket material
compressed against the coil.
f. Install the water blow-off baffles provided on
each side of the coil with the flange at the top as
shown in Figure 9. The bottom of the baffle is to
be as close to the bottom of the coil as possible.
g. Install the 7/8" wide gasket in each side of the
drain pan as shown in Figure 9.
h. Place the 2 water diverter baffles (5 ton mod-
el only) underneath the coil on the inside edge
of the drain pan, Figure 9. Fill the bend in the
baffle which fits the inner edge of the drain pan
with non-acetic acid RTV type adhesive/sealant
before installing the baffle.
i. The unit is then placed with the blower side down
and the coil is replaced on the coil channel sup-
ports with the drain connections at the bottom.
The unit is now in downflow position with front
access. Do not reattach coil support tab.
j. When air handler with supplementary heater
is to be installed in the downflow position on
combustible flooring an accessory subbase (TAY-
BASE101 for 4TEC3F24B-36B or TAYBASE100
for 4TEC3F42B-60B) must be used. See Figure
1.
HORIZONTAL DRIP TRAY REMOVAL
7
DRIP TRAY BRACKET REMOVAL
8
DRIP PAN FOAM REMOVAL
6
6 18-GE08D1-10
Installer’s Guide
k. If a return duct is connected to the air handler,
it must be the same dimensions as the return
opening shown in the outline drawing.
l. On units with sheet metal returns: Return ple-
num should be flanged. Sheetmetal screws must
be 1/2" in length or shorter.
m. No sheetmetal screws may be used to attach
return ductwork on the side of the unit.
n. Openings where field wiring enters the cab-
inet must be completely sealed. Location of
power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electri-
cal knockouts. See Figure 11.
o. After ductwork connections are made, seal air-
tight and per local codes.
HORIZONTAL LEFT
a. To convert the unit to horizontal left, front ac-
cess, slide the coil out on the coil channel sup-
ports and rotate the complete coil 180 degrees.
b. For maximum efficiency and Customer ease
of filter maintenance, it is recommended that a
properly sized remote filter grille be installed
for horizontal applications. Airflow should not
exceed the face velocity of the filter being used.
The factory installed filter should then
be removed from the unit. Remove the fac-
tory installed baffle assembly from the apex of
the coil by using a 5/16" nutdriver to remove
the hex head screws. Replace this baffle with
the factory supplied narrow coil baffle using
the screws removed previously. See Figure 5.
▲CAUTION
!
When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.
c. The coil is then inserted back into the cabinet on
the opposite side coil channel supports. The unit
is now horizontal left with front access. Do not
reattach coil support tab.
d . If the unit is suspended, it must be supported
from the bottom near both ends as well as the
middle to prevent sagging. The service access
must remain unobstructed. If the unit is sup-
ported along the length of the front and back
with rails, the air handler only needs to be sus-
pended at both ends. See Figure 10.
DOWNFLOW BAFFLE KIT
X
X
7/8" GASKET
SCREWS TO
REMOVE COIL
SCREWS TO
REMOVE COIL
DISCARD HORIZONTAL
DRIP TRAY
1/2" GASKET
INSIDE SURFACE
OF BAFFLE
7/8" GASKET
SECT. X-X
(TYP. BOTH SIDES)
FILL WITH SEALANT
WATER
BLOW-OFF
BAFFLES
ATTACH WITH
2 SCREWS
EACH SIDE
WATER
DIVERTER
BAFFLES
(5TON ONLY)
9
18-GE08D1-10 7
Installer’s Guide
k. Openings where field wiring enters the
cabinet must be completely sealed. Location
of power entry is shown on the outline drawing.
Use 2.5" clear stickers provided to seal all un-
used electrical knockouts. See Figure 11.
l. After ductwork connections are made, seal air-
tight and per Local codes.
HORIZONTAL RIGHT
a. For maximum efficiency and Customer ease
of filter maintenance, it is recommended that a
properly sized remote filter grille be installed
for horizontal applications. Airflow should not
exceed the face velocity of the filter being used.
The factory installed filter should then be
removed from the unit.
b. Unit is shipped from the factory in the upflow or
horizontal right configuration. Unit conversion
is not required.
c. If the unit is suspended, it must be supported
from the bottom near both ends as well as the
middle to prevent sagging. The service access
must remain unobstructed. If the unit is sup-
ported along the length of the front and back
with rails, the air handler only needs to be sus-
pended at both ends. See Figure 10.
If the unit is not suspended it must be support-
ed as mentioned above and isolated carefully
to prevent sound transmission. Vibration isola-
tors (purchased locally) must be placed under
the unit.
e. It is always recommended that an auxiliary
drain pan be installed under a horizontal air
handler (See Condensate Piping) to prevent
possible damage to ceilings.
f. Isolate the auxiliary drain pan from the unit or
from the structure.
g. Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line) and
terminate according to National and Local
codes.
h. If a return duct is connected to the air handler,
it must be the same dimensions as the return
opening shown in the outline drawing.
i. On units with sheetmetal returns: Return
plenum should be flanged. Sheetmetal screws
must be 1/2" in length or shorter.
j. No sheetmetal screws may be used to attach
return ductwork on the side of the unit.
Rail
0
Electrical Knockout Sticker Sheet
q
8 18-GE08D1-10
Installer’s Guide
d. If the unit is not suspended it must be isolated
carefully to prevent sound transmission. Vibra-
tion isolators (purchased locally) must be placed
under the unit.
e. It is always recommended that an auxiliary
drain pan be installed under a horizontal air
handler (See Condensate Drain Piping) to pre-
vent possible damage to ceilings.
f. Isolate the auxiliary drain pan from the unit or
from the structure.
g. Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line) and
terminate according to local codes.
h. If a return duct is connected to the Air Handler,
it must be the same dimensions as the return
opening shown in the outline drawings.
i. On units with sheetmetal returns: Return ple-
num should be flanged. Sheetmetal screws must
be 1/2" in length or shorter.
j. No sheetmetal screws may be used to attach re-
turn ductwork on the side of the unit.
k. Openings where field wiring enters the cab-
inet must be completely sealed. Location of
power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electri-
cal knockouts and cage nut openings. See Fig-
ure 11.
l. After ductwork connections are made, seal air-
tight and per local codes.
D. DUCT CONNECTIONS
The supply and return air ducts should be connected to
the unit with flame retardant duct connectors.
Convertible duct flanges are provided on the discharge
opening to provide a “flush fit” for 3/4" or 1-1/2" duct
board applications. See the Outline drawing for sizes
of the duct connections. After the duct is secured, seal
around the supply duct to prevent air leakage.
NOTE: No sheetmetal screws may be used to attach re-
turn ductwork on the side.
NOTE: On units with sheetmetal returns: Return ple-
num should be flanged. Sheetmetal screws must be
1/2" in length or shorter. See Figure 12.
NOTE: If the convertible duct flanges are not used, they
must be removed and discarded for proper airflow.
NOTE: Any duct board return connection can be made
to the sides of the unit using tape or mastic.
E. REFRIGERANT PIPING
IMPORTANT:
Refrigerant piping must be routed to maintain service ac-
cess to blower compartment and provide easy removal of
filter access panel and filter.
1. Refrigerant connections are made outside the cabi-
net.
NOTE: TXV bulb MUST be protected (wrap a wet rag
around the suction line between the TXV bulb and the
braze joint) or removed, while brazing the tubing. Over-
heating of the sensing bulb will affect the functional
characteristics and performance of the air handler.
NOTE: The area around refrigerant lines must be sealed
and electrical inlets need to be sealed at both the low
and the high voltage.
2. Installation of refrigerant lines is covered in the in-
stallation instructions packaged with the outdoor
unit. Evacuation, leak testing and brazing pro-
cedures are included in those instructions. Read
those instructions before starting installation of re-
frigerant lines.
NOTE: Torque specification for TXV equals 1/6 turn past
finger tight.
F. BRAZING TO EVAPORATOR
NOTE: A brazing shield is provided in the information
pack accompanying this unit. This shield fits over the
refrigerant fittings while brazing. Wet the shield before
brazing. See Figure 13.
IMPORTANT:
Do NOT unseal refrigerant tubing until ready to cut and fit
refrigerant lines.
1. Remove the sealing caps from indoor coil field con-
nections.
2. Field supplied tubing should be cut square, round
and free of burrs at the connecting end. Clean the
tubing to prevent contaminants from entering the
system.
Flange Attachment
w
18-GE08D1-10 9
Installer’s Guide
G. CONDENSATE DRAIN PIPING
NOTE: Make certain that the unit has been installed in
a level position to ensure proper draining.
The indoor blower is downstream of the evaporator coil
which creates a negative pressure at the condensate
drain connections during operation. The condensate
drain connections in front of the indoor coil are 3/4"
NPT. The lower connection is the primary drain. See
Figure 14.
Two secondary drain connections are provided for the
different orientations (See Figure 14). The lower of the
two should be connected as a backup to prevent con-
densate overflow by a blocked primary drain. The weep
hole in center of drain coupling area should be sealed
with caulk or RTV except in downflow unless second-
ary drain is connected.
For proper drainage of condensate, the following steps
should be followed:
1. The primary drain line must be trapped with a
minimum of 2" water seal as shown in Figures 15
& 16. Do not use preformed 3/4" PVC running
traps.
The use of Field fabricated or manufactured traps
as shown in Figures 15 & 16 is acceptable. The
manufactured trap shown in Figure 15 allows for a
float switch option to be added. Refer to the manu-
facturer’s data and instructions for details.
2. The trap must be located within 4 feet of the air
handler drain outlet connection.
3. It is recommended that a clean-out tee or cross be
installed in the primary drain line for future main-
tenance (See Figures 15 & 16)
3. Run refrigerant tubing into the stub sockets of in-
door unit coil. Refrigerant line openings must
be completely sealed.
4. Braze and evacuate according to indoor and out-
door installation instructions.
5. Seal around refrigerant lines.
PAINTED AREAS OF UNIT MUST BE SHIELDED
DURING BRAZING.
r
4. Do not use reducing fittings in the condensate
drain lines.
5. Slope the drain lines downward a minimum of 1/4"
per foot.
6. Insulate the primary drain to prevent sweating
where dew point temperatures may be met.
7. Provide means for drainage to prevent win-
ter freeze-up of condensate line.
8. Do not connect the drain line to a closed drain sys-
tem.
9. Use Teflon®tape on the air handler drain line con-
nections! Do Not Use pipe joint compound or PVC/
CPVC cement!
It is always recommended that an auxiliary drain pan
be installed under a horizontally installed air handler.
Connect the auxiliary drain line to a separate drain
line (no trap is needed in this line) and terminate ac-
cording to local codes.
NOTE: DO NOT use a torch or flame near the plastic
drain pan coupling.
NOTE: DO NOT tighten the drain pipe excessively. Sup-
port the condensate piping and traps outside the unit
to prevent strain on the drain coupling.
BRAZE SHIELD
e
3/4" NPT
Primary drain
connection
3/4" NPT
Secondary
drain con-
nection
Seal weep
hole except
for Downflow
configuration
10 18-GE08D1-10
Installer’s Guide
2. The selection of wire and fuse sizes should be made
according to the Minimum Branch Circuit Ampac-
ity and the Maximum Overcurrent Device listed on
the unit nameplate.
3. Field wiring diagrams for electric heaters and unit
accessories are shipped with the accessory.
4. Wiring must conform to National and Local codes.
Ground unit per Local codes with good safety pro-
cedures.
If an electric heater is not installed, the Knockout
Plate provided in the Accessory Kit MUST be in-
stalled on the air handler and the conduit termi-
nated to it. The electrical connections are made
using the two power leads and ground wire con-
nections which are located near the discharge of
the blower. Openings where field wiring en-
ters the cabinet must be completely sealed.
Location of power entry is shown on the outline
drawing. Use 2.5" clear stickers to seal all unused
electrical knockouts.
NOTE: If air handler is used with or without a heater,
the 7/8" electrical entry hole as well as any other cabi-
net penetrations must be sealed air tight.
I. CONTROL WIRING
1. Connect wiring between indoor unit, outdoor unit
and Comfort Control. The use of color-coded low-
voltage wires is recommended.
2. A low voltage terminal board is provided for con-
trol wiring, and is located on the left side of the
cross brace in the center of the unit.
3. Field wiring diagrams are provided which show
the low voltage wiring hook-up for a single speed
cooling only system (with supplementary heaters)
and a heat pump system (with supplementary
heaters). Plug in type electrical connectors are
provided for use with supplementary heaters.
IMPORTANT:
When supplementary heaters are installed, inspect to
insure that all packaging material has been removed.
NOTE: Direct drive motors have bearings which are
permanently lubricated and under normal use lubrica-
tion is not recommended.
HOOK-UP DIAGRAMS
2" MINIMUM
2" MINIMUM
MANUFACTURED TRAPS
EZT-105
t
FIELD FABRICATED TRAP
2" MIN.
2" MIN.
CAP OR PLUG
Trap must be within 4'
of air handler condensate
drain connection.
Close as possible
y
H. ELECTRICAL — POWER WIRING
1. These Air Handlers are shipped from the factory
wired for 230 volts. The units may be wired for 208
volts. Follow instructions on unit wiring diagram
located on blower housing and in the Service Facts
document included with the unit.
WARNING
!
ELECTRICAL SHOCK HAZARD
LOCK OUT UNIT DISCONNECT SWITCH IN OPEN PO-
SITION BEFORE SERVICING UNIT. FAILURE TO FOL-
LOW THIS WARNING COULD RESULT IN PROPERTY
DAMAGE, PERSONAL INJURY, OR DEATH.
18-GE08D1-10 11
Installer’s Guide
4TEC AIR HANDLER WITH HEAT PUMP WITH SUPPLEMENTAL HEAT
From Dwg. B801082 Rev. 2
12 18-GE08D1-10
Installer’s Guide
4TEC AIR HANDLERS WITH SINGLE SPEED COOLING UNIT, 1 STAGE HEAT
From Dwg. B801083 Rev. 2
18-GE08D1-10 13
Installer’s Guide
4TEC AIR HANDLER WITH SINGLE SPEED COOLING UNIT, 2 STAGE HEAT
From Dwg. B801081 Rev. 2
14 18-GE08D1-10
Installer’s Guide
OUTLINE DRAWING FOR 4TEC3F24-60B
MODEL NO. A B C D E F G FLOW
CONTROL
GAS LINE
BRAZE
LIQ LINE
BRAZE
4TEC3F24B 43 21.50 19.50 15.66 3.62 1.89 N/A TXV/NB 5/8 5/16
4TEC3F36B 45 21.50 19.50 17.66 3.62 1.89 N/A TXV/NB 3/4 3/8
4TEC3F42B 51.75 23.50 21.50 22.41 3.62 1.89 N/A TXV/NB 3/4 3/8
4TEC3F48B
4TEC3F60B
57.90 23.50 21.50 27.57 3.62 1.89 32.39 TXV/NB 7/8 3/8
18-GE08D1-10 15
Installer’s Guide
4TEC AIR HANDLER DIMENSIONAL DATA
H
W
21.0"
4TEC3F48B & 60B
are two piece cabinets
MODEL H W
4TEC3F24B 43.00 21.50
4TEC3F36B 45.00 21.50
4TEC3F42C 51.75 23.50
4TEC3F48B 57.90 23.50
4TEC3F60B 57.90 23.50
Trane
6200 Troup Highway
Tyler, TX 75707
www.trane.com
For more information contact
your local dealer (distributor)
The manufacturer has a policy of continuous product and product data improvement, and it reserves the right
to change design and specifications without notice.
SUPPLEMENTARY HEATERS CHECKOUT PROCEDURES,
IF USED DOES HEATER REQUIRE A SPECIAL CIRCUIT?
SEE “LIMITATIONS AND RECOMMENDATIONS”
1. Be sure the disconnect switch is “OFF”, and safety label (if any) is attached....................................... [ ]
2. Check on field wiring for tight connections and grounding according to codes ..................................... [ ]
3. Check circuit protection for proper size per nameplate specifications................................................... [ ]
4. Check control box panel — in place and secured..................................................................................... [ ]
NOTE: OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL
SYSTEM.
CHECKOUT PROCEDURES
After installation has been completed, it is recommended that the Air Handler be checked against the following
checklist.
1. Make sure power is “OFF” at power
disconnect switch................................................. [ ]
2. Check all field wiring for tight connections. See
that grounding of unit is in accord with code .... [ ]
3. Make sure unit suspension (if used) is secure
and that there are no tools or loose debris in,
around or on top of the unit ................................ [ ]
4. Check all duct outlets; they must be open and
unrestricted ......................................................... [ ]
5. Check drain lines and be sure all joints are tight
.............................................................................. [ ]
6. Make sure secondary drain pan is installed ...... [ ]
7. Check power supply for correct requirements
per unit nameplate.............................................. [ ]
8. Check filters for proper size. Inform owner
of proper procedure for removal and
reinstallation ....................................................... [ ]
9. Energize the system and carefully observe its
operation; make any necessary adjustment....... [ ]
10. Instruct owner, engineer (if possible) on proper
operating procedure and leave Use and Care
Manual with owner ............................................. [ ]
Installer’s Guide
J.CHECKOUT PROCEDURE
1. Check the Air Handler operation and installation
in accordance with these instructions below.
2. “Operational Procedure” for the system instal-
lation can be found in the outdoor unit installer
guide and will be compatible with this Air Han-
dler.
CAUTION
!
Cardboard packing material must be removed from in-
side the blower assembly before starting the unit.
Failure to do so may cause indoor blower motor fail-
ure.
WARNING
!
ELECTRICAL SHOCK WARNING
LOCK OUT UNIT DISCONNECT SWITCH IN OPEN PO-
SITION BEFORE SERVICING UNIT. FAILURE TO FOL-
LOW THIS WARNING COULD RESULT IN PROPERTY
DAMAGE, PERSONAL INJURY, OR DEATH.
The following warning complies with State of California law, Proposition 65.
▲WARNING: This product contains
fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
cause respiratory, skin, or eye irritation.
PRECAUTIONARY MEASURES
●Avoid breathing fiberglass dust.
●Use a NIOSH approved dust/mist respirator.
●Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye
protection.
●Wash clothes separately from other clothing: rinse
washer thoroughly.
●Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact - Flush eyes with water to remove dust.
If symptoms persist, seek medical
attention.
Skin Contact - Wash affected areas gently with soap
and warm water after handling.

This manual suits for next models

5

Other Trane Air Handler manuals

Trane 4YCC4024E1060 User manual

Trane

Trane 4YCC4024E1060 User manual

Trane IntelliPak WEHE Series Installation and operating instructions

Trane

Trane IntelliPak WEHE Series Installation and operating instructions

Trane A4AH5E19A1B30A Assembly instructions

Trane

Trane A4AH5E19A1B30A Assembly instructions

Trane 7 Series Installation and operating instructions

Trane

Trane 7 Series Installation and operating instructions

Trane Oxbox J4HP4018A1 User manual

Trane

Trane Oxbox J4HP4018A1 User manual

Trane TRANE Quantum CLCPEuro Operating and safety instructions

Trane

Trane TRANE Quantum CLCPEuro Operating and safety instructions

Trane UCCA Installation and operating instructions

Trane

Trane UCCA Installation and operating instructions

Trane LPC User manual

Trane

Trane LPC User manual

Trane 4TWL9048A1000A Service manual

Trane

Trane 4TWL9048A1000A Service manual

Trane Horizon OADG Series Installation and operating instructions

Trane

Trane Horizon OADG Series Installation and operating instructions

Trane AM7A0C36H31SA Series Service manual

Trane

Trane AM7A0C36H31SA Series Service manual

Trane 5 Series Service manual

Trane

Trane 5 Series Service manual

Trane TWG018A140C Assembly instructions

Trane

Trane TWG018A140C Assembly instructions

Trane A4AH4E24A1B60A User manual

Trane

Trane A4AH4E24A1B60A User manual

Trane BAYAHEMIKIT001A User manual

Trane

Trane BAYAHEMIKIT001A User manual

Trane 4TEE3C01A1000A Assembly instructions

Trane

Trane 4TEE3C01A1000A Assembly instructions

Trane OXBOX JMM4A0A18S21SAA Assembly instructions

Trane

Trane OXBOX JMM4A0A18S21SAA Assembly instructions

Trane PCC-1L-3210-4-7.5 User manual

Trane

Trane PCC-1L-3210-4-7.5 User manual

Trane 4YCC4024E1060A User manual

Trane

Trane 4YCC4024E1060A User manual

Trane Performance Climate Changer Installation and operating instructions

Trane

Trane Performance Climate Changer Installation and operating instructions

Trane LWHA Owner's manual

Trane

Trane LWHA Owner's manual

Trane Performance Climate Changer PSCA Installation and operating instructions

Trane

Trane Performance Climate Changer PSCA Installation and operating instructions

Trane Hyperion AM8A0A24V21CA Series Service manual

Trane

Trane Hyperion AM8A0A24V21CA Series Service manual

Trane 4TGB3F18A Assembly instructions

Trane

Trane 4TGB3F18A Assembly instructions

Popular Air Handler manuals by other brands

Mitsubishi Heavy Industries AHU-KIT-SP Technical manual

Mitsubishi Heavy Industries

Mitsubishi Heavy Industries AHU-KIT-SP Technical manual

IV Produkt Envistar Flex Assembly instructions

IV Produkt

IV Produkt Envistar Flex Assembly instructions

American Standard TAM9A0A24V21DA Installer's guide

American Standard

American Standard TAM9A0A24V21DA Installer's guide

BLAUBERG BlauAir CFV Series user manual

BLAUBERG

BLAUBERG BlauAir CFV Series user manual

Stulz Tecnivel ClimaPac Installation, operation and maintenance manual

Stulz Tecnivel

Stulz Tecnivel ClimaPac Installation, operation and maintenance manual

Vents MICRA 100 user manual

Vents

Vents MICRA 100 user manual

Zehnder Rittling ComfoCool Q600 installation manual

Zehnder Rittling

Zehnder Rittling ComfoCool Q600 installation manual

Dantherm Combo Cooling 6000/900 Service manual

Dantherm

Dantherm Combo Cooling 6000/900 Service manual

BLAUBERG KOMFORT EC D5B 180 user manual

BLAUBERG

BLAUBERG KOMFORT EC D5B 180 user manual

Zehnder Rittling ComfoClime 24 Service manual

Zehnder Rittling

Zehnder Rittling ComfoClime 24 Service manual

Dantherm DanX 2/4 Service manual

Dantherm

Dantherm DanX 2/4 Service manual

nilan Compact P installation instructions

nilan

nilan Compact P installation instructions

Swegon CASA R5 Smart Installation instruction

Swegon

Swegon CASA R5 Smart Installation instruction

Bosch BVA 15 Series installation instructions

Bosch

Bosch BVA 15 Series installation instructions

ActronAir CRV13AS/EVV13AS owner's manual

ActronAir

ActronAir CRV13AS/EVV13AS owner's manual

Flexit Albatros S10R Installation and Maintenance

Flexit

Flexit Albatros S10R Installation and Maintenance

Zehnder Rittling ComfoSpot 50 manual

Zehnder Rittling

Zehnder Rittling ComfoSpot 50 manual

murprotec CTA 4 Instructions for use

murprotec

murprotec CTA 4 Instructions for use

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.