
Electropneumatic Transducer
The Electropneumatic Transducer incorporates
quiet low wattage poppet valves and a pressure
sensor to measure and adjust the branch line
pressure proportional to its field selectable
input. A pressure gauge provides a readout for
the branch line pressure.
Required power for the Electropneumatic Transducer
is 24 VAC or 24 VDC. The transducer is designed for
mounting on a flat surface. Dimensions are
3¼”x3
1/8” x 3” (83m x 79mm x 76mm). See figure 1.
Before installation, check to see if you received the
correct transducer. Verify ordering # 4190 1097, range
of 3 to 15 psig and pneumatic control application.
Specifications
Ordering Number 4190 1097
Supply Voltage 24
VAC
/
VDC
Air Consumption None
Operating Temperature 25° F to 150° F (4° C to 65° C)
Field Selectable Inputs 4 to 20 mA, 0 to 5
VDC
,or0to
10
VDC
Output 3 to 15 psig
Maximum Air Capacity at 15 lbs. - output 800 scim
at 20 lbs. - output 1100 scim
Ports Brass Hose Barb for ¼”
O.D.
poly tubing
Maximum Main Pressure 40 psig
Maximum Current Draw 50 mA
Agency Listing CE EMC Standards
EN50082-1/EN55014/EN60730-1
Location
Proper location of the transducer is important to
ensure accurate measurement of pressure.
IMPORTANT!
Avoid locating the transducer
in places having excessive vibration.
Mounting
The Electropneumatic Transducer’s steel
chassis design makes installation directly in a
control panel or with a snap track easy.
➊Position the transducer on a flat mounting
surface. Make sure the override buttons
and pressure gauge are accessible.
➋Mark the centers of the mounting holes.
➌At each of the marked locations, drill
holes for the mounting screws.
➍Mount the transducer to the surface with
the mounting screws.
Wiring
Air Connections
When connecting the main air supply, connect
transducer lines to clean air.
➊Connect the main air supply to the barbed
¼” (.0063m) brass connector labeled Main.
Pressure should not exceed 35 psig.
➋Connect the output air to the barbed ¼”
(.0063m) brass connector labeled
Branch. There should be a minimum of 6
to 10 feet (1.8m to 3.05m) of tubing
between the transducer and actuator.
The Trane Company
La Crosse, Wisconsin 54601-7599
An
American-Standard
Company
© American Standard Inc. 1997
1
3270 3225 Rev 2
Figure 1 Dimensions of the transducer
© 2008 Trane All rights reserved