Trane X13790901010 Installation and operating instructions

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
Wireless Comm
January 2014 BAS-SVX40B-EN
WCI
WCI WCI WCI
WCI
WCI
WCI
WCI
WCI
WCI WCI
WCI
WCI
WCI
Installation, Operation,
and Maintenance

© 2014Trane All rights reserved BAS-SVX40B-EN
Introduction
Read this manual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
Copyright
This document and the information in it are the property of
Trane and may not be used or reproduced in whole or in
part, without the written permission ofTrane.Trane
reserves the right to revise this publication at any time and
to make changes to its content without obligation to notify
any person of such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
The three types of advisories are defined as follows:
WARNING Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTIONsIndicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
NOTICE: Indicates a situation that could result in
equipment or property-damage only.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertaken
could result in death or serious injury.Technicians, in
order to protect themselves from potential electrical,
mechanical, and chemical hazards, MUST follow
precautions in this manual and on the tags, stickers,
and labels, as well as the instructions below:
• Before installing/servicing this unit, technicians
MUST put on all PPE recommended for the work
being undertaken. ALWAYS refer to appropriate
MSDS sheets and OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection, and handling recommendations.
• If there is a risk of arc or flash, technicians MUST put
on all PPE in accordance with NFPA 70E or other
country-specific requirements for arc flash
protection, PRIOR to servicing the unit.

Table of Contents
BAS-SVX40B-EN 3
Introduction ............................................................ 2
Warnings, Cautions, and Notices ..................................... 2
Important Environmental Concerns ............................... 2
Important Responsible Refrigerant Practices ....................... 2
General Information .................................................... 5
Product Description ................................................ 5
Dimensions for Indoor Model ........................................ 6
Specifications and Agency Compliance ............................... 7
Device Firmware Requirements ...................................... 8
Location Considerations ................................................. 9
Maximum Wire Length ......................................... 9
Installation Locations .......................................... 9
WCI Addressing ....................................................... 11
Setting Network Communication Addressing ......................... 11
Setting Wireless Zone Sensor Receiver Addressing ................... 12
Mounting and Wiring the WCI .......................................... 13
Controller Applications ............................................ 13
Repeater Applications ............................................. 17
Establishing the Network ............................................... 18
WCI LEDs and Buttons ............................................. 18
Three Ways to Establish a Wireless Network ......................... 20
Establishing the Network After Tracer SC Installation ............... 20
Establishing the Network Prior to Tracer SC Installation or Without
Tracer SC Installation ....................................... 20
WCIs as Zone Sensor Receivers ..................................... 22
Modifying the Network ................................................. 23
Adding Additional WCIs to an Existing Network ....................... 23
Adding Coordinators to a Tracer SC ................................. 23
Removing a WCI from a Network ................................... 24
Replacing a WCI on a Network ...................................... 24
Closing the Network ............................................... 24
Disbanding a Network ............................................. 24
Troubleshooting ....................................................... 25
WCI does not join network ..................................... 25
Tracer SC does not communicate with WCI ...................... 25
Sensor does not communicate with WCI ......................... 25
No communication ........................................... 26

4 BAS-SVX40B-EN
Slow communication ......................................... 26
Replacing a Failed WCI ........................................ 26
Appendix: Using the Tracer™ TU Service Tool with Wireless Networks .... 28
Requirements for Joining .......................................... 28
Joining Tracer TU with a Wireless Network .......................... 28
Managing a Wireless Network and Devices ........................... 30
Connecting to a Device ........................................ 30
Wireless Menu ............................................... 31
Wireless Zone Sensor Enable/Disable ............................ 35

BAS-SVX40B-EN 5
General Information
This section provides general information about the wireless Comm interface (WCI).
Product Description
TheTrane® Wireless Comm Interface (WCI) enables wireless communication between system
controls, unit controls, and wireless sensors for the new generation ofTrane control products.The
WCI replaces the need for communication wire in all system applications.
Types of Devices Supported by the WCI
• Tracer™ SC system controller
• Tracer™ UC210 programmable controller
• Tracer™ UC400 programmable controller
• Tracer™ UC600 programmable controller
• BCI-I: BACnet Communications Interface for IntelliPak™ systems
• BCI-R: BACnet Communications Interface for ReliaTel™ systems
• Tracer™TU
• Wireless zone sensors
Quantity of WCIs per Network
EachTrane wireless network can have a total of 31WCIs (30 member WCIs plus 1 coordinatorWCI).
Each network requires one WCI to function as network coordinator.
Quantity of Networks per Tracer SC
ATracer SC can support up to 8 wireless networks.
Notes:
• The number of WCIs that can be installed at a site is determined by the applicable
Tracer SC license, which specifies the total number of controllers.
• For information about installing aWCI on aTracer SC, see “Mounting andWiring theWCI,”
p. 13 and Figure 6, p. 15.
Automatic Network Formation
When a WCI is connected to aTracer SC, it is auto-assigned as the coordinator.To enable the
coordinator,Tracer SC must be configured for wireless communication.The coordinator WCI
opens the network to allow allWCIs having matching addresses to automatically join the network.
If noTracer SC is present, a centrally located WCI connected to a programmable controller or a BCI
must be designated to act as the coordinator.You can manually set the coordinatorWCI so all WCIs
having matching addresses automatically join the network.
Note: For additional information, see “Establishing the Network,” p. 18.
Wireless Zone Sensors
TheWCI also communicates withTrane wireless zone sensors, eliminating the need for standalone
receivers.
Wired Zone Sensors
Systems using Wireless Comm can also use wired zone sensors.
Network Security
The WCI uses standard ZigBee™ Building Automation security practices by the use of AES128
encryption, keys, and device authentication.

6 BAS-SVX40B-EN
General Information
Part Numbers
Available WCI models are listed by part number:
Dimensions for Indoor Model
The dimensions of the WCI enclosure are as follows:
Part number BAY Number IndividualPart
Number Description
X13790901010 BAYWCII001 SEN01806 Indoor model includes wiring harness and mounting
hardware intended for indoor installations.
X13790902010 (NO BAY #) SEN01807 For flush-mount applications. (Wiring harness not
included.)
X13790941010 BAYWCII200A MOD02422 Outdoor model includes wiring harness and mounting
hardware intended for outdoor installations.
0.650 in. (16.50 mm)
2.896 in. (73.55 mm)
3.386 in. (86.00 mm)
2.480 in. (63.00 mm)
1.344 in. (34.14 mm)
0.236 in. (6.00 mm)
1.419 in. (36.03 mm)
4.677 in. (118.80 mm)
0.118 in. (3.00 mm)
2.620 in. (66.55 mm)
0.581 in. (14.76 mm)
R0.71 in. (R1.80 mm) TYP

BAS-SVX40B-EN 7
General Information
Specifications and Agency Compliance
Specifications
Operating temperature -40 to 158ºF (-40 to 70ºC)
Storage temperature -40 to 185ºF (-40 to 85°C)
Storage and operating humidity range 5% to 95% relative humidity (RH), non-condensing
Voltage 24 Vac/Vdc nominal ± 10%
If using 24 Vac, polarity must be maintained.
Receiver power consumption <2.5 VA
Housing material Polycarbonate/ABS (suitable for plenum mounting), UV protected,
UL 94: 5 VA flammability rating
Mounting 3.2 in (83 mm) with 2 supplied mounting screws
Range(a) Open range: 2,500 ft (762 m) with packet error rate of 2%
Indoor: Typical range is 200 ft (61 mm); actual range is dependent on the environment.
See BAS-SVX55 for more detail.
Output power North America: 100 mW
Radio frequency 2.4 GHz (IEEE Std 802.15.4-2003 compliant) (2405–2480 MHz, 5 MHz spacing)
Radio channels 16
Address range Group 0–8
Network 1–9
Mounting
Fits a standard 2 in. by 4 in. junction box (vertical mount only). Mounting holes are spaced
3.2 in. (83 mm) apart on vertical center line. Includes mounting screws for junction box
or wall anchors for sheet-rock walls. Overall dimensions: 2.9 in. (74 mm) by 4.7 in.
(119 mm)
Wireless protocol ZigBee PRO—ZigBee Building Automation Profile, ANSI/ASHRAE Standard 135-2008
Addendum q (BACnet™/ZigBee)
Agency compliance
United States
UL listed: UL 94, 5 VA flammability rating and UL916.
Energy Management Equipment FCC CFR47, Sec. 15.247 & subpart E, Digital Modulation
Transmission with no SAR (FCC ID: TPF-251701).
This device complies with part 15 of the FCC Rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired
operation.
Changes or modifications not expressly approved by the manufacturer for compliance
could void the user’s authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following
measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.

8 BAS-SVX40B-EN
General Information
Device Firmware Requirements
The following table lists the minimum firmware levels required to allow devices to participate in
a wireless network.
Canada
CSA-C22.2 No. 205-M1983 Signal Equipment Industry Canada
(IC: 6178A-251701)
Cet appareil est conforme à la partie 15 du règlement du FCC. Son fonctionnement fait
l’objet des deux conditions suivantes : (1) Cet appareil ne produit pas de brouillages
nuisibles, et (2) cet appareil doit pouvoir recevoir n’importe quel type d’interférence, y
compris les brouillages pouvant occasionner un fonctionnement non désiré.
Les changements et les modifications n’ayant pas été approuvés expressément par le
fabricant comme étant conformes, pourraient rendre nulle le droit de l’utilisateur à faire
fonctionner cet équipement.
Remarque: Cet équipement a été testé et reconnu comme étant conforme aux limites des
appareils numériques de classe B, tel qu’indiqué dans la partie 15 du règlement du FCC.
Ces limites ont été établies afin de fournir un niveau de protection raisonnable contre le
brouillagenuisible dans lesinstallationsrésidentielles.Cet appareilproduit, utilise,et peut
aussi émettre des fréquences radioélectriques. Si celui-ci n’est pas installé et utilisé
conformément aux instructions, il peut provoquer des brouillages nuisibles dans les
communications radioélectriques. L’absence d’interférence n’est cependant pas garantie
dans toutes les installations. Si cet équipement provoque des brouillages nuisibles dans
la réception des communications radioélectriques ou de télévision (ceci pouvant être
déterminéen allumant etenéteignantl’équipement), l’utilisateurest encouragé àessayer
de corriger l’interférence en utilisant un ou plusieurs des moyens suivants :
• Réorienter ou changer l’emplacement de l’antenne réceptrice.
• Éloigner l’équipement et le récepteur l’un de l’autre.
• Brancher l’équipement à une prise de courant se trouvant sur un circuit différent de
celui sur lequel le récepteur est branché.
• Faire appel aux services du fournisseur ou d’un technicien radio/TV qualifié.
IEEE/radio frequency range
IEEE 802.15.4-2003, IEEE Standard for Information Technology—Telecommunications
and information exchange between systems—Local and metropolitan area networks—
Specific requirements, Part 15.4: Wireless Medium Access Control (MAC) and Physical
Layer (PHY) Specifications for Low Rate Wireless Personal Area Networks (LR-WPANs)
(a)Range values are estimated transmission distances for satisfactory operation. Actual distance is job specific and must be determined during site eval-
uation. Placement of the WCI is critical to proper system operation. In most general office space installations, distance is not the limiting factor for
proper signal quality. Signal quality is more greatly affected by walls, barriers, and general clutter. Note that sheetrock walls and ceiling tiles offer little
restriction to the propagation of the radio signal throughout the building as opposed to concrete or metal barriers. More details information, including
wiring schematics, are available at http://www.trane.com.
Device Minimum Level
Required
Tracer SC 3.6.xxx
UC210 (Any version)
UC400 V6.00.007.mod
UC600 V4.00.027.mod
BCI-I V25.00.014.mod
BCI-R V5.02.02.mod
Tracer TU 8.2
TU Adapter V1.00.024.mod

BAS-SVX40B-EN 9
Location Considerations
To provide the best signal strength between associated wireless devices and to reduce the number
of WCIs needed for an application, mount WCIs in direct, unobstructed, line-of-sight paths. Locate
WCIs so that the number of metal and concrete barriers between pairs of devices is minimal. In
general, sheetrock walls and ceiling tiles are not of concern.
For more detailed information aboutWCI placement, see theWireless Comm Network Design Best
Practices Guide (BAS-SVX55).
The WCI produces very low levels of electromagnetic (RF) energy. To avoid exposure, keep the WCI a minimum of 8
in. (20 cm) from your body.
Maximum Wire Length
The maximum wire length between the WCI and its power source is 656 ft (200 m).
Note: The connector that comes with the WCI is one meter in length.
Installation Locations
Unit controller
For a unit controller installation, the most typical WCI mounting location is on the sheet metal
enclosure of the unit controller or HVAC equipment housing.
Coordinator Location
For optimum network performance and reliability, the coordinator WCI should be centrally located
within the network. See theWireless Comm Network Design Best Practices Guide (BAS-SVX55) for
more detail.
Repeaters overcome out-of-radio-range issues
A WCI can be installed to function as a repeater to bridge the signal between a WCI that is out of
the radio range of the other WCIs (see “Repeater Applications,” p. 17). When choosing a location
for a repeater WCI, consider the availability of a 24 Vac/Vdc power source to meet its power
requirement.
Note: A repeater extends comm link radio communications only. It cannot be used to extend
wireless zone sensor communications.
Coordinator and repeater placement recommendations on sites without VAV
boxes
The recommended mounting location for RTU installations is in the return plenum, above the roof
penetration.This location provides the best overall sensor and communication link quality, and
makes access to the WCI easier than below the roof deck for improved serviceability.
In RTU/VAV systems, there is adequate network density minimizing the need for repeaters.
However, the increased distance between devices on single zone rooftops means that repeaters
will be required in many of these installations. Unlike VAV boxes, which may be within line of site,
RTUs have greater obstructions between devices, such as steel roof decks and return ducts.
CAUTION
Avoid exposure to electromagnetic energy!
The WCI produces very low levels of electromagnetic energy. To avoid exposure, keep the WCI
a minimum of 8 in. (20 cm) from your body.
Risque d’exposition à l’énergie électromagnétique!
L’interface de communication (WCI) sans fil produit de l'énergie électromagnétique de très bas
niveau. Afin d'empêcher toute exposition, maintenez-la à au moins 20 cm (8 pouces) de votre
corps.

10 BAS-SVX40B-EN
Location Considerations
Consequently, the design range between these devices is shorter. Based on our tests, we
recommend a design range of 100 feet.

BAS-SVX40B-EN 11
WCI Addressing
This section describes theWCI addressing scheme and procedure. WCIs can be ordered either pre-
addressed or without addresses. Verify pre-addressed WCI prior to installation.
Setting Network Communication Addressing
Important: Addresses must be set on WCIs before applying power to them.
Follow this procedure to set the WCI address for network communication. Figure 1 illustrates the
addressing scheme used for WCIs.The illustration shows four networks and twoTracer SCs, with
eachTracer SC communicating on two networks. See Table 1, p. 12 for address settings.
1. Set the left (GRP) rotary address switch for each WCI that is in the sameTracer SC group to an
identical number. (ATracer SC group refers to all of the networks that communicate with the
sameTracer SC.)
2. Set the right (NET) rotary address switch for each WCI that is to be on the same network to an
identical number. If there are multiple networks in aTracer SC group, each network in that group
must have a unique number.
Note: The NET address (ranging from1-8)must match the wireless link onTracer SC.
Figure 1. WCI addressing example
Note: The Wireless Comm Network Design Best Practices Guide (BAS-SVX55) provides an
example of network addressing from a floor plan perspective.
UC/BCI
Tracer SC-1
UC/BCI
WCI WCI
GRP NET
NET
GRP NET
111
11
WCI
WCI WCI
GRP NET
GRP
NET
GRP NET
12 12
12
WCI
WCI WCI
GRP NET
GRP
NET
GRP NET
21 21
21
WCI
WCI WCI
GRP NET
GRP
NET
GRP NET
22 22
22
WCI
UC/BCI UC/BCI UC/BCI UC/BCI UC/BCI UC/BCI
GRP
1
Tracer SC-2
Network Network
Network
Network
Tracer SC Group Tracer SC Group
1
2
3
4
5
6
7
8
9
0
NET
GRP
1
2
3
4
5
6
7
8
9
0

12 BAS-SVX40B-EN
WCI Addressing
*Must match the wireless link network number. (See “Tracer SC Addressing” in the Wireless Comm Network Design Best Prac-
tices Guide (BAS-SVX55.)
Setting Wireless Zone Sensor Receiver Addressing
AWCI that is installed on a unit controller as a wireless communication interface can also function
as a zone sensor receiver.To set up this function, follow this procedure:
WARNING
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure that power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
1. Make sure that AC power is disconnected from the unit controller that the WCI is installed on.
2. Choose unit controller and wireless zone sensor addresses so that no two wireless zone sensors
sharing the same address are within radio range of each other. (Addresses above 127 may be
used for Wireless Comm systems. See the Wireless Comm Network Design Best Practices
Guide (BAS-SVX55) for more information.)
3. Set the address on the wireless zone sensor to match the rotary address setting on the unit
controller (see Figure 2).
Note: The numbers on the WCI rotary address switches are oriented differently from those on
the unit controllers, as the illustration indicates.
Figure 2. Wireless zone sensor addressing
Table 1. Address settings
Function/Purpose GRP NET
Trane BACnet communication and receiver for sensor 1–8 1–8*
Receiver for sensor only 1–9 0
Return to default configuration 0 0
Future use 9 1–8
Future use 0-9 9
1
2
2
3
4
5
6
7
8
9
0
1
3
4
5
6
7
1
2
3
4
5
6
7
8
9
0
8
9
0
UC Wireless zone
sensor
Match to UC
1
2
3
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
ADDRESS
4
WCI as zone
sensor receiver
Be careful to match
addresses rather than the
direction of the arrows.

BAS-SVX40B-EN 13
Mounting and Wiring the WCI
Follow these instructions:
Controller Applications
1. Remove power from the controller that is to have the WCI wired to it.
2. Remove the WCI cover by firmly pressing the thumb tab at the bottom of the cover and pulling
the cover away from the back plate (Figure 3).
Note: If present, remove the security screw before removing the cover.
Figure 3. Removing the cover
3. Secure the backplate to the mounting surface using appropriate hardware. (M3.5 x 20 mm self-
drilling screws are provided.)
4. Attach the 4-connector screw terminal block on the wiring harness to the receptacle on theWCI
(Figure 4).
Figure 4. Connecting wiring harness
WARNING
Hazardous Service Procedures!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Blue = LINK +
Gray = LINK -
Black =
Red = +24 Vdc/ac

14 BAS-SVX40B-EN
Mounting and Wiring the WCI
5. Route the wires from the WCI through either:
a. The opening in the back plate (Figure 5, a).
b. The bottom exit port (Figure 5, b).
Figure 5. Routing the wires through the WCI backplate (a) or bottom exit port (b)
6. Connect the wiring harness according to the illustration that is appropriate for your application:
Note: Wiring between a WCI and a controller cannot exceed 656 ft (200 m). If the wiring
harness does not provide enough length, use 18 AWG (24 pF/ft max.) communication
wire (Trane purple wire, which is shielded).To extend both the comm link and the power,
use two pieces orTrane purple wire (4 conductors, 2 shields). Each shield needs to be
grounded at one spot.The shield should be grounded at the UC, the BCI, or the PM014.
If you power theWCI remotely, then you only need to run one piece ofTrane purple wire
(2 conductors, 1 shield) for the comm link.Trane recommends that you ground the
shield at the UC, the BCI, or the PM014.
Note:
•To wire the WCI to aTracer SC, see Figure 6, p. 15.
•To wire the WCI to a UC210, UC400, or a UC600, see Figure 8, p. 16.
•To wire the WCI to a BCI-I, see Figure 9, p. 16.
•To wire the WCI to a BCI-R, see Figure 10, p. 16.
Note: For detailed information, refer to the BACnet MS/TP Wiring and Link Performance Best
Practices andTroubleshooting Guide (BAS-SVX51)
7. Restore power to the controller.
Important: The WCI must be wired to the controller prior to power up in order to establish
network communication. If you cannot apply power to theWCI and the controller
at the same time, apply power to theWCI first. However, if you use a remote power
source to power the WCI, apply power to the WCI before applying power to the
unit controller.
8. The network is ready to be formed. Refer to “Establishing the Network,” p. 18.
(a) (b)

BAS-SVX40B-EN 15
Mounting and Wiring the WCI
Figure 6. Wiring the WCI to a Tracer SC
Figure 7. Wiring multiple WCIs to a Tracer SC
Tracer SC
PM014
WCI wiring
LINK +
LINK –
+ 24VDC
IMC– IMC+ Grou nd 2 4 Vd c
Gray = LINK -
Blue = LINK +
Black = Ground
Red = 24 Vdc
Connect both 2-connector
screw terminal blocks to
either of the IMC terminals
on the PM014.
WCI WCIWCIWCI
WCI WCIWCIWCI
Tracer SC PM014
Notes:
• A maximum of eight WCIs can be
daisy-chained to the Tracer SC.
• Use both IMC terminals on the
PM014 for wiring multiple WCIs
(see the detail in Figure 6).
• The WCIs on both links can span a
total of 200 meters.

16 BAS-SVX40B-EN
Mounting and Wiring the WCI
Figure 8. Wiring the WCI to a UC210, UC400, or a UC600
Figure 9. Wiring the WCI to a BCI-I
Figure 10. Wiring the WCI to a BCI-R
+
24
VDC
IM
C
LINK IMC
LINK+
LINK-
+24 Vdc
UC
Gray = LINK -
Blue = LINK+
Black = Ground
Red = 24 Vdc
VAC
24
BI
1
BI
2
BI
3
LINK IMC
+
24
VDC
IM
C
Jumper
LINK -
LINK +
+24 Vdc
WCI
BCI-I
Attach jumper at BI1
to enable wireless
communication. Gray = LINK -
Blue = LINK +
Black = Ground
Red = 24 Vdc
The connector is not
included with the BCI-I.
It is user-supplied. The IMC terminal is
usedtocommunicate
with an IntelliPak.
BCI-R Board
Gray = IMC–
Blue = IMC+
Slide switch to IMC
RTRM
Black = Ground
Red = 24 Vac

BAS-SVX40B-EN 17
Mounting and Wiring the WCI
Repeater Applications
Note: For more information about the use of repeaters with Wireless Comm, see the Wireless
Comm Network Design Best Practices (BAS-SVX55).
Installing a WCI to Function as a Repeater
1. Remove theWCI cover by firmly pressing the thumb tab at the bottom of the cover and pulling
the cover away from the back plate (Figure 3, p. 13).
Note: If present, remove the security screw before removing the cover.
2. Secure the backplate to the mounting surface using appropriate hardware. (M3.5 x 20 mm self-
drilling screws are provided.)
3. Address the unit.
4. Attach the 4-connector screw terminal block on the wiring harness to the receptacle on theWCI
(Figure 4).
5. Remove the blue (IMC+) and gray (IMC-) wires from the wiring harness.
6. Connect the red (24Vdc/Vac) wire and black (ground) wire through the opening in the backplate
(Figure 5a) or the bottom exit port (Figure 5b) to a 24 V power source (AC or DC).
Figure 11. Wiring a WCI as a repeater
7. Apply power to the WCI.
Changing a WCI from Device Association to Repeater
If the WCI communication wire was previously connected to a unit controller, return the WCI to its
default configuration as follows:
1. Set its rotary address switch to 0,0 (the WCI must be powered).
2. Observe its LEDs blink On briefly (<1 second). (It takes about 10 seconds for the blink to occur.)
3. Reset its rotary address switches to the correct network address.
You are now ready to add the repeater to an existing network (refer to “Adding AdditionalWCIs
to an Existing Network,” p. 23) or to proceed with establishing a new network (refer to
“Establishing the Network,” p. 18).
Note: When the repeater is added, its DIAG LED blinks constantly. This behavior is normal.
+24 VDC/VAC

18 BAS-SVX40B-EN
Establishing the Network
When all aspects of hardware installation are complete, you are ready to power up the system and
establish the network. Before you perform these tasks, ensure that all work described in the “WCI
Addressing,” p. 11 and “Mounting and Wiring the WCI,” p. 13 sections are complete. If you cannot
power up all devices at the same time, then power them up in the following order: (1)all WCIs, (2)
all Unit Controllers (UC210, UC400, UC600, BCI-I, BCI-R), (3) theTracer SC , (4) wireless zone
sensors, if present.
WCI LEDs and Buttons
Before establishing a network, you should be familiar with the layout of the WCI board, the
behavior of its LEDs, and the function of its buttons.The WCI board contains two buttons and
several LEDs.The LEDs relevant to network formation are shown in Figure 12.
Figure 12. LEDs and buttons related to network formation
NWK
SNSR
CRD
RX LINK
TX LINK
DIAG
PWR
OPEN NET
The green NWK LED:
• Illuminates on every WCI that has joined the
network.
• Flashes for 10 seconds every 2.5 minutes if the
WCI is not a member of the network.
The yellow CRD LED
illuminates on the
coordinator WCI.
The START button:
• On a network without a
Tracer SC, designates a
WCI as the network
coordinator and opens the
network for joining.
• Removes a member WCI
from the network (see
“Removing a WCI from a
Network,” p. 24).
• Disbands the network (see
“Disbanding a Network,”
p. 24).
The green SNSR LED:
• Illuminates on a WCI that functions as a zone sensor
r
and is associated with a sensor.
• Flashes slowly if not associated with a sensor.
• Flashes quickly if associated with a sensor and
the sensor button is pushed.
OPEN NET LED
• All member WCIs and
the coordinator WCI
illuminate this LED
when the network is
opened from Tracer TU
or the coordinator WCI.
• If the network is
opened from a member
WCI (Open button),
only the member WCI
illuminates its OPEN
NET LED. Any WCI
withinrangeofthisWCI
can join the network.
The OPEN NET button:
• On coordinator WCI, opens
network for 1 hour.
• On coordinator WCI, extends
time that network is open for
additional hour.
• On member WCI, opens that
WCI for 10 minutes.
• Closes open network when
pressed on the coordinator
WCI.
• Closes just the member WCI
when pressed on an open
member WCI.
Note: There are two very small LEDs at the bottom of theWCI board next to
the sensor radio chip (labeled LED1 and LED2).The red LED flashes
during a channel scan.The flashing occurs for about 1 minute after the
controller is powered up. It is always lighted when the associated
device is installed on aTracer SC.

BAS-SVX40B-EN 19
Establishing the Network
On power-up, the WCI goes through a check list and updates LED activity according to the type of
device associated with the WCI and the status of the WCI in the network.The LED flash patterns
vary depending on current conditions. LED behavior is described in Table 2.
Table 2. LED identification and interpretation
LED LED activity Indicates...
Network LED (green)
NWK
On solid WCI is a network member.
Flashes for 10 seconds every 2.5
minutes. WCI is not a member of a network.
The WCI will join a network when the NWK LED
is flashing. If there is an open network nearby
withthesamerotarysettings andthe WCIjoins
the network, the NWK LED turns on solid and
then the OPEN LED turns on solid.
Sensor LED (green)
SNSR
Flashes slowly Sensor has lost its association with the WCI.
Flashes quickly Sensor is associated with the WCI and the
sensor button has been pushed.
On solid A sensor is associated with the WCI.
Coordinator LED (yellow)
CRD On solid WCI is network coordinator.
Open Net LED (yellow)
OPEN NET
On solid Network is open for joining.
Off Network is closed.
Reception LED (yellow)
RX LINK Flickers Data is being received.
Transmission LED (green)
TX LINK Flickers Data is being transmitted.
Diagnostic LED (red)
DIAG
Flashes 50% on/off Hardware failure or failed re-flash of a radio.
Corrective action: Try updating the firmware.
Triple flash pattern. Occurs for 30
seconds after failing to join a
network.
WCI is not configured correctly, or the unit
controller, IMC communication, or a repeater is
down.
Corrective action: Cycle power.
Double flash pattern
One of the following causes:
• WCI lost MAC address on radios or WCI lost
ability to communicate with radio.
• WCI could be a repeater.
• WCI lost IMC link to the UC/BCI/PM014
Corrective Action: Cycle power to restore
communications with unit controller. MAC
address can be checked on TU >Wireless >
Advanced page when connected directly to the
controller (if UC to WCI comm is up).
If more than one condition is present, the priority is in the order listed.
Power LED (green)
PWR On solid WCI has power.

20 BAS-SVX40B-EN
Establishing the Network
Three Ways to Establish a Wireless Network
A wireless network can established:
• After aTracer SC has been installed.
• Prior toTracer SC installation.
• On a network that will not have aTracer SC installed on it.
Establishing the Network After Tracer SC Installation
If aTracer SC is installed prior to establishing the wireless network, the WCI that is installed on a
Tracer SC automatically becomes the network coordinator after power is applied to theTracer SC.
If multiple WCIs are installed on aTracer SC, each WCI forms an independent network for which
it is the coordinator.
Follow this procedure:
1. Observe the yellow CRD LED on the WCI illuminate to identify the WCI wired to theTracer SC
as the network coordinator (see Figure 12, p. 18).
2. Observe the yellow OPEN_NET LED illuminate on the coordinatorWCI.This LED remains lit for
1 hour, indicating that the network is open to allow WCIs with matching addresses to join the
network for that duration. After each WCI joins, the 1 hour timer starts over.
Note: If the network closes because the timer has expired, you can open the network for an
additional hour by pressing the OPEN_NET button on the network coordinator WCI.To
extend time on a network that has not yet closed, press the OPEN_NET button on the
coordinator to close the network, then press it again to open the network for an
additional hour. As an alternative, you can use TracerTU to open the network.
3. Observe the green NWK LED illuminate:
•On the coordinator WCI, indicating that it has joined its own network.
•On each additional WCI as it joins the network.
Note: Typically, it takes about 10 minutes for a WCI to join the network. However, the time is
dependent on the distance between the WCIs in network as well as the size and type of
structures that may exist between them.
4. After the network is formed, press the OPEN_NET button on the coordinator to close the
network if it is still open (indicated by an illuminated OPEN_NET LED).
5. To enable and configureTracer SC for the new wireless network, seeTracer SC Online Help and
the current edition of theTracer SC System Controller Installation and Setup guide (BAS-
SVX31).
Establishing the Network Prior to Tracer SC Installation or Without Tracer SC Installation
If aTracer SC has not been installed at the time that you are ready to establish the network or will
never be installed on the network, follow this procedure to establish the network.
Task 1: Activate Communication Among Existing WCIs
1. Choose a centrally located WCI that has been wired to a unit controller to become the network
coordinator.
Note: This WCI will be network coordinator temporarily, if the network is to have aTracer SC
installed on it at a later time. At that time, the WCI that is installed on theTracer SC will
become the network coordinator.
2. Press the START button for 5 seconds to establish the WCI as the coordinator and to open the
network for joining.The yellow CRD LED on the WCI illuminates to identify the WCI as the
network coordinator (see Figure 12, p. 18).
This manual suits for next models
5
Table of contents
Other Trane Recording Equipment manuals
Popular Recording Equipment manuals by other brands

Free The Tone
Free The Tone MC-3 owner's manual

Amptone Lab
Amptone Lab XY MIDIpad user manual

Mitsubishi Electric
Mitsubishi Electric DX-TL5716U installation manual

Ross
Ross OpenGear SFS-8622 Series user guide

Axel
Axel RS-USBX user manual

HomeMatic
HomeMatic HmIP-ESI-IEC Installation and operating instructions

CHD Elektroservis
CHD Elektroservis 7-401 user guide

Korg
Korg Electribe ESX-1 Quick start tutorial

Philips
Philips Respironics CoughAssist 70 Series manual

VADDIO
VADDIO Quick-Connect Universal Cat-5 CCU Installation and user guide

socomec
socomec DIRIS Digiware D-50 Installation and operating manual

Peak
Peak IPEH-003026 user manual